Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance C 344 GALI NO 2 BLOCK C WEST KARAWAL NAGAR DELHI 110094 | NORTH EAST | DELHI | 110094 | Admitted-Finance |
Tender Value
₹15.3 L
EMD Value
₹30,602
Closing Date
2 Mar 2022, 3:00 pmClosed
Executive Engineer (E)
O/o EE (E), PWD NES/ M-251, LM Bund Road, Ramesh Park, Delhi-92
RMO E and M Services in Lawyers Chambers Block D, E, F, G, H at Distt Court KKD Delhi. (SH- Pdg. of EI and Earthing in Lift Machine Rooms, Shafts, pathway and replacement/ Pdg of burnt-out fittings, cable, MCCBs etc.)
2022_PWD_217284_1
95/EE (E)/PWD NE and Shah. Elect. Divn./2021-22
Open Tender
Electrical Works
Item Rate
60 days
KKD Court Complex
Please refer Tender documents.
2 documents required · 2 mandatory
₹0
₹30,602
4 Mar 2022
23 Feb 2022
2 Mar 2022
23 Feb 2022
2 Mar 2022
23 Feb 2022
Amount
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
3 x 1.5 sq. mm
3 x 4 sq. mm
3 x 6 sq. mm
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 12 Module (200 mmX150 mm)
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.
5/6 A switch
3 pin 5/6 A socket outlet
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, connections etc. as required.
Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12-way, Double door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Supplying, installation, testing and commissioning of new 36 to 40 watt recessed mounted LED Luminaries of size 300 mm (Length) x 1200 mm (Width) housing made with white powder coated CRCA sheet metal and polycarbonate diffuser suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency not less than 120 luman per watt. and colour temperature of 6000 K, CRI >80 with driver having power factor > 0.90, THD < 20% and efficiency > 85% driver should be IC Complete, with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. including connection with 1.5 sq. mm. PVC insulated copper conductor FRLS cable with the help of 4 nos. fastener Hook, Clutch wire and sleeve i/c testing, commissioning etc. complete as required.
Supplying, Installation, Testing & Commissioning of LED bulkhead fitting with following technical specification: - i). System Lumen output >1000 ii). System Efficiency >100 lm/Watt iii). Input Power not more than 10 W iv). CCT >5700, CRI> 70, PF > 0.95, THD< 10% v). Life 50 K hours @ L70
Supplying, Installation, Testing & Commissioning 18 to 20 watt 1200 mm long high efficiency LED linear batten Luminaries having aluminium extruded housing and polycarbonate diffuser within built APFC driver having efficiency of driver 85% power factor > 0.90, THD <20% with minimum 2.5 KV surge protection, LED life with L-70 criteria shall be not less than 50000 burning hours etc. suitable for operation on 150 to 265V single phase A.C. supply, having system efficiency 120 luman per watt and colour temperature of 6000 K, CRI >80 including connect ion with 1 5 sq. mm PVC insulated copper conductor FRLS cable i/c dismantling of existing old fitting if any etc. complete as required.
Supplying and Fixing 380 mm dia 900 RPM heavy duty exhaust fan suitable for operation on 230 volt, ±10%, 50 Hz supply to fixed on wall i/c connection with 1.5 Sq.mm PVC insulated PCV sheathed copper conductor single core cable i/c testing etc. as reqd.
Supplying and Fixing 300 mm dia 900 RPM heavy duty exhaust fan suitable for operation on 230 volt, ±10%, 50 Hz supply to fixed on wall i/c connection with 1.5 Sq.mm PVC insulated PCV sheathed copper conductor single core cable i/c testing etc. as reqd.
Supplying, Installation, Testing and Commissioning of 1200 mm sweep ceiling fan, made out of aluminium housing and aluminium blades ISI marked and 5-star rating including wiring the down rods of standard length (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable, including providing and fixing M.S flat Fan hook if required etc. complete as required.
Replacement of defective/worn-out MH/SV Flood light fitting by Supplying, Installation Testing and Commissioning of 150-watt LED Flood Light fitting aluminium die cast housing, IP 66 with high power LED as light source, system lumen efficiency of ≥ 120 lm/W, colour rendering (CRI) ≥ 70, and correlated colour temperature (CCT) of 5500 - 6500 (±300K). The luminaries should have 10KV surge protection, PF≥0.95, the total harmonic distortion≤ 10% operatable in voltage range of 120-270 V, total burning hours 50000 with LM 70/79/80 Certificates The driver used must be a constant current driver with efficiency of ≥ 85% and driving current ≤ 725mA complete r on surface with suitable fasteners as required and as per direction of Engineer-In charge. i/c dismantling of existing fittings. The manufacturer should provide LM 80 reports along with warrantee of 5 years for luminaires i/c drivers etc. as required.
Replacement of defective/worn-out Flood/ high mast light fitting by Supplying, Installation Testing and Commissioning of 250-watt LED High Mast/ Flood Light fitting aluminium die cast housing, IP 66 with high power LED as light source, system lumen efficiency of ≥ 120 lm/W, colour rendering (CRI) ≥ 70, and correlated colour temperature (CCT) of 5500 - 6500 (±300K). The luminaries should have 10KV surge protection, PF≥0.95, the total harmonic distortion≤ 10% operatable in voltage range of 120-270 V, total burning hours 50000 with LM 70/79/80 Certificates The driver used must be a constant current driver with efficiency of ≥ 85% and driving current ≤ 725mA complete r on surface with suitable fasteners as required and as per direction of Engineer-In charge. i/c dismantling of existing fittings. The manufacturer should provide LM 80 reports along with warrantee of 5 years for luminaires i/c drivers etc. as required.
Replacement of defective/ burnt-out fittings by Supplying, Installation Testing and Commissioning of LED Post Top fittings of range 40 watt round spigot shaped with 40-watt LED lamp suitable for use on single phase AC supply 50 Hz having pressure dia cast housing with IP- 65 protection including dismantling of old fittings, connection with 2.5 sq. mm. FRSL copper wire, testing and commissioning etc. complete as required.
Providing and fixing pole box of size 250mm X 200mm X 105mm (product code GSJB2520) with side openable hinged cover complete with two strip aluminium bus-bar of 100 amps capacity mounted on DMC bus support and 1 no. of SPMCB of 6 amps 'C' series capacity with din rail on the existing street light pole with the help of two nos. MS clamps of suitable size, including making hole to insert the cable and dismantling the worn out MS box etc. complete as required.
Supplying and fixing of 600 mm. sweep Air Circulator wall fan suitable of operation on single phase 230 volts 50 Hz. on existing wall/ surface i/c connection with 4 sq. mm. FRLS PVC insulated copper conductor cable etc. complete as required.
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required.
400 A, 35 kA, TPMCCB
250 A, 35 kA, TPMCCB
150 A, 16 kA, TPMCCB
100 A, 16 kA, TPMCCB
Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32 A, 240 V “C” curve DP MCB complete with connections, testing and commissioning etc. as required.
Earthing with G.I. earth pipe 4.5-meter-long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required.
Supplying, Installation, Testing and Commissioning of 70-watt LED Flood Light fitting aluminium die cast housing, IP 66 with high power LED as light source, system lumen efficiency of ≥ 120 lm/W, colour rendering (CRI) ≥ 70, and correlated colour temperature (CCT) of 5500 - 6500 (±300K). The luminaries should have 10KV surge protection, PF≥0.95, the total harmonic distortion≤ 10% operatable in voltage range of 120-270 V, total burning hours 50000 with LM 70/79/80 Certificates The driver used must be a constant current driver with efficiency of ≥ 85% and driving current ≤ 725mA complete r on surface with suitable fasteners as required and as per direction of Engineer-In charge. i/c dismantling of existing fittings. The manufacturer should provide LM 80 reports alongwith warrantee of 5 years for luminaires i/c drivers etc as required.
Supplying & Laying of 2x6 sq. mm. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with amendment No. 1 direct on surface/ wall i/c connection etc. as required.
Supplying & Laying of one Number 3x10 sq. mm. XLPE insulated PVC outer sheathed armoured with galvanized round steel wire or strip cables with standard aluminium conductor suitable for rated voltage of 1.1 KV grade ISI marked confirming to IS 7098 / (Pt.-I)/88 with amendment No. 1 in following manners.
In Loose & Connection/Open duct
On surface
Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE Aluminium Conductor armoured power cable of 1.1 KV grade as reqd. 3 X 10 sq. mm (22mm)
Credit & buy back of old dismentalled material received from the work.
Assorted Fl. Fitting
Exhaust Fans
Ceiling Fans
Assorted flood/street light fittings
Wall circulators fans
Assorted MCCB
Pole Box
MCB's/Isolator
Assorted material like wire, conduit, switches, sockets, fan regulators, plats etc.
A K Enterprises
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .