Supply, Installation, Testing and commissioning of Fire hydrant landing valves and piping accessories at E.C. Rangreth.
2021_SIDCO_119784_1
SIDCO/CONSTT/Div./1ST/10
Open Tender
Civil Works - Others
Item Rate
90 days
Budgam
as per NIT
4 documents required · 4 mandatory
₹6,000
Executive Engineer Constt Div 1st JK SIDCO Haftchi
Exempted
Office of the Executive Engineer Constt Div 1st JK
5 Apr 2021
9 Mar 2021
29 Mar 2021
9 Mar 2021
27 Mar 2021
13 Mar 2021
24 Mar 2021
Amount
Note: Contractor should Quote Rates with all taxes.
Supply and Fixing of MS Pipe of size 100 mm. of IS 1239/3589 specs pipe including cutting, welding, supply and fixing of GI/MS Nipples/Reducers, Sockets, Tank Nipples, , etc complete at various locations as under :- C Class Make - Jindal/Prakash Surya
For interconnection of the existing GI Pipeline with Fire Hydrant Landing Valve including red oxide coating and red paint at various locations
Providing and Fixing of below mentioned piping accessories
MS Flanges including Nuts/Bolts Size = 100 mm Dia
Rubber Washers Size = 100 mm Dia
MS Flange (Large Size) - Dia - As required with coupling of Fire hydrant valves.
GI/MS Tee Size = 100 mm Dia
GI/MS Elbow (100 mm) Long size (around 1'6" length)
Earthwork in excavation by manual means in trenches a. For foundation of MS Angle Iron and MS Flat Iron framed Fire Hydrant Cabinets of all classfications including disposal of excavated earth beyond site or as directed at site of work.
Providing and laying of stone soling including watering ramming dressing levelling and consolidation by hand hammer and carriage complete a. For New Fire Hydrant Landing Valves 1 x 2'6" x 2'6" x 0'2" x 20 No.
Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering all works upto plinth level in 1:2:4 mix ( 1 cement :2 coarse sand : 4 graded stone aggregrate 40mm nominal size crushed including all carriages complete. For New Fire Hydrant Landing Valves 1 x 3'0" x 3'0" x 2'6" x 20 No. = 450 cft
CMS Framed Structure for enclosure of Fire Hydrant Landing Valves.Structural steel work in single section fixed with connecting plate including cutting hoisting fixing in position and applying a priming coat of approved steel primer including sign boards (as FH Valve)depicting the fire hydrant valve system including red oxide coating and red paint. complete. Steel cabinet with glass door and lock facilities. For 20 New Fire Hydrant Landing Valves
Providing lock to the fire hydrant steel enclosure Make - Thapar
Providing and Fixing of Steel Hinges 4" including welding, fixing, etc complete
Providing and Fixing of Handle 6" Size - 25mm x 5mm
Design, Construction, Testing &Commissioning of RCC Reservoir of 150000 lts. capacity on Turn Key basis including fixing of C-Class MS Pipes for inlet/outlet washout and over flow facilities with contol valves and all necessary accessories such as lightening arrester, water level indicator, RCC/MS stair, man hole covers with frame with locking arrangements, standard pipe fittings etc. all complete including appropriate capacity Pumping and Piping system. The job includes design of reservoir on the basis of foundation bearing capacity of the soil. (The design should be vetted by Design Directorate Srinagar)
Supply and Installation of Non percolating fire delivery hose of 70 mm. Diameter bound with GM couplings (Male-Female) of 63 mm. dia. (IS 636-1988) of 15 mts. Length - 02 lengths for each hydrant with one emergency (short) branch with GM Nozzle compatible with the above Landing Valves for each hydrant. The two fire hoses, the branch pipe and other related hydrant accessories shall be kept in a steel cabinet with glass door with locking facility. The steel cabinets to be kept in close custody of nearest unit holder for security reasons.
Supply and Installation of ABC stored pressure type fire extinguishers MAP90 consisting of welded M.S. cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 30 cms long high pressure discharge hose, discharge nozzle, suspension bracket, confirming to IS 13849-1993 finished externally with red enamel paint and fixed to wall with brackets with rawl plug / dash fasteners complete with internal charge for building. With all accessories/fittings as per approved standards a) Capacity 6.0 kg I.S.I marked
Supply and Installation of CO2 fire extinguishers fitted with discharge horn and provided with all accessories/fittings as per approved standards confirming to IS 2878-2004 fixed to wall with brackets with rawl plug / dash fasteners complete with internal charge for buildings a) Capacity 4.5 kg I.S.I marked
Supply and Installation of overload trip off by way of installation of electrical safety equipments outside all the buildings for all the elecrical equipments inside the building
FIRE ALARAM DETECTION SYSTEM
Providing and fixing MS conduit of 16 SWG ISI marked (15:9537-1981, Part-11) complete with all fittings viz. tees, bends, junction boxes, clamps/supports etc. to be concealed in slabs/brick work as required or surface laid. 20mm dia
Providing and laying in PVC conduit PVC insulated ISI marked copper control cable in existing conduit (IS:694) from individual flow switches on each floor to annunciation panel installed in fire control room including sleeves cable clips, supports for horizontal runs etc. complete of size
Supplying, installing, testing and commissioning of following items in real/false/wall in M.S junction box with all installation accessories as per requirement.
i) Analog addressable multisensing detector below false ceiling (Photoelectric sensor for smoke and heat detector) with bases.
ii) Control Relay Module as per the specification.
iii) Addressable type Manual Call Point (Pull Station) as per specification.
PSupplying, installing, testing and commissioning of annunciating panel with Addressable Hooter-cum-Strobe Unit (including control module) having desired control zone and zone indications along with 240 V battery and battery chargr to be mounted on wall surface including supply of all installation material, interconnections, cutting chases on wall and mending good the damages, painting, earthing, complete as required.
Supply Installation Testing and commissioning of hooters
Repairing of Wall of all buildings by way of Paint, Plaster, Cement, etc and making the base for pumps
FIRE TECHNOS
M/S ZAIM ENGINEERS KHANMOH SRINAGAR KASHMIR
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .