Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹19.6 LAccepted-Finance A 3 257 JANAKPURI NEW DELHI 110058 | WEST DELHI | DELHI | 110058 | L1 | Accepted-Finance LOWEST BIDDER | |
| 2 | L2₹26.0 L+₹6.4 L (32.7%)Rejected-Finance | L2 | Rejected-Finance BIDDER NOT LOWEST | |
| 3 | L3₹26.1 L+₹6.5 L (33.1%)Rejected-Finance A 303 VEENA CGHS LTD PLOT NO 5D SECTOR 22 DWARKA NEW DELHI 110077 | NEW DELHI | SOUTH WEST DELHI | DELHI | 110077 | L3 | Rejected-Finance BIDDER NOT LOWEST | |
| 4 | L4₹28.2 L+₹8.6 L (43.8%)Rejected-Finance | L4 | Rejected-Finance BIDDER NOT LOWEST | |
| 5 | Rejected-Technical | - | Rejected-Technical NOT IN CATEGORY |
Tender Value
₹45 L
EMD Value
₹90,000
Closing Date
5 Jun 2021, 6:00 pmClosed
GE WEST DELHI CANTT 10
GE WEST DELHI CANTT 10
REPAIR REPLACEMENT OF HTLT UG HTLT PANELS FEEDER PILLAR BOXES DBS AND STREET LIGHT FITTINGS HT LT UG CABLES AT SALARIA OFFICERS ENCLAVE AT DWARAKA UNDER GE WEST DELHI CANTT 10
2021_MES_426911_1
GE/DW-58/2021-22
Open Tender
Civil Works
Item Rate
270 days
DELHI CANTT
Please refer Tender documents.
7 documents required · 7 mandatory
₹500
GE WEST DELHI CANTT
₹90,000
21 Jun 2021
10 May 2021
12 Jun 2021
11 May 2021
5 Jun 2021
24 May 2021
Amount
Disconnecting HT sides of VCB indoor installed in power house Dwraka on PCC foundation of any capacity up to 11KV. Opening of top cover with due care and removal of all HT connections from bus bar with due care for inspection and ascertain it’s serviceability state. Removal of all sludge and unwanted material from inside the VCB. Reconnect the HT connection after repairing/ serviceability of VCB including repair and servicing of vacuum adapter, replacement of following spares will be measured and paid separately complete all as specified and directed. Note : Breakdown complaints on external electric network shall be completed within 48 hrs without any delay. Necessary repairs/ replacement will be reacted on urgent basis no delay action shall be applicable during the breakdown conditions and accessories or components to be provided for replacement will be Measured separately under item 2 to 10 of this schedule
Supply only Shunt trip coil suitable for CG VCB complete all as specified and directed.
Supply only closing coil suitable for CG VCB complete all as specified and directed.
Supply only spring charging motor suitable for CG VCB complete all as specified and directed.
Supply only Limit switch of AC 15 , 3A/400 V suitable for CG VCB complete all as specified and directed.
Supply only Limit switch of 16 A/250 V AC suitable for CG VCB complete all as specified and directed.
Supply only breaker control switch suitable for CG VCB complete all as specified and directed.
Supply only Master relay Relay 110 V DC suitable for CG VCB complete all as specified and directed.
Supply only Rail Pole Relay 110 V DC suitable for CG VCB complete all as specified and directed.
Supply only Aux. Contact block (VCB) suitable for CG VCB complete all as specified and directed.
Disconnecting and opening of RMU and removal of all connections with due care for serviceability of its parts including minor unserviceable electric wiring changing as per existing guage to all connections of RMU and reconnect as per existing for serviceabilty of RMU Note : Breakdown complaints on external electric network shall be completed within 48 hrs without any delay. Necessary repairs/ replacement will be reacted on urgent basis no delay action shall be applicable during the breakdown conditions and accessories or components to be provided for replacement will be Measured separately under item 12 to 21 of this schedule
Supply only Relay suitable for CG Lucy VCB complete all as specified and directed.
Supply only Bus bar extansion Bushing Set of three suitable for CG Lucy VCB complete all as specified and directed.
Supply only Bus bar obround Bushing Set of three suitable for CG Lucy VCB complete all as specified and directed.
Supply only Ring switch Actuator suitable for CG Lucy VCB complete all as specified and directed.
Supply only Bottom Entry Gland suitable for CG Lucy VCB complete all as specified and directed.
Supply only Tripping coil suitable for CG Lucy VCB complete all as specified and directed.
Supply only Indicator suitable for CG Lucy VCB complete all as specified and directed.
Supply only Stainless steel on/off handle suitable for CG Lucy VCB complete all as specified and directed.
Supply only Gas pressure indicator suitable for CG Lucy VCB complete all as specified and directed.
Supply only Time limit switch suitable for CG Lucy VCB complete all as specified and directed.
Taking out the existing transformer from site and transporting to workshop for servicing and repairing including loading unloading and handling to carry out the following repairs and refixing the same after repairing , installation , testing and commissioning at its existing location all as specified and directed (a) Decant the transformer oil and checking of all parts for repair/ replacement of parts of cap from 1000 KVA capacity of distribution transformer 11/0.440 KV . (b) Rewinding of coils all as per its original stranded specifications by appropriate size/gauge copper conductor and with HT/LT necessary insulation materials. (c) Replacement of HT 11 KV bushing with brass terminal, neoprene rubber gasket and washers etc complete. (d) Replacement of LT bushing with brass terminal, neoprene rubber gasket and washers etc complete (e) Replacement of Transformer oil up to conservator level marking with new oil as per IS 335 having dielectric strength not less than 40 KV at 2.5 mm gap (f) Replacement of silica Jel in existing transformer breathers. (g) Replacement of HT 11 KV off-load tap changing assembly complete. (h) Painting of Transformer body complete with one coat of Simense grey paint with spray paint all as directed by the Engineer-in-charge. (i) Filtration of transformer oil of the transformer at site by providing filtration machine at site. Note : Breakdown complaints on external electric network shall be completed within 48 hrs without any delay. Necessary repairs/ replacement will be reacted on urgent basis no delay action shall be applicable during the breakdown conditions and accessories or components to be provided for replacement will be Measured separately.
All as above item No : 22 -but Cap 630 KVA
Dehydration/filtration of transformer oil by means centrifuging machine electrically operated at site of installation of transformer in running condition including testing of transformer oil before and after filtration by means of oil testing machine, keeping the electrodes at 2.5 mm gap and to achieve die electric strength of filtered oil 50 KV and above complete all as specified and directed.
Supply and topping up/replaced transformer oil conforming to IS : 335 and withstand dielectric strength of 60 KV (when tested with 2.5 Gap electrode) complete all as specified and directed. Make: Savita or equivalent as approved.
Supplying, laying, jointing, testing and commissioning LT, XLPE insulated armoured, heavy duty aluminium conductor electric cable 1100 Volts grade, cross sectional area 240 Sqmm, 3.5 core including taking out old existing cable in trench/wall/feeder connections complete all as specified and directed.
All as per item No 26 but 3.5 core 185 sqmm.
All as per item No 26 but 3.5 core 150 sqmm.
All as per item No 26 but 3.5 core 35 sqmm.
All as per item No 26 but 3.5 core 25 sqmm.
All as per item No 26 but 4 core 16 sqmm.
S&F in replacement with new HT Cable jointing kit for 11 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed.
S&F in replacement with new HT Cable jointing kit for 11 KV (Earthed) grade cable for indoor termination heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 240 sqmm to 300 sqmm complete all as specified and directed.
Taking out/down 80mm bore steel tubing with fittings and M&L 80mm bore steel tubing light grade, galvanized with all fitting laid in trenches/poles complete all as specified and directed.
All as per item 34 but 40 mm bore size.
S&F MCCB 3 pole suitable for AC 3 phase 415 volt 50 HZ, 400 Amp, 35 KA, with thermal magnetic release fixed on existing LT panel complete all as specified and directed. Note: Rate quoted deemed to include taking down the existing MCCB from panel board and incoming / outgoing cable and fix the new MCCB in position at panel board / incoming / outgoing cable connections of any size/ rating.
All as per item 36 but 250 Amps, 50 KA omplete all as specified and directed.
All as per item 36 but 200 Amps, 50 KA omplete all as specified and directed.
All as per item 36 but 125 Amp, 50 KA omplete all as specified and directed.
All as per item 36 but 100 Amp, 50 KA omplete all as specified and directed.
S&F in repair MCB double pole, 63 Amp 415 volt 10 KA complete all as specified and directed.
M&L LT 1100 volts straight through joints kit epoxy type of size 16 to 95 sqmm 3.5 core, jointing LT UG cable complete all as specified and directed.
M&L LT 1100 volts straight through joints kit epoxy type of size 120 to 240 sqmm 3.5 core, jointing LT UG cable complete all as specified and directed.
M & L servicing of feeder pillar box, after dismantling the incoming and outgoing connections from MCCB/ Bus bar and replacing the old burnt/ overheated unserviceable lugs, terminals, nuts, bolts, washers supporting insulators etc and checking the serviceability of MCB / MCCB, earth continuity conductor and strip etc complete all as specified. Note: (i) Spare parts such as terminals, lugs, nut bolts, insulators etc will be measured and paid under respective item in the schedule, (ii) Fixing charge of the spare parts deem to include the rate quoted for the items.
Supply only aluminium lugs suitable for 240 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for150 Sqmm omplete all as specified and directed.
Supply only aluminium lugs suitable for120 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 95 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 70 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 50 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 35 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 25 Sqmm complete all as specified and directed.
Supply only aluminium lugs suitable for 16 Sqmm complete all as specified and directed.
Supply only GI Nuts, bolts, screws, washers of required sizes omplete all as specified and directed.
Supply only bus bar Insulators Epoxy type as required at site min size 45mm x 50 mm dia omplete all as specified and directed.
Supplying and laying unreinforced precast cement concrete cable covers,ISI Marked Class HV, Flat, Type - 1, of size 300 mm X 180 mm X 40mm in trenches for cable protection, embossed with "ELECTRIC" on the top surface including taking UP complete all as specified and as directed .
Supplying, laying and commissioning of HT XLPE cables, insulated, screened, PVC bedded, galvanized steel strip armoured, earthed, electric power cable with Aluminium conductor, 11 KV grade, 3 Core, 240 Sq.mm cross sectional area laid in trenches / fixed on poles including taking up/down old cables complete all as specified and as directed. Note: Earth work,excavation,cable covers and sand cushioning shall be measured and paid separately.
Material and Labour for heat shrinkable HT, 11 KV cable straight through joint suitable for 11 KV, 3 Phase, AC, 50 Hz, 3 Core, Size of 50 to 95 Sq.mm XLPE Cable including jointing materials, including taking down old unserviceable joints etc complete all as specified and directed.
Material and Labour for heat shrinkable HT, 11 KV cable straight through joint suitable for 11 KV, 3 Phase, AC, 50 Hz, 3 Core, size of 120 to 240 Sq.mm XLPE Cable including jointing materials, including taking down old unserviceable joints etc complete all as specified and directed
M & L preparation of old painted steel surface by cleaning, removing rust, grease and apply one coat of synthetic enamel paint of approved shade and Spray painting outside/inside surface of the feeder pillar box / LT Panels Outdoor / Indoor type complete with prior permission of Engineer in Charge. Base frame with Black enamel paint (Rate quoted shall deem to be included of Numbering of Panel/ Feeder pillar) complete all as specified.
M & L Bakelite strip connector, 4 way, 100 Amp cap including electrically connections including taking down old item complete all as specified.
M & L in replacement LT danger notice board of size 20x15 cm made of aluminium sheet 1 mm thick fixed with Nut / bolts and washers or riveting on LT panels/ feeder pillar boxes with vitreous enamelled white back ground, with letters figures and conventional skull and bones in signal red colour complete all as specified.
M & L in replacement HT danger notice board of size 25x20 cm made of aluminium sheet 1 mm thick fixed with Nut / bolts and washers or riveting on LT panels/ feeder pillar boxes with vitreous enamelled white back ground, with letters figures and conventional skull and bones in signal red colour complete all as specified.
S & F in replacement LED type R/Y/B/G indicating lamp omplete all as specified and directed.
S & F aluminium bus bar of required size, shape, length and making drilling for fixing in LT panel /feeder pillar/change over switch etc including taking down old item complete all as specified.
S&F Volt meter 3 phase, 415 V in existing panel including wiring from bus bar to volt meter terminals including taking down complete all as specified.
S&F Ammeter 0-200 Amp 3 phase, 415 V in existing panel including wiring from bus bar to volt meter terminals including taking down complete all as specified.
S&F current Transformer coil of rating from 100/5 to 400/5 CT ratio in existing panel including taking down complete all as specified.
S&F earth continuity conductor or main earthling lead of Galvanised iron strip of size 25 x 4 mm, fixed on floor/ wall with supporting insulators / laid in trench from existing earth test point including taking down old items complete all as specified.
Dismantling and taking down HPSV 150 Watt street light fittings for repair or replacement of burnt/ worn out accessories and repairing and refixing the same from approximate height 9 mtr after repair around the pole one meter area treaming bushes all directed. Note:(i) T&P for Dismantling deemed to be included in the unit rate. (ii) Accessories or components to be provided for replacement will be Measured separately.
Supply and fix in replacement HPSV Lamp tubular 150Watt,Make: Philips /Equivalent in Crompton Greaves
Supply & Fix in replacement Ignitor suitable for 150 W HPSV street light fittings.
Supply and fix in replacement copper wound ballast suitable for 150 Watt HPSV street light fittings
Supply and fix in replacement Porcelain holder thread type suitable for 150W HPSV fittings
Supply and fix in replacement junction box made from SMC/FRP sheet ready made of size 300 X 200 X 100 mm having 100 A capacity for RYB and neutral with aluminium bus bar including all necessary insulators fix to Box and MCB SP 6 Amp 10 KA 240V with aluminium lugs - 01 No with 4 way connector fixed to Pole /Wall with MS clamp 25 X 5 mm with the help of suitable nuts and bolts. Make : Sintex or equivalent Make Legrand
Supply and fix in replacement 3 Pole contactor MNX 18, including necessary connections for incoming and outgoing connections .
Supply and fix in replacement Timer for 24 hrs including necessary wiring from contactor and supply connections.
Supply and fixing in replacement MS kiosk box made out from 2 mm thick MS sheet including bus bar TPN 4 strip 63 A capacity and one MCB SP 6 Amp for street light fitting to be mounted on pole with 2 nos 25x3 mm flat iron clamps and shutter to be opened and closed vertically with ball locking system size of box 200x150x100 mm complete with two coats of synthetic enamel paint of approved colour over one coat of red oxide primer complete all as specified and directed.
Supply and fixing in replacement of 90 watt LED fitting for street light on pole complete with electronic drivers and other accessories prewired complete all as specified and directed.
Supply & laying Sub class ‘B’ bricks for cable protection including taking up old bricks complete all as specified and directed.
M&L for scrapping/removing rusted partials on surface of existing single swan neck steel tubular electric street light pole including nut and bolts after cleaning Appling one coat of red oxide and two coats of aluminium paint including stranded size of numbering and alternate strip black and yellow synthetic enamelled painting from the coping of pole as directed and two coats of cement base paint on surface area of copping complete all as specified and directed by Engr-in-charge.
Excavation in trenches n.exc.1.5m wide and n.exc1.5m deep and getting out in soft/loose soil all as specified.
Returning,filling in,including spreading ,levelling ,watering and well ramming inlayers n.exc,25cm.any tyoe of soil all as specified.
Removal of surface soil to a distance n.exc 50 m and deposited where directed at a level n. exc 1.5 m above the starting point complete all as directed by ECI .
M&L for sand cushioning for cable protection etc in trenches, complete all as specified and directed.
Supply and lay in trenches/fixed on wall GI tubing light grade with necessary fittings such as bend, tee, elbow etc including taking up/down complete for the size 50 mm omplete all as specified and directed.
Supply and erecting of steel tubular swaged pole single swan neck bent to shape complete with cast iron base plate bolts and nuts and screws 410 SP 31( 9 mtr long) complete including taking down old pole complete all as specified and directed.
Supply and fixing passing through cable 3 core PVC insulated unsheathed multistranded copper conductor of size 2.5 Sqmm from junction box to street light fitting all as specified and directed.
M&L for earthing complete with GI earth plate electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 Mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 Mtrs below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using GI wire 4 mm by means of bolts, nuts, chuck nuts, and washers and protected by medium grade 50 mm dia GI pipe connected to main control board and GI pipe medium grade 20mm bore for watering , including funnel, wire mesh, RCC 75 mm thick pit cover 1:2:4 type B-1 using 20 mm graded stone aggregate with and including 8 mm dia TMT bars @ 100 mm centre to centre both ways ,PCC chamber pit with PCC 1:2:4 B-1 ( including necessary form work, excavation and earth work, disposal of surplus soil two a distance not exc. 50 Mtrs) complete all as specified and shown in SSR – Part I 2009. NOTE :-1. PCC pit shall be provided at list 500 mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipe and fittings, junction, elbow etc shall be deemed to be included in the unit rate.
M&L for earthing complete with GI earth plate electrode of size 60cmx60cmx6mm buried directly in ground vertically at a depth not less than 2.25 Mtr below normal ground level with top edge of earth plate at a depth not less than 1.5 Mtrs below normal ground level surrounded from all sides by 15 cm thick and packed layer of charcoal dust and common salt filling in alternate layers and electrode connection by using GI but using galvanised iron strip 25×4mm as earthling lead by means of bolts, nuts, chuck nuts, and washers and protected by medium grade 50 mm dia GI pipe connected to main control board and GI pipe medium grade 20mm bore for watering , including funnel, wire mesh, RCC 75 mm thick pit cover 1:2:4 type B-1 using 20 mm graded stone aggregate with and including 8 mm dia TMT bars @ 100 mm centre to centre both ways ,PCC chamber pit with PCC 1:2:4 B-1 ( including necessary form work, excavation and earth work, disposal of surplus soil two a distance not exc. 50 Mtrs) complete all as specified and shown in SSR – Part I 2009. NOTE :-1. PCC pit shall be provided at list 500 mm away from the earth pit and not just on the earth pit and extra cost of additional length of water pipe and fittings, junction, elbow etc shall be deemed to be included in the unit rate.
M&L in replacement Mild steel plates, plain or chequered, thickness in available sizes all as specified and directed.
M&L in replacement rubber Insulating protective mat size 1950 X 950 X 20 mm all as specified and directed by Engr-In-Charge
M&L for PCC 1:4:8 type D-2 using 40 mm grade stone aggregate as in foundation concrete for pole including finishing the exposed surface using extra cement complete all as specified and directed
M&L for PCC 1:2:4 type C-1 using 20 mm grade stone aggregate as in foundation concrete for pole including finishing the exposed surface using extra cement complete all as specified and directed
M & L Machine pressed precast concrete interlocking paver block any shape and size confirming to IS 15658-2006 of 60 mm thickness, M-35 Grade complete all as specified and directed
M&L for brick work with sub class 'B' straight or curved on plan exc 6m mean radius and built in CM 1:6 complete all as specified and directed.
M & L Overhauling of water pump for 140 KVA DG set complete all as specified and directed
M & L in replacement Fan belt for water pump omplete all as specified and directed.
M & L in replacement Water seal for water pump omplete all as specified and directed.
M & L in replacement Hosepipe including clamps omplete all as specified and directed.
Cleaning of air cleaner, tightening of intake and exhaust manifold’s nuts and cap screws for sealing of 140 KVA DG set including complete all as specified and directed.
Calibration/setting of timing to FIP for 140 KVA DG set including all necessary items such as rotary piston,rings,springs etc complete all as specified and directed.
M&L in replacement injectors/nozzles for 140 KVA DG set complete all asall as specified and directed.
M&L for servicing of Radiator 140 KVA DG set and refixing including normal repairs and maintenance complete all as specified and directed.
M & L in replacement diesel primary and secondary filter element with O ring suitable for 140 KVA DG Set.
M & L in replacement Oil primary and secondary filter with O ring suitable for 140 KVA DG Set.
M & L Engine OIL for topping up suitable for 140 KVA DG Set.
M & L in replacement Air filter element suitable for 140 KVA DG Set.
M & L in replacement HEX SCREW suitable for 140 KVA DG Set.
M & L in replacement FIP High pressure pipe suitable for 140 KVA DG Set.
M & L in replacement fuel pipe M14 BANJO 1100 L, RB suitable for 140 KVA DG Set.
M & L in replacement turbo oil drain pipe (4G11TAG3) suitable for 140 KVA DG Set.
M & L in replacement turbo oil inlet pipe side open suitable for 140 KVA DG Set.
M&L in replacement of gasket cylinder suitable for 140 KVA DG Set incl taking down Cylinder head cleaning carbon with help of chemical polishing valves adjusted required spring action, fixing of new gasket and refined cylinder head required tighting all as specified and directed.
M&L in replacement Batteries DC, 12V, 110 AH, lead acid duly initial charged complete al as specified
Supply and fix in replacement Volt meter 0-500 Volt (suitable for DG set 140 KVA) in existing panel including wiring from bus bar to volt meter terminals and fix the wiring wit existing control wiring all as specified and directed.
Supply and fix in replacement Ammeter(suitable for DG set 140 KVA) of following range in existing panel with necessary wiring from CT to Ammeter and fix the wiring in existing set of control wiring all as specified and directed.
M & L in replacement asbestos rope at silencer of DG Set of any capacity/ Make to be fix on pipe after removing existing unserviceable rope all as specified and directed.
M & L for Cleaning the fuel tank, after taking the shut down of DG set 140 KVA in all respects and drain out fuel from tank collect in suitable container and checking of leakage,repair the same as directed and cleaning the tank up to bottom and refill the fuel after cleaning and start test/Run the DG set all as specified and directed. .
Deduct Credit: for demolished/dismantled material of (-) Rs 149923.00(Minus) as listed in Schedule 'A' Part II (Credit Schedule) Note: Tenderer's shall not quote against this item. The amount of Credit Schedule is tentative, however the same shall be considered to arrive at the contract sum
M/s KUNDU CONSTRUCTION
Ridhi engineers and builders
H.B. Traders
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .