| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.6 LAccepted-AOC | L1 | Accepted-AOC reasonable bid | |
| 2 | L2₹41.8 L+₹4.9 L (13.3%)Rejected-Finance NO 18 BHARATHI STREET WEST GANDHI NAGAR AVADI CHENNAI 600 054 | CHENNAI | THIRUVALLUR | TAMIL NADU | 600054 | L2 | Rejected-Finance NOT lOWEST | |
| 3 | L3₹49.4 L+₹12.6 L (34.2%)Rejected-Finance | L3 | Rejected-Finance NOT lOWEST | |
| 4 | L4₹50.5 L+₹13.7 L (37.2%)Rejected-Finance NO 439 AHIV ADAN 11ND FLOOR 2RD STAGE INDIRA NAGAR BANGALORE 560 075 | BENGALURU URBAN | KARNATAKA | 560075 | L4 | Rejected-Finance NOT lOWEST |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
14 Jun 2022, 6:00 pmClosed
CHIEF ENGINEER R AND D SECUNDERABAD
CHIEF ENGINEER R AND D SECUNDERABAD JUBILEE BUS STAND PICKET SECUNDERABAD 500003
SPECIAL REPAIRS FOR REPLACEMENT OF LT ACB PANEL AT T 54 AND SUB STATION NO 1 UNDER CVRDE AREA AVADI
2022_MES_524777_1
CA NO.CERD/AVD/TOKEN/ 03 OF 2022 - 2023
Open Tender
Civil Works
Item Rate
180 days
AVADI
as per tender documents
8 documents required · 8 mandatory
₹500
AGE I R AND D Avadi Chennai
₹96,000
Yes
30 Jun 2022
18 May 2022
21 Jun 2022
18 May 2022
14 Jun 2022
1 Jun 2022
Amount
Supply, assemble, erection, testing and commissioning indoor type floor mounted free standing dust and vermin proof LT panel 3 phase, 4 wire, 50 HZ, 433 volts, 50 KA fault level with IP-54 protection fabricated out of suitable sized angle iron and flats and covered with 2mm thick CRCA sheet duly pretreated in seven tank process for degreasing, de-rusting & Phosphated painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel shall be compartmentalised with rubber casketed hinged door. Panel shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switch gear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200mm to be kept from floor level for switch gear compartment. Extended busbar links / terminals to be provided for heat dissipation. Air ventilation breather to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided as directed. Each compartment shall be numbered / lettered as directed, affixing MV danger plate at suitable intervals / locations including panel wiring with PVC insulated unsheathed, 1100 volts grade multistranded copper conductor cable of suitable size and inter connection of ACB's, MCCB's with bus bars by copper strip of suitable size with following switch gears all as specifed and directed.
INCOMER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps capacity, 50KA manual draw out type and inter locked mechanically and electrically, with micro processor release, over load protection, no volt release, with necessary suitable terminal for connecting the incomer feeder - 01 No. BUS COUPLER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps 50KA capacity, manual draw out type and inter locked mechanically and electrically, with micro processor release, over load protection, no volt release, with necessary suitable terminal for connecting the bus bar - 01 No. BUS BAR: Bus bar of high conductivity electrolytic copper bus TP 1200 Amps rating and neutral 600 amps rating supported suitable insulator and heat shrinked insulating sleeves - 01 set. OUTGOING: (a) MCCB 415 volts, AC, 50 Hz, 4 pole, 400 Amps capacity, 50KA fixed thermal magnetic release complete - 01 No. (b) MCCB 415 volts, AC, 50 Hz, 4 pole, 250 Amps capacity, 36KA fixed thermal magnetic release complete - 01 No. (c) MCCB 415 volts, AC, 50 Hz, 4 pole, 125 Amps capacity, 36KA fixed thermal magnetic release complete - 02 Nos. (d) MCCB 415 volts, AC, 50 Hz, 4 pole, 100 Amps capacity, 25KA fixed thermal magnetic release complete - 02 Nos. (e) MCCB 415 volts, AC, 50 Hz, 4 pole, 63 Amps capacity, 25KA fixed thermal magnetic release complete - 01 No. (f) Digital multifunctional meter, panel mounted, sqaure type for measuring voltage, current, KWH etc including necessary CT's. (g) Indication lamp (RYB) LED type - 01 set of three.
Supply, assemble, erection, testing and commissioning indoor type floor mounted free standing dust and vermin proof LT panel 3 phase, 4 wire, 50 HZ, 433 volts, 50 KA fault level with IP-54 protection fabricated out of suitable sized angle iron and flats and covered with 2mm thick CRCA sheet duly pretreated in seven tank process for degreasing, de-rusting & Phosphate painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel shall be compartmentalised with rubber gasket hinged door. Panel shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switch gear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200mm to be kept from floor level for switch gear compartment. Extended busbar links / terminals to be provided for heat dissipation. Air ventilation breather to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided as directed. Each compartment shall be numbered / lettered as directed, affixing MV danger plate at suitable intervals / locations including panel wiring with PVC insulated unsheathed, 1100 volts grade multistranded copper conductor cable of suitable size and inter connection of ACB's, MCCB's with bus bars by copper strip of suitable size with following switch gears all as specifed and directed. INCOMER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps 50KA capacity, manual draw out type and inter locked mechanically and electrically, with micro processor based, over load protection, no volt release, with necessary suitable terminal for connecting the incomer feeder - 01 No.
BUS BAR: Bus bar of high conductivity electrolytic copper bus TP 1200 Amps rating and neutral 600 Amps rating supported suitable insulator and heat shrinked insulating sleeves - 01 set. OUTGOING: (a) MCCB 415 volts, AC, 50 Hz, 4 pole, 400 Amps capacity, 50KA fixed thermal magnetic release complete - 01 No. (b) MCCB 415 volts, AC, 50 Hz, 4 pole, 250 Amps capacity, 36KA fixed thermal magnetic release complete - 01 No. (c) MCCB 415 volts, AC, 50 Hz, 4 pole, 125 Amps capacity, 36KA fixed thermal magnetic release complete - 02 Nos. (d) MCCB 415 volts, AC, 50 Hz, 4 pole, 100 Amps capacity, 25KA fixed thermal magnetic release complete - 02 Nos. (e) MCCB 415 volts, AC, 50 Hz, 4 pole, 63 Amps capacity, 25KA fixed thermal magnetic release complete - 01 No. (f) Digital multifunctional meter, panel mounted, sqaure type for measuring voltage, current, KWH etc including necessary CT's. (g) Indication lamp (RYB) LED type - 01 set of three.
Supply, assemble, erection, testing and commissioning indoor type floor mounted free standing dust and vermin proof LT panel 3 phase, 4 wire, 50 HZ, 433 volts, 50 KA fault level with IP-54 protection fabricated out of suitable sized angle iron and flats and covered with 2mm thick CRCA sheet duly pretreated in seven tank process for degreasing, de-rusting & Phosphate painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel shall be compartmentalised with rubber gaskete hinged door. Panel shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switchgear compart ments.Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200mm to be kept from floor level for switch gear compartment. Extended bus bar links / terminals to be provided for heat dissipation. Air ventilation breather to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided as directed. Each compartment shall be numbered / lettered asdirected, affixing MV danger plate at suitable intervals / locations including panel wiring with PVC insulated unsheathed, 1100 volts grade multistranded copper conductor cable of suitable size and inter connection of ACB's, MCCB's with bus bars by copper strip of suitable size with following switch gears all as specifed and directed. INCOMER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps capacity, 50KA manual draw out type and inter locked mechanically and electrically, with micro processor based, over load protection, no volt release, with necessary suitable terminal for connecting the incomer feeder - 01 No.
BUS COUPLER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps capacity, 50KA / manual draw out type and inter locked mechanically and electrically, with micro processor based, over load protection, no volt release, with necessary suitable terminal for connecting the bus bar - 01 No. BUS BAR: Bus bar of high conductivity electrolytic copper bus TP 1200 Amps rating and neutral 600 Amps rating supported suitable insulator and heat shrinked insulating sleeves - 01 set. OUTGOING: (a) MCCB 415 volts, AC, 50 Hz, 4 pole, 400 Amps capacity, 50KA fixed thermal magnetic release complete - 01 No. (b) MCCB 415 volts, AC, 50 Hz, 4 pole, 250 Amps capacity, 36KA fixed thermal magnetic release complete - 01 No. (c) MCCB 415 volts, AC, 50 Hz, 4 pole, 125 Amps capacity, 36KA fixed thermal magnetic release complete - 02 Nos. (d) MCCB 415 volts, AC, 50 Hz, 4 pole, 100 Amps capacity, 25KA fixed thermal magnetic release complete - 02 Nos. (e) Digital multifunctional meter, panel mounted, sqaure type for measuring voltage, current, KWH etc including necessary CT's. (f) Indication lamp (RYB) LED type - 01 set of three.
Supply, assemble, erection, testing and commissioning indoor type floor mounted free standing dust and vermin proof LT panel 3 phase, 4 wire, 50 HZ, 433 volts, 50 KA fault level with IP-54 protection fabricated out of suitable sized angle iron and flats and covered with 2mm thick CRCA sheet duly pretreated in seven tank process for degreasing, de-rusting & Phosphate painted with 2 coats of primer paint then painted with final coat of epoxy based powder coated paint. Panel shall be compartmentalised with rubber gaskete hinged door. Panel shall be having front and rear opening for installation of separate cable alleys, busbar chamber and switch gear compartments. Provision in cable alleys to be kept for bottom cable entry for incoming and outgoing cables. A clear space of 200mm to be kept from floor level for switch gear compartment. Extended bus bar links/terminals to be provided for heat dissipation. Air ventilation breather to be provided for heat dissipation. Suitable sized knock-out holes for cable glands shall be provided complete all as specified and directed. INCOMER: ACB, 415 volts, AC, 50 HZ, 4 pole, 800 Amps capacity, manual draw out type and inter locked mechanically and electrically, with micro processor based, over load protection, no volt release, with necessary suitable terminal for connecting the incomer feeder - 01 No. BUS BAR: Bus bar of high conductivity electrolytic copper bus TP 1200 Amps rating and neutral 600 Amps rating supported suitable insulator and heat shrinked insulating sleeves - 01 set.
OUTGOING: (a) MCCB 415 volts, AC, 50 Hz, 4 pole, 400 Amps capacity, 50KA fixed thermal magnetic release complete - 01 No. (b) MCCB 415 volts, AC, 50 Hz, 4 pole, 250 Amps capacity, 36KA fixed thermal magnetic release complete - 01 No. (c) MCCB 415 volts, AC, 50 Hz, 4 pole, 125 Amps capacity, 36KA fixed thermal magnetic release complete - 02 Nos. (d) MCCB 415 volts, AC, 50 Hz, 4 pole, 100 Amps capacity, 25KA fixed thermal magnetic release complete - 02 Nos. (e) Digital multifunctional meter, panel mounted, sqaure type for measuring voltage, current, KWH etc including necessary CT's. (f) Indication lamp (RYB) LED type - 01 set of three.
Earthing complete with galvanised steel earth plate electrode 60 x 60cm x 6.0mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of the plate not less than 1.5 mtr below normal ground level, connected to and including using of 32 x 6 GI strip as earthing lead by means of bolts, nuts, check nuts and washers of galvanised steel, connected to earthing test point, all as specified & indicated, including testing on completion including earth work and excavation in any type of soil / rock, PCC 1:3:6 type C1, earthing chamber, precast RCC slab 50mm thick in cement concrete 1:2:4 type B1 reinforced with welded steel wire febric weight hot less than 4 Kg/Sqm, funnel with GI watering pipe of 20mm bore, medium grade wire mesh and lugs, GI protection pipe of 40mm bore light grade upto 7.50 mtr long test point etc all as specified including testing on completion and including taking down old earthing set complete all as specifed and directed.
M&L for demolition of RCC of any description and in any position not otherwise specifically provided (cable duct cover portion) complete all as specified and directed.
S&F, (Plain or chequered) channels / plate Fe 410-W (Gde-E-250 Quality-A) Square cut or notched (ordinary and counter sunk) for covering plates and base plates, cladding, etc forming holes, with any attachment angle or other section with gusset plates, rails, braces with ornamental and intricate design with complete drilled for fixing of steel sheeting or other covering with handles, running rails and guides, hanging also fastening and fixing complete including dismantling and taking down unserviceable old one complete all as specified and directed.
BKR Enterprises
EASHWAR ELECTRICALS
Shiva Shakthi Electrical Enterprises
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .