Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹15.9 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹16.7 L+₹84,628 (5.32%)Rejected-Finance F IA 24 4210 CO JAYKRISHNAPUR P O BEGAMPUR DIST HOOGHLY | BEGAMPUR | HOOGHLY | WEST BENGAL | L2 | Rejected-Finance Rejected_Fin | |
| 3 | L3₹23.4 L+₹7.5 L (47.2%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | L3 | Rejected-Finance Rejected_Fin | |
| 4 | Rejected-Technical SRINIKETAN ROAD BOLPUR BIRBHUM 731204 | BOLPUR | BIRBHUM | WEST BENGAL | 731204 | - | Rejected-Technical Rejected_Technical |
Tender Value
₹15.9 L
EMD Value
₹31,801
Closing Date
28 Oct 2024, 12:00 pmClosed
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
75 Diamond Harbour Road Kolkata 23
SITC of Air Conditioning system for Renovation and Remodelling of Radiology Department at 1st Floor of Emergency Building in the campus of IPGMER SSKM Hospital Kolkata
2024_WBPWD_736855_1
WBPWD/EE-I/KSHED/Q22/24-25/2nd call
Open Tender
A/C ORG
Item Rate
60 days
SSKM Hospital Kolkata
Please refer Tender documents.
3 documents required · 3 mandatory
₹31,801
O/O Exe. Engr, Kolkta South Health El. Divn, PWDte
4 Apr 2025
21 Aug 2024
30 Oct 2024
21 Aug 2024
28 Oct 2024
27 Aug 2024
27 Aug 2024
Amount
S&D of minimum 13KW nominal cooling capacity ceiling suspended [ concealed] Split Air Conditioner with R410A / R407C / R-32 Refrigerant, with single Scroll Compressor / Swing compressor in inverter machine, suitable for operation on 415V,+_ 5% , 50Hz, 3Ph AC Supply. with precharged refrigerant, Wired/ Wireless remote & all other accessories (Make : DAIKIN model FDMF140BRV16/ RZMF140BRV16 / Mitsubishi heavy industries model FDUM125CSV-S6/FDC125CSV-S6 / O General model ARG60F/AOG60F).
Installation testing & commissioning of above AC machines at 1st floor by fixing the indoor with two number 1.5 mt long MS "C" channel of sizes 80mmX40mmX 6mm with minimum 6nos 10mm X75mm anchor fastner bolt drilled into the ceiling. The indoor unit suspended from this "C" channel support with 4 nos 40mm X 6mm MS flat & 10mm full threaded suspender bolt with double nut & spring washer. (Out door unit will be fixed on pre fabricated MS platfrom on 2nd floor height.) [All MS Structure should be painted with one Coat of good Quality red oxide paint and 2 Coat of enamel Paint and all nut,bolt and washer Should be stainless steel grade]
S&D of minimum 10.55KW nominal cooling capacity ceiling suspended [Concealed] medium static, Split Air Conditioner with R410A / R407C / R-32 Refrigerant having single Scroll Compressor / Swing compressor for inverter machine, suitable for operation on 415V,+_ 5% , 50Hz, 3Ph AC Supply. with precharged refrigerant, Wired/ Wireless remote, filter & all other accessories (Make : DAIKIN model FDMF100BRV16/ RZMF100BRV16 / Mitsubishi heavy industries model FDUM100CSV-S6/FDC100CSV-S6 / O General model ARG36F/AOG36F).
Installation testing & commissioning of above AC machines at 1st floor by fixing the indoor with two number 1.5 mt long MS "C" channel of sizes 80mmX40mmX 6mm with minimum 6nos 10mm X75mm anchor fastner bolt drilled into the ceiling. The indoor unit suspended from this "C" Channel support with 4 nos 40mm X 6mm MS flat & 10mm full threaded suspender bolt with double nut & spring washer. (Out door unit will be fixed on pre fabricated MS platfrom on 2nd floor height.) [All MS Structure should be painted with one Coat of good Quality red oxide paint and 2 Coat of enamel Paint and all nut,bolt and Washer Should be stainless steel grade]
S&D of minimum 7KW nominal cooling capacity ceiling suspended [Concealed] medium static, Split Air Conditioner with R410A / R407C / R-32 Refrigerant having single Rotary Compressor / Swing compressor for inverter machine, suitable for operation on 240V,+_ 5% , 50Hz, 1Ph AC Supply. with precharged refrigerant, Wired/ Wireless remote, filter & all other accessories (Make : DAIKIN model FBQ71DV1+RZQ71KCV4A Mitsubishi heavy industries model FDUM71CNV-S6 / O General model ARG25** + AOG25**).
Installation testing & commissioning of above AC machines at 1st floor by fixing the indoor with two number 1.0 mt long MS "C" channel of sizes 65mmX32mmX 6mm with minimum 6nos 10mm X75mm anchor fastner bolt drilled into the ceiling. The indoor unit suspended from this "C" section support with 4 nos 10mm full threaded suspender bolt with double nut & spring washer. (Out door unit will be fixed on pre fabricated MS platfrom on 2nd floor height.) [All MS Structure should be painted with one Coat of good Quality red oxide paint and 2 Coat of enamel Paint and all nut,bolt and washer should be stainless steel grade]
Supply & Laying of Refrigerant Copper pipe of following diameter for connecting of Indoor to Outdoor unit, along with drip resistant nitrile rubber insulation with double insulating wrapping tape to avoid dripping of condensate water:-
Discharge Line 9.5mm dia, min. thickness 0.8mm with 9mm thick nitrile insulation. (Make : Rajco / Mandev).
Suction Line 15.88mm dia, min. thickness 0.99mm with 9mm thick nitrile insulation. (Make : Rajco / Mandev).
Suction Line 19.05mm dia, min. thickness 0.99mm with 9mm thick nitrile insulation. (Make : Rajco / Mandev).
Supply & Laying of PVC insulated unarmoured 1.1 KV grade 6 Core 2.5sq mm copper cable from indoor to outdoor unit with necessary fixing arrangement. (Finolex / Polycab / Havells)
Supply & Laying of PVC insulated unarmoured 1.1 KV grade 4 Core 2.5sq mm copper cable from indoor to outdoor unit with necessary fixing arrangement. (Finolex / Polycab / Havells)
Wrapping the copper pipe with insulation & electric cable by S/F 26SWG Aluminimum sheet to make it weather & vermin proff.
9.5mm dia with 9mm thick nitrile insulation, 15.88mm dia with 9mm thick nitrile insulation & 4 core 2.5Sqmm Copper cable.
9.5mm dia with 9mm thick nitrile insulation, 19.05mm dia with 9mm thick nitrile insulation & 6core 2.5Sqmm Copper cable.
Supply & laying drain Water piping work with 25 mm dia Schedule 40 PVC/ UPVC hard pipes (Finolex / Ashirbad / Supreme) incl. fitting , accessories bends, elbows, tees, flanges, tapings, etc. insulated with 9mm. thick nitrile rubber tube insulation.
S&F flexible canvas connection for indoor to duct/ air terminal for
7KW indoor
10.55KW indoor
13KW indoor
SITC of Powder Coated Al. Grill without VCD suitable size (Make:Systemair / Primier)
S & providing drop ceiling to cover the indoor units & supply air duct including the cost of 3mm thick outdoor type ACP sheet as per manufacturer's specification on the frame work fabricated from Aluminium hollow rectangular section of size 50mm x 25mm (2mm thick) & duly suspended by Aluminium hollow rectangular section of size 50mm x 38mm (2mm thick) and silicon sealent complete in all respect including making trap door arrangement as per direction of EIC. (Make:Aludecor/Armstong)
M.S. structural works in columns, beams etc. with simple rolled structural members (e.g. joists, angle, channel sections conforming to IS: 226, IS: 808 & SP (6)- 1964 connected to one another with bracket, gussets, cleats as per design, direction of Engineer-incharge complete including cutting to requisite shape and length, fabrication with necessary bolting, metal arc welding conforming to IS: 816- 1969 & IS: 1995 using electrodes of approved make and brand conforming to IS:814- 2004, haulage, hoisting and erection all complete. The rate includes the cost of rolled steel section, consumables such as electrodes, gas and hire charge of all tools and plants and labour required for the work including all incidental chages such as electricity charges, labour insurance charges etc. I) For structural members of specified sections weighing less than 22.5 Kg./m(Necessary Fabricated ladder,Red oxide and enamel Painting, Brick Wall cutting ,Grouting and Masionary work for making AC outdoor unit platfrom)
Box type scaffolding charges for structual works upto 2nd floor for SITC of AC machine & outdoor units.
Supplying & Fixing of PVC water proof type Loop box (Make-Sintex GSJB2520 /Hensel) of size [250X200X100]mm having hinged PVC top cover & 4 mm thick with rubber gasket lining,railway type mechanical locking arrangement, with DIN rail. on wall as per direction of EIC.
S.I.T.C. of Crono time switch [Make - L&T Cat. No. 67DDT0]
S & F of 3 pole 25A/32A DIN rail mounted Power contactor with 240V operating coil [ make L&T/ ABB/ Siemens/ Schneider].
Supply and fixning of of Supplying and fixing 240/415 V MCB of Breaking capacity 10kA & C characteristics on din rail of existing DBs and necessary connection (Make - Legrand)
16 A DP MCB
16 A TP MCB
Supply and fixing of 32A PVC terminal block on din rail (Make - Legrand)
TERMS & CONDITIONS :- The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Defect Liabibility Period 1 (One) year
Make & model of each and every material to be approved by EIC
P. M. COOLING AND ENGINEERING CO (BID ID -5724568)
Shinryo Suvidha Engineers India Pvt. Ltd. (BID ID -5553814)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .