OFFICE OF THE EXECUTIVE ENGINEER JAL SHAKTI PHE MECHANICAL DIVISION SRINAGAR
Rewinding of stator winding coils of 695KW, 11KV, 3-Phase, 1488 rpm Squirrel Cage Induction Motor (Unit-4) Sr No 43150-A-40411-03 at WSS Tangnar Stage-2nd
2023_PHE_218361_1
PHE/MECH/e-NIT- 15 of 06/2023
Open Tender
Miscellaneous Works
Item Rate
30 days
Tangnar
As Per NIT
2 documents required · 2 mandatory
₹500
Yes
Ex Engineer Jalshakti Mech Div Sgr
₹26,500
Yes
7 Jul 2023
23 Jun 2023
3 Jul 2023
23 Jun 2023
1 Jul 2023
23 Jun 2023
Amount
Disconnecting the connections of power and control cables from the connection box, setting aside the cables and earthing strip from the Motor & removing the coupling hub and key from DE shaft extension of motor. After dismounting the motor from the motor stool, bearing housing and motor shield is disassembled from the Motor and rotor is to be extracted from the stator. While extracting the rotor extreme caution is to be exercised in order to prevent any damage to the rotor or stator core. The contractor shall have to arrange all tools, tackles and highly skilled manpower for this purpose.
Extraction of stator coils totaling 60 in number including the insulating material from the slots of the stator core using special tools & tackles without causing any damage to the stator slots and core. The stator slots shall be cleaned of all sorts of debris consisting of insulating material & winding. The stator slots shall be finally washed with acetone/Isopropyl alcohol and dried completely using blower. Also, the stator shall be painted with epoxy, besides the stator core assembly shall be tested with flux loop test. The contractor shall have to arrange all tools, tackles and highly skilled manpower for this purpose.
Winding of copper strip of adequate size and number (as per original design) in two parallel layers, vacuum pressure impregnated (VPI) as per the sample (approx. 3M length), frame size & specification 1LA45004 conforming to relevant IS code. (Test certificate on a/c of purity of copper (not less than 99.9%)) is to be provided by the firm at the time of receipt of material. These copper strips shall be wound together to form a loop, which shall subsequently be formed to the exact shape and size of the sample coil. The job includes p/f of 70 Sq.mm 11KV XLPE copper flexible insulated terminal leads. The contractor shall have to arrange 11KV F-class sleeves and other related raw material in order to achieve the desired insulation levels. No of Coils ….. 60 Weight of each Coil … 6.1 Kg (Approximately) Weight of Connection Leads for internal connections & leads upto terminal box= 14 Kg’s (Approximately) Total \Weight= 60*6.1+ 14=380 Kg’s (Approximately)
After achieving the desired shape of the winding coil strictly as per the sample, each coil shall be wrapped with several layers of high-grade insulating materials like Glass mica, Kapton mica and PGMP tape with an overlap of 50%. The no of layers of each insulation type shall be as per the original design. However, the contractor shall ensure that requisite insulation levels as per relevant IS Code and standards are achieved and whatever insulation required, is to be borne by the contractor without any additional cost to the Department. On completing the insulation each coil shall be tested for insulation resistance, inter turn short and any minor current leakage or sparking by injecting 11KV voltage into the coil. If the values obtained for the above tests are within the prescribed limits as defined in the relevant standards, the coil shall be pre dried in an oven and varnished. Rewinding of the stator by placing the winding coils (duly tested) into the stator slots as per original shape and size. Applying additional insulation on the overhang portion and slot portion with semi poor (resin poor) tapes and special covering of slot portion with conducting and semi conducting tapes. Fixing of magnetic wedges in slot as per original type, size and shape. Lacing of overhung portion, making coil connection including brazing, varnishing, P/F of fiber glass spacers of 5mm thickness and locking of 60 slots with 2mm thick magnetic wedges. Besides the coils shall be firmly held in their respective slots by fitting of magnetic wedges. The contractor shall have to arrange 11KV F-class sleeves and other related raw material in order to achieve the desired insulation levels.
Testing of the winding in an open circuit w.r.t to earth on 27KV at workshop. Tests include IR/ PI Value, Winding Resistance Test & Surge Test. The terminal connection shall be tapped out of the coil as per the type & pattern of winding of extracted ones. The job includes fixing of 14-line temperature sensors (Stator Winding Thermo-couple/ RTD), 12 for windings & 02 for bearings. The sensor shall be fixed & activated for over current, locked rotor, dry run, earth fault & thermal overload. Besides a space heater shall also be fitted in the stator.
Heat treatment of the stator by placing it inside the Oven up to the recommended temperature until the desired IR Values of minimum of 50M-ohms is attained. The treatment shall last for at least 02 Days.
Application of specially formulated epoxy resin insulation to copper strips in order to ensure sealed and homogenous insulation system with high dielectric strength. The job also includes sealing of the slots with epoxy sealant.
Assembling, installation and testing of the motor by way of fitting and assembling the stator with rotor, bearing housing and end shield employing highly skilled technical man power well versed with HT motor works. Installation of the HT motor over the discharge head of the pump and connecting the HT motor to the electric mains including connecting the control wires to the motor & ensuring all the motor protections are in place with requisite relay settings commensurate to the motor load and other related parameters. Thereafter testing of the motor shall be carried out on no load for one hour. The motor shall then be coupled to the pump through available coupling and finally successfully testing the pumping unit on full load.
Carriage Charges Shifting of the stator of the Motor from the site to the workshop of the contractor by employing Hydra Crane for loading the stator of HT motor from the pump house into the truck and unloading the same at the workshop. After completion of work shifting back of stator to WSS Tangnar by employing the same means.
PERFECT ELECTRICAL WORKS
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .