Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹33.8 LAccepted-AOC | L1 | Accepted-AOC Being L1 | |
| 2 | L2₹36.9 L+₹3.0 L (8.96%)Rejected-Finance | L2 | Rejected-Finance BEING NOT L1 |
Tender Value
₹36 L
EMD Value
₹76,000
Closing Date
17 Mar 2022, 6:00 pmClosed
GE AF OJHAR
GE AF OJHAR
PROVISIONING OF WORK SERVICES FOR PROVIDING WIRING AND FLAME PROOF ELECTRICAL FITTING IN PZ LOADING BAY AT ASD-30 AT AF STATION OJHAR AND CERTAIN REVENUE WORKS AT AF STATION BORGAD
2022_MES_509286_1
8855/E8
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
OJHAR
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE AF OJHAR
₹76,000
Yes
31 Mar 2022
19 Feb 2022
19 Mar 2022
21 Feb 2022
17 Mar 2022
5 Mar 2022
Amount
Taking down existing Sub main wiring of any size at any height complete all as specified and as directed by Engineer -in- Charge.
M&L wiring for circuit/ sub main wiring 2x2.5 Sqmm+1x2.5 Sqmm earth wire PVC (FRLSH) insulated copper conductor, single core, 1100 v grade cable in surface as required including in stove enameled steel conduit conduit in 20 mm complete all as specified and directed by Engineer-In-Charge,
M&L wiring for circuit/ sub main wiring 2x4 Sqmm+1x4 Sqmm earth wire PVC (FRLSH) insulated copper conductor, single core, 1100 v grade cable in surface as required including in stove enameled steel conduit conduits in concealed 20 mm complete all as specified and directed by Engineer-In-Charge.
Supply and fix LED street light fitting 70 Watt of 110 lum/ watt, body made out of cast aluminium alloy, epoxy painted alongwith wire guard complete with all accessories of IP 66 Protection incl fixing arrangement and connecting up, complete all as directed by Engineer-in-Charge. Cat No LST-70-CDL of make crompton or equivalent make of philips/wipro as approved.
Supply, Installation, Testing and commissioning of flame proof-weather proof LED flood light 120 watt circular LED flood light with tapered fin design and excellent thermal management along with IP65 protection, complete all as specified and as directed by engineer in charge. Including taking down existing fittings. Make: SHYAM SWITCH GEARS Cat. No. “SSPL/FL/1251” Or Equivalent make as mentioned in Appx 'B'.
Supply and fix flame proof wall mounted fan of 13000 cfm & 1440 rpm of capacity 0.25 HP, 230 volts AC all as per cat No SSPL/WMF/140 Make: SHYAM SWITCH GEARS make as mentioned in Appx 'B'. including fan blades & fixing, complete all as specified and as directed by Engineer -in- Charge. Including taking down existing fittings and depositing MES storeyard.
Supply & Fix flame proof-weather proof switch socket and plug combined 16A, 250V(2POLE+EARTH),SHYAM SWITCH GEARS make as mentioned in Appx 'B'. complete all as specified and directed by Engineer-In-Charge.
Point wiring with 1.5 Sqmm (nominal area) PVC( Antitermite ecofriendly FRLSH) insulated sheathed copper stranded conductor cable run in and including concealed in wall/floor PVC conduit Medium grade not less than 20 mm as per IS with all fittings such as bends, tee,junction boxes,etc of suitable size including 1.5 Sqmm PVC(FRLSH) insulated copper earth continuity conductor connected to common earth dolly and including MS/GI sunken boxes with modular inner & surface plate suitable for housing modular switches, sockets,fan regulators etc for one light/fan/call bell point controlled by one 1- way switch complete all as specified and as directed by Engr -in -Charge.
Supply, Installation, Testing and commissioning of flame proof-weather proof Distribution Board, 4 way TPN of Make: SHYAM SWITCH GEARS or equivalent make as mentioned in Appx 'B'. complete all as specified and directed by Engineer-In-Charge.
Supply, Installation, Testing and commissioning of flame proof-weather proof Distribution Board, 8 way SPN of Make: SHYAM SWITCH GEARS or equivalent complete all as specified and directed by Engineer-In-Charge.
Supply and fix in repair MCB Triple pole ON OFF 32 amp 240 V, of Make SHYAM SWITCH GEARS cat part no SSPL/CS/174 or equivalent make as mentioned in Appx 'B'. complete all as specified and as directed by Engineer -in- Charge.
Supply and fix in repair MCB Double pole ON OFF 32 amp 240 V, of MakeSHYAM SWITCH GEARS cat part no SSPL/RI/106 or equivalent make as mentioned in Appx 'B'. complete all as specified and as directed by Engineer -in- Charge.
Supply and fix in repair MCB SINGLE pole ON OFF 10 amp 240 V, of MakeSHYAM SWITCH GEARS cat part no SSPL/RI/146 or equivalent make as mentioned in Appx 'B'. complete all as specified and as directed by Engineer -in- Charge.
M&L for earthing in repair including taking out GI plate with pipes earthing lead fasteners etc and earthing complete with galvanised steel earth plate electrode 600x600x6mm thick,burried directly in ground (earth pit not less than 2.25 Mtr deep below ground level ) with top edge of the plate not less than 1.5 Mtr below normal ground level,connected to galvanised iron wire 4 mm as earth lead by means of bolts,nuts ,washer and check nut of galvanized steel, protected by and including GI pipe 15 mm bore (light grade) and connected to main switch / MCB DBs box point / LP test point as directed and including cement concret pit in 1:2:4 type B1 using 12.5mm graded aggregate, with cast iron miled steel frame embedded in the concrete enclouser fineshed flushed & CI cover 10 mm thick of size (300mmx300mm CI) having locking arrengment hinged to CI frame all as shown under electrical plate of SSR Pt - I 2009 and as directed including painting the external surface of chamber & cover with enamel paint in diffrent colour as directed and writing earth results & date of test carried out with white paint on black painted background, wiremesh funnel 20 mm bore GI pipe medium grade for watering adequate quantity of charcol,Bentonite and common salt in alternate layer of 15cm 3ft x 3ft thick all around the electrode including necessery excavation & earth work in any type of soil complete testing on completion all as directed. Note:- i) Filling the pit with black cotten soil brought at site.
Re routing of cable for crane by making hole on wall making good of disturbed surface as original one, complete all as specified and as directed by the engineer in charge.
Taking down aluminium strip & air termination rod of any size at any height complete all as specified and as directed by Engineer -in- Charge.
S & F in repair Aluminium strip 25 x 3.15mm with saddles and fixing screws etc. for roof conductors and down conductors above ground, complete all as specified and as directed by Engineer -in- Charge.
Refixing of aluminium strip obtained from item no 17, complete all as specified and as directed by the Engineer-in-charge.
S & f in repair porcelain type insulators for fixing with suitable fixing arrangements for roof conductor and down conductor duly insulated from wall / surface/ roof, complete all as specified and as directed by the engineer-in-charge.
M & L for fixing arrangement of GI tube using PCC 1:3:6 C1 (20mm gradedaggregate) , complete all as specified and as directed by the Engineer-in-charge.
S & F in repair Air termination, single pointed aluminium rod 12mm dia and 300mm long, complete all as specified and as directed by Engineer -in- Charge.
S & F GI tube of 20 mm dia after cutting into required length for fixing air termination including fixing arrangement, complete all as specified and as directyed by the Engineer-in-charge.
S & F GI tube of 40 mm dia after cutting into required length for Earthing protection at wall fixing arrangement, complete all as specified and as directyed by the Engineer-in-charge.
S & F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw, complete all as specified and as directed by Engineer -in- Charge.
Flame proof - weather proof rotory switch with separate cable termination box Make SHYAM SWITCH GEARS cat part no SSPL/RI/1010 or equivalent make as mentioned in Appx 'B'. , complete all as specified and as direcetd by the engineer-in-charge
Taking down existing copper/aluminum point wiring (light/ fan/ socket or power points) complete including (fittings such as switches, ceiling roses, pendents, regulators, sockets, Light fitting etc including wooden battens /casing /capping and conduit etc and making good disturbed surface of walls, ceilings and floors etc. complete all as specified & as directed by Engineer-in-Charge.
Point wiring with 1.5 Sqmm (nominal area) PVC( Antitermite ecofriendly FRLS) insulated sheathed copper stranded conductor cable run in and including concealed in wall/floor PVC conduit not less than 20 mm as per IS with all fittings such as bends, tee,junction boxes,etc of suitable size including 1.5 Sqmm PVC(FRLS) insulated copper earth continuity conductor connected to common earth dolly and including MS/GI sunken boxes with modular inner & surface plate suitable for housing modular switches, sockets,fan regulators etc for one light/fan/call bell point controlled by one 1- way switch complete all as specified and as directed by Engr -in -Charge.
Taking down main switch, DB, MCB, and electric Meter etc all as directed.
Modular switch one way 6 Amp,1 Module , complete all as specified and directed by Engineer-in-Charge
Supplying and fixing Modular socket, 6 amps-2/3 pin combined, 2 Module, complete all as specified and directed by Engineer-in-Charge
Supply & Fix Ceiling rose surface type, PVC/Polycarbonate isolated body size 50x28 mm two to three terminals.complete all as specified and directed by Engineer-in-Charge
Supply and fix in repair sheet metal enclosure for DBs when MCBs to be used single pole and neutral double door, 240 volt, IP 43 with metal door , 8 way, complete all as specified and as directed by Engineer-in-Charge.
Supply and fix in repair MCB SPN 32 amp 240 V,10KA of complete all as specified and as directed by Engineer -in- Charge.
Supply and fixing 240V, 10 KA 'B' curve miniature circuit breaker (MCB) of single poles and current carrying capacity 5 to 32 AMP, in the MCB DB Complete with connection testing and commissioning..
Supply & fix in repair copper strip 20x3.15 mm with saddles & fixing screws etc., for roof conductors & down conductors above ground complete including porcelein insulators complete all as specified & as directed by the Engineer-in-charge.
Supply and lay,testing & commissioning in trenches/ducts or pasing through pipe 1100 Volt grade LTUG cable with XLPE insulated armored heavy duty electric cable with stranded aluminium conductor 1100V grade 4 core cross sectional area 240 sqmm, Complete all as specified and as directed by the Engineer -in-charge.
M & L fixing of DWC pipes it should be flexible & ahould allow deformation in diameter as well as in joints under external load & soil natural movement, socket & spigot joints with elastoatic sealing ring it should be highly, corrosive resistant & it`should be impact resitant, elbows , joints & necessary joints required for completion of work all as specified and as directed by the Engineer- in- charge.
Exacavation in trenches n. exc. 1.5 mtr width and n. exc. 1.5 mtr deep for foundation, laying DWC pipes, Complete all as specified and as directed by the Engineer -in-charge.
Returning filling in incl spreading leveling watering and well rammingin layers not exceeding 25 mm levers of soil, Complete all as specified and as directed by the Engineer -in-charge.
Removing excavated materials n. exc 50m and depositing where directed at a level n. exc. 1.5 above the starting point, Complete all as specified and as directed by the Engineer -in-charge.
Supplying, installing, commissioning and testing solar water heating system of capacity 200 LPD comprising of following accessories as per specification given below and all as directedi) Flat Plate Collectorii) Hot water storage tank of 500 LPD capacity inner tank material of high grade stainless steel insulated of 1.0 mm thick stainless steel sheet plain, with stand/ staging made of MS 50X50X6 mm angle iron fixed on the wall/ minereal wool 50mm thickness on the sides with aluminium sheet of 26 SWG size as required, vent and drainage suitable range of temperature gauge 0°C to 100°C, water strainer, copper coil heat exchanger (plain) option with sacrificial pipes, flat plate collector etc, iii) Electric back up heater including thermostat for cut off required temperature, forming part of the solar water heating system all as directed. iv) The rates quoted is inclusive of all taxes & transport. Make : Racold/ V-Guard, TATA or equivalent make.
M&L for cross arms, bracings, supports, clamps and back plates fabricated from strucural steel sections including nuts, bolts, washers,welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated, with & inclusive of one coat red oxide primer & one under coat and one finishing coat of synthetic enamel paint after preperation of surfaces complete all as specified & directed by Engineer-In-Charge.
S&F Rotational moulded polyethylene water storage tanks for back up supply (cylindrical vertical with closed top) hoisted and fixed in position all as specified capacity of 500 Ltr
S&F Bib taps 25 mm, chromium plated cast copper alloy with crunch or buterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed complete all as specified & directed by Engineer-In-Charge.
Supply & Lay CPVC pipes SDR 11 & Plain CPVC SDR 11 fitting in trenches/surface for hot water complete all as specified & directed by Engineer-In-Charge of 25 mm outer dia
Supply & Fix gun metal gate valve ISI marked screwed both ends of 25 mm dia bore complete all as specified & directed by Engineer-in-charge.
Supply & Fix Ball valve suitable for CPVC pipe of outer Dia 25 mm complete all as specified & directed by Engineer-In-Charge
S&F Brass Non-Return Valve 25 mm dia complete all as specified & as directed by Engineer in charge
Supply & Fix float valve assembly complete with PVC ball valve & flynut screwed for iron pipe of 25 mm bore complete all as specified and as directed by Engineer in charge.
Supply and laying on wall ,trenches/ducts or passing through pipe 1100 volt grade LTUG cable with XLPE insulated armored heavy duty electric cable with stranded aluminium conductor 1100V grade 4 core cross sectional area 10 sqmm complete all as specified & directed by Engineer-In-Charge.
Supply & fix Double door sheet metal enclosure distribution board recessed mounting 230 volt SPN DB for DX3/Lexic MCB ,IP 54 IK-09 with metal door, 4 way of Make Legrand cat part No 507640 complete all as specified & as directed by Engineer in charge. (Note: Outgoing MCB will be measuserd & paid under relevant item)
Supply and fix MCB TPN 32 amp,10KA, C curve,DX3 series of Make Legrand cat part no 408680 complete all as specified & as directed by Engineer in charge
S&F Sheet metal enclosure single door with socket plug top and MCBs triple pole and neutral enclosure with 3 pin and earth plug & socket complete with one triple pole MCB of 32 Amps 415 V complete all as specified & as directed by Engineer in charge
Provision of soil resistivity testing by wenners method of 1 location approx area 40X10 Mtr & further recommending the quantity of earth required to achieve the desired results as per requirement, Complete all as specified and as directed by the Engineer -in-charge
Supply & fix in repair copper strip 20x3.15 mm with saddles & fixing screws etc., for roof conductors & down conductors above ground complete including porcelein insulators complete all as specified & as directed by the Engineer-in-charge.
S & F GI tube of 40 mm dia after cutting into required length for Earthing protection at wall fixing arrangement, complete all as specified and as directyed by the Engineer-in-charge.
S & F Test point terminal block made of gun metal or phosphorus bronze size 75x75x25mm drilled and screwed including 3 nos. 8mm dia 25mm long hex. head screw, complete all as specified and as directed by Engineer -in- Charge.
United Enterprises
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .