CHIEFCONSTRUCTIONENGINEERCENTRALRANDBCIRCLEBBSR
OFFICE OF THE CHIEF CONSTRUCTION ENGINEER, CENTRAL RANDB CIRCLE, BHUBANESWAR
Construction of Central Ware House GPlus3 for Medicine at Government Ayurvedic Hospital Campus, Bhubaneswar, Odisha for the year 2025-26.
2026_EICCL_124175_1
TENDER CALL NOTICE NO.21 OF 2025-26
Open Tender
Civil Works - Buildings
Percentage
365 days
Bhubaneswar
Please refer Tender documents.
2 documents required · 2 mandatory
₹10
₹6.5 L
Yes
6 Jan 2026
3 Jan 2026
15 Jan 2026
3 Jan 2026
15 Jan 2026
3 Jan 2026
CIVIL WORK
Dismantling brick or stone masonry in lime or cement mortar under 3m. height including stacking the useful materials for reuse and removing the debris within 50m. Lead
(a)First Floor
Dismantling brick or stone masonry in lime or cement mortar under 3m. height including stacking the useful materials for reuse and removing the debris within 50m. Lead
(a)First Floor
Clearing and grubbing roads and land including uprooting rank vegetation, grass, bushes, shrubs, saplings and trees girth up to 300 mm, removal of stumps of trees cut earlier and disposal of unserviceable materials and stacking of serviceable material to be used or auctioned, up to a lead of 1000 metres including removal and disposal of top organic soil not exceeding 150 mm in thickness.
(a)Ground Floor
Earth work in excavation in foundation trenches, column foundation, pit, etc in all kind of soil including moorum stony earth and earth mixed with boulders except sheet rock and boulders not requiring blasting including dressing of sides and levelling the bed up to the required depth and depositing the excavated materials away from the work site with initial lead of 50 mtr and all lifts, including shoring, shuttering & dewatering (if required) with cost of labour, labour cess, hire & running charges of all machineries, sundries & T&P required for the work complete as directed by the Engineer in charge.
(a)up to 1.5m depth
(b)1.5m to 3.00 m depth
Filling in Foundation, Plinth and other low laying area with excavated materials including cost of all labour, T&P etc complete including watering and ramming as directed by the Engineer-in-charge .
(a)Ground Floor
Supplying, Diluting and Preparing Chemical Emulsion like CHLORPYRIPHOS or other chemicals approved by Central Insecticides Board or as directed by the manufacturer and spraying the mixture uniformly by sprayer as pre-constructional Anti Termite Treatment and creating a chemical barrier under and around the column pits, wall trenches, basement excavation, top surface of plinth filling, junction of walls and floors along with external perimeter of the building, expansion joints, surrounding the pipes and conduits etc. complete at the rate of 7.5 liters (or as directed by the manufacturer) per sqm on vertical and 5.0 liters per sqm on horizontal surfaces, 50% of the emulsion to be filled in the holes made in trenches at 150mm center to center etc.complete as per IS:6313/1981(Part-II) and as per the direction of the Engineer-in-charge including cost of all materials, labour, taxes, etc. complete.
(a)Ground Floor
Supplying and filling in foundation and plinth with sand including watering and ramming, poking and compacting including cost, conveyance, royalties, taxes of the materials and cost of all labour, labour cess, T&P etc. required for the work complete as directed by the engineer-in-charge.
(a) Ground Floor
Providing and laying Plain Cement Concrete of proportion (1:3:6) using 4 cm. size black hard crusher broken granite stone metal and screened and washed sharp sand for mortar of approved quality and from approved quarry including the cost of all materials, cost of labour, conveyance, taxes, royalties, loading, unloading, shuttering, centering, curing, labour cess, T&P, etc. all complete as per the direction of engineer-in-charge.
(a)Ground Floor
Providing, lifting, hoisting and laying in position machine batched , machine mixed and machine vibrated Design Mix Cement Concrete of M-25 Including the cost of Centering and Shuttering (minimum cement content not less than 407 Kg/Cum) grade in reinforced cement concrete structural elements using black hard crusher broken granite chips of approved quality from approved quarry including mixing and compacting to proper shape and size, level and plumbs and finishing the exposed surfaces smooth including the cost of all materials, cost of labour, conveyance,loading, unloading, royalties, watering and curing for the required period, T&P , hire & running charges of concrete mixer and vibrator, cost of Admixtures in recommended proportions ( as per IS 9103 ) to accelerate, retard setting of concrete, improve workability without impairing strength and durability etc. complete as per the direction of the Engineer-in-charge but excluding the cost of steel reinforcement.
R.C.C. Foundation and Footing Bases of Columns Mass Concrete Pre-Cast Slab etc.
(a)Ground Floor
R.C.C. Grade Beams
(a)Ground Floor
R.C.C. Columns
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
R.C.C. Roof Beams
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
R.C.C. Lintel
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
R.C.C. Chajja
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
R.C.C. Stair Case
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
R.C.C. Floor and Roof Slab, Landing, Balconies, Projecting Sun Shades and Chajjas up to 4.3 Mtr. Height.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
R.C.C. Shelve
(a) Ground Floor
R.C.C. Wall
(a)Ground Floor
(b)Terrace Floor
Providing & fixing TOR Fe-500 HYSD Reinforcement Bars (SAIL /TATA /RINL) of required diameter and approved quality for Reinforced Cement Concrete work including straightening, cutting, bending, binding, welding(if approved) , joining (if necessary), tying the grills, hoisting, lowering and placing in position as per the approved design & drawings (BBS) with provision of standard fan hooks including the cost of all materials, cost of all labour, conveyance, loading, unloading, cost of binding wires of 18 to 20 gauge, T&P, etc, all complete as per the direction of Engineer-in-Charge. Note: (Linear measurements will be taken & quantity will be calculated on standard weight. Lap length of bars & Weight of binding wire will not be considered for measurement and payment.)
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing Fly-Ash Brick masonry work in Foundation & Plinth using Fly-Ash Bricks of size 250mm x 120mm x80mm having crushing strength not less than 75Kg/Sqcm in cement mortar (1:6) including the cost of all materials, cost of labour, conveyance, taxes, loading, unloading, royalties, labour cess, scaffolding, curing for required period, T&P, etc. all complete as per the direction of the engineer-in-charge.
(a) Ground Floor
Providing 1st class Fly Ash Brick Masonry Work Using (250mmx120mmx80mm) Size Fly-Ash Bricks having crushing strength not less than 75Kg/Sqcm in Cement Mortar (1:6) after immersing the bricks for minimum 6 hours in water before use with all necessary projections, splays cutting, circular moulding, coFBelling etc as per drawings. including cost, conveyance, all taxes, royalties, loading and unloading of all materials, including cost of all labour, scaffolding, watering and curing, sundries, T&P etc. complete as per the direction of the Engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing and laying Brick masonry work in Superstructure using Fly-Ash bricks confirming to IS 12894 and IS 2212 in cement mortar (1:4) for Half Brick Masonry Wall with provisions for 2 nos 6mm dia MS bar at each 4th layer after immersing the bricks for minimum 6 hours in water before use, with all necessary projections, splays cutting, circular moulding, corbelling, etc. as per the drawings including the cost of all materials, cost of all labour, conveyance, royalties, loading, unloading, scaffolding, staging, watering and curing, sundries, T&P, etc. complete as per the direction of the Engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing 12mm thick cement Plaster in Cement mortar (1:6) to the surface of brick masonry wall including racking out joints, scraping and cleaning the surface and finishing the plaster surface smooth using wooden floats, bars, etc only to proper plumbs and level and making grooves, beads and drip coarse to give required ornamental finish as per drawings including cost of all materials, conveyance, loading and unloading,royalties, cost of labour, scaffolding, staging, watering before plastering and curing, sundries and T&P, etc. complete as per direction of the Engineer-in-charge.
(a) Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing 12mm thick Cement Plaster in Cement Mortar (1:4) to the surface of half brick masonry wall including racking out joints, scraping and cleaning the surface and finishing the plaster surface smooth using wooden floats, bars, etc only to proper plumbs and level and making grooves, beads and drip coarse to give required ornamental finish as per drawings including cost of all materials, conveyance, loading and unloading, royalties, cost of all labour, scaffolding, staging, watering before plastering and curing, sundries and T&P, etc. complete as per direction of the Engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing 16mm thick cement plaster in cement mortar (1:6) to the surfaces of brick masonry wall including racking out joints, scraping and cleaning the surface and finishing the plaster surface smooth using wooden floats, bars, etc only to proper plumbs and level and making grooves, beads and drip coarse to give required ornamental finish as per drawings including cost of all materials, conveyance, loading and unloading, royalties, cost of labour, scaffolding, staging, watering before plastering and curing, sundries and T&P, etc. complete as per direction of the Engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing 6 mm thick cement plaster in cement mortar of (1:4) to RCC work including roughening, scraping, cleaning and finishing the plastered surface smooth using wooden floats with proper plumbs and level including the cost of all materials, cost of labour, conveyance, loading and unloading, all taxes and royalties, scaffolding, watering and curing , sundries, T&P etc. complete as per direction of the Engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Supplying, fitting and fixing in proper position dressed seasoned sal wood chaukaths of best quality with applying coal tar 2 coats coaltar on the wall side surface of the choukath including cutting the grooves in chaukaths including cost of all materials, labour, conveyance, taxes, T&P etc. complete.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Supplying and fixing W.I. clamps 33cm to 38Cm long of 35mm × 5mm size for doors, windows and ventilators including fixing in cement concrete (1:3:6) with 12mm, to 20mm hard stone chips or in cement mortar (1:3) including cost of all materials.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Supplying, fitting and fixing of 32mm thick flush door shutter with approved quality of 30mm thick BWR block board pasted with 1mm thick sunmica on both side of approved design and quality including cost of all door fittings and fixtures etc. complete
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Providing and fixing 50 mm thick powder coated Fire Resistant GI pressed door shutters with frame of SIGNUM make of 60 minutes fire rating conforming to IS:3614 (Part-II), tested and certified as per laboratory approved by Engineer-in-charge, with suitable mounting on door frame, consisting of vertical styles, lock rail, top rail 100 mm wide, bottom rail 200 mm wide, made out of 16 SWG G.I. sheet (zinc coating not less than 120 gm/m2) duly filled FR insulation material and fixing with necessary stainless steel ball bearing hinges of approved make, including applying a coat of approved fire resistant primer etc. all complete as per direction of Engineer-in-charge.
(a)First Floor
(b)Second Floor
(c)Third Floor
Providing and fixing Structural Glazing with 5 mm thick reflective glass (Approved Make) provided on 1.2 mm thick Aluminium soft frame of section 19 mm x 19 mm fixed on powder coated structural Aluminium frame work made with 2 mm thick section of 100 mm x 48 mm size sealed with silicon sealant etc complete with all labour, cost of all materials and T & P etc. complete as per direction of engineer-in-charge.
(a) Ground Floor
Supplying , fitting and fixing of two track UPVC sliding window /Ventilator of approved make with 6mm thick glass of approved quality complete with frame, shutters and all fitting and fixtures.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Supplying, fitting and fixing of G.I. Grills in Gate & windows made out of G.I. square bars, angles, flats, etc painted with red oxide primer cost of all materials, labour, conveyance, taxes, loading, unloading, T&P, etc. all complete.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Supplying and finishing the plastered surface of wall using Cement Based Wall Putty (Water Based) of approved make and quality and finished smooth and even surface to receive the paint including the cost of all materials, cost of all labour, conveyance, taxes, loading, unloading, scaffolding, T&P, etc, all complete as per the direction of Engineer-in-Charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing and Painting with Two Coats Weather Coat Paint (exterior grade) of approved make & shade manufactured by reputed manufacturer like NEROLAC / ASIAN / BERGER / DULOX or equivalent to make an even finished surface over a coat of water bound cement primer and wall putty in all heights with all scaffolding and staging charges including cost, conveyance, cost of all labours, T & P, sundries etc. as required for the work complete.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing and applying 2 Coats Plastic Emulsion Paint of approved quality and shade over a coat of wall primer of approved quality to surfaces (interior) including throughly brushing the surface free from foreign materials, sand papering smooth the intermediate coats, providing necessary putty & primer including of all materials, labour, conveyance,royalties, scaffolding, watering, curing, sundries, tools and plants etc as per the direction of Engineer-in-charge. (colour & shade to be approved before procurment & use)
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Painting Two Coats of Synthetic Enamel Paint over Iron Works as per approved shade of approved quality over a coat of primer, sand papering, polishing the surface including cost, conveyance,labour, T&P, scaffolding etc. as required for the work complete as per direction of Engineer-in-charge. (The paints and primer are to be approved before procurement and use).
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing & laying Granite Stone Flooring in Floors and Landing using 20 mm thick Granite Stone Slab of approved quality, colour and size above 0.4 Sqm as per IS 14223 laid over an under layer of 20 mm thick cement mortar (1:4) (1 cement: 4 coarse sand) confirming to IS-1443 including cutting to size, laying and filling the joints with white cement slurry mixed with colouring pigment to match the shade and colour, cleaning the surfaces with oxlaic acid, machine grinding, mirror polishing including the cost of all materials, cost of all labour, conveyance, royalties, loading, unloading, sundries, watering and curing, T&P, etc. complete as per the direction of the Engineer-in-Charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing & laying Granite Stone tiles in Dado/Skirting using 10mm thick Granite Stone Slab of approved quality, colour and size above 0.4 Sqm as per IS 14223 to proper line, level and slope laid over 12mm thick cement mortar (1: 3) confirming to IS IS-1443 including cutting to size, laying and filling the joints with white cement slurry mixed with colouring pigment to match the shade and colour, cleaning the surfaces with oxlaic acid, machine grinding, mirror polishing including the cost of all materials, cost of all labour, conveyance, royalties, loading, unloading, sundries, watering and curing, T&P, etc. complete as per the direction of the Engineer-in-Charge. (Note- Sample of tiles shall be approved before procurement and use.)
(a) Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing & laying Granite Stone Flooring using 20 mm thick Granite Stone Slab of approved quality, colour and size between 0.4 Sqm. to 1.0 Sqm. & above in Stair Case Treads and Risers over an under layer of 20 mm thick cement mortar (1:4) (1 cement: 4 coarse sand) confirming to IS-1443/1972 including cutting to size, laying and joining with white cement slurry and colouring pigment to match the shade including cost of all labour, materials,royalties, loading and unloading, conveyance, sundries, watering and curing, making three nos horizontal grooves in treads etc. complete as per the direction of the Engineer-in-Charge. (Note- Sample of stone tiles shall be approved before procurement and use.)
(a) Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Providing, fiting and fixing of 16mm thick kota stone flooring using kota stone of approved quality, colour and size above 0.10 sqm in floors over an under layer of 20 mm thick cement mortar (1:4) (1 cement: 4 coarse sand) confirming to IS-1443/1972 including cutting to size, laying and joining with white cement slurry and colouring pigment to match the shade, machine grinding, cleaning with oxalic acid, mirror polishing the surface including cost of all labour, materials, taxes, royalties, loading and unloading, conveyance, sundries, watering and curing, etc. complete as per the direction of the Engineer-in-Charge.
(a) Ground Floor
(b)Terrace Floor
Providing, fitting and fixing of 16mm thick finished kota stone in dado/skirting using Kota stone of approved quality,colur and size over 12mm thick cement mortar (1:3) (1 cement: 3 coarse sand) confirming to IS-1443/1972 including cutting to size, laying and joining with white cement slurry and colouring pigment to match the shade,machine grinding, cleaning with oxalic acid, mirror polishing the surface including cost of all labour, materials, taxes, royalties, loading and unloading, conveyance, sundries, watering and curing, etc. complete as per the direction of the Engineer-in-Charge.
(a) Ground Floor
(b)Terrace Floor
Supplying, fitting and fixing Mattfinished Vitrified Tiles in floors of size 600mm x 600mm (Plain/Ivory) of approved make confirming to IS:13755 laid on 20mm thick cement mortar (1:4) (1 cement : 4 Course Sand) and filling joints with white cement of approved quality including cost, conveyance, taxes, cost of all labour, labour cess, etc. all complete.
(a) Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Supplying, fitting and fixing vitrified tiles in dados, skirting and risers of steps on 12mm thick cement mortar (1:3) jointed with neat cement slurry mixed with colouring pigments to match the colour and shade including the cost of washing, polishing, cost of materials, cost of all labour, conveyance, taxes, loading & unloading, T&P, watering and curing etc. complete.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Supplying, fitting and fixing Vitrified industrial floor tiles of appoved make and size (300mm x 300mm) confirming to IS:4457 laid on 20mm thick cement mortar (1:4) (1 cement : 4 Course Sand) and filling joints with white cement of approved quality including cost, conveyance, taxes, cost of all labour, labour cess, etc. as per the direction of Engineer-in-Charge.
(a)Ground Floor
Supplying, fitting and fixing of Stainless steel of 304 grade in hand railing using 50mm dia of 2mm thick circular pipe with Balustrade of size 32mm x 32mm x 2mm @ 0.90 mtr. C/C and stainless square pipe bracing of size 32mm x 32mm x 2mm in 3 rows in stair case as per approved design and specification, buffing, polishing etc with cost, conveyance, taxes of all materials, labour, T&P etc.as per the direction of engineer-in-charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(e)Terrace Floor
Providing & fixing False Ceiling at all height including providing & fixing of framework made of special section, power pressed from M.S. sheets and galvanised with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleat of size 25mm wide x 1.6mm thick with flanges of 27mm and 37mm, at 1200mm c/c, one flange fixed to the ceiling with dash fastener 12.5mm dia x 50mm long with 6mm dia bolts, other flange of cleat fixed to the angle hangers of 25 x10 x0.50mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I chanels 45 x15 x 0.90mm running at the spacing of 1200 mm c/c, to which the ceiling section 0.5mm thick bottom wedge of 80mm with tapered flanges of 26 mm each having lips of 10.5mm, at 450mm c/c, shall be fixed in a direction perpendicular to G.I intermediate channel with connecting clip made out of 2.64mm dia x 230mm long G.I wire at every junction, including fixing perimeter channels 0.50mm thick 27mm high having flanges of 20mm and 30mm long, the perimeter of ceiling fixed to wall/ partitions with the help of Rawl plugs at 450mm centre, with 25mm long dry wall screws @ 230mm interval, including fixing of Calcium Silicate Board to ceiling section and perimeter channels with the help of dry wall screws of size 3.5 x25mm at 230mm c/c, including jointing & finishing to a flush finish of tapered and square edges of the board with recommended jointing compounds, jointing tapes,finishing with jointing compounds in three layers covering up to 150mm on both sides of joints and two coats of primer suitable for boards, all as per manufacture's specification and also including the cost of making opening for light fittings, grills, diffusers, cut outs made with frame of perimeter channels suitably fixed, all complete as per drawings, specificaton and direction of the Engineer in charge but excluding the cost of painting with:
8 mm thick Calcium Silicate Board made with Calcareous & Siliceous materials reinforced with cellulose fiber manufactured through autoclaving process.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Providing and Fixing 15 mm thick densified tegular edged eco friendly light weight calcium silicate false ceiling tiles of approved texture of size 595 x 595 mm in true horizontal level, suspended on inter locking metal grid of hot dipped galvanised steel sections (galvanising @ 120 grams per sqm including both side) consisting of main ‘T’ runner suitably spaced at joints to get required length and of size 24x38 mm made from 0.33 mm thick (minimum) sheet, spaced 1200 mm centre to centre, and cross “T” of size 24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced between main’T’ at 600 mm centre to centre to form a grid of 1200x600 mm and secondary cross ‘T’ of length 600 mm and size 24 x28 mm made of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the 1200x 600 mm panel to from grid of size 600x600 mm, resting on periphery walls /partitions on a Perimeter wall angle pre-coated steel of size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the help of rawl plugs at 450 mm centre to centre with 25 mm long dry wall screws @ 230 mm interval and laying 15 mm thick densified edges calicum silicate ceiling tiles of approved texture in the grid, including, cutting/ making opening“for services like diffusers, grills, light fittings, fixtures, smoke detectors etc., wherever required. Main ‘T’ runners to be suspended from ceiling using G.I. slotted cleats of size 25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main ‘T’, bottom exposed with 24 mm of all Tsections shall be pre-painted with polyster baked paint, for all heights complete , as per specifications, drawings and as directed by Engineer-in-Charge.
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
Providing and laying 25mm thick grading Concrete of proportion (1:2:2) using 6mm size crusher broken black hard granite chips from approved quarry, scraping and cleaning the surface, fininishing smooth to proper slope and gradient including cost of all materials, cost of labour, conveyance, taxes, loading, unloading, curing,T&P, etc. all complete as per the direction of the engineer-in-charge.
Terrace Floor
Expansion Joint : The Expansion Joint Treatment shall be executed in two stages. First stage consist of providing and filling of the expansion joints using two part liquid polysulphide polymer sealant Thioflex 600 having solid content 100%, density 1.60 - 1.65 Kg/ltr, movement capacity: 25% MAF including fixing of backer rod with straight edge finish complete all as specified and as directed. Second stage consist of supplying and installing of Fosroc Expoband one Flexible Polyolefin (FPO) membrane system which is designed to be bonded over expansion and movement joints in structures to prevent the passage of water having Thickness: 1mm, Width: 200mm, Elongation at break : 400% , Tensile Strength : 12.5N/mm2 (DIN EN 12311-2 Method B), Water vapour permeability : 2.7g/Sqm/day (DIN EN 1931-Method B). It is bonded in position using two-part epoxy adhesive, Nitobond PC40 as per manufacturer direction. The item rate shall be including of all kinds of labour, tools & tackle, machineries, lead & lift, mathadi charges, curing, wastages, consumable, cleaning, surface preparation, placing baker rod, covering the expansion joint using 2mm thick Aluminium plate fixed by HYSD bolts etc. complete as per design, drawing & instructions of EIC. Make-Fosroc/Myk/Equivalent
(a)Ground Floor
(b)First Floor
(c)Second Floor
(d)Third Floor
(d)Terrace Floor
Construction of granular sub-base by providing close graded Grading-VI material of table 400-1, spreading in uniform layers with motor grader on prepared surface, mixing by mix in place method with rotavator at OMC and compacting with vibratory roller to achieve the desired density including cost of all materials, cost of labour, conveyance, taxes, loading, unloading, T&P, etc. all complete as per the clause of MoSRT&H specification for road and bridge work.
(a)Ground Floor
Providing, laying, spreading and compacting graded stone aggregate to wet mix macadam specification including premixing the material with water at OMC in mechanical mix plant, carriage of mixed material by tipper to site, laying in uniform layers with paver in subbase/ base course on well prepared surface and compacting with vibratory roller to achieve the desired density as per Clause 406 of MoSRT&H Specifications for Road & Bridge works (4th Revision).
(a)Ground Floor
Providing and laying 80mm thick M-30 grade factory made cement concrete interlocking paver block of approved colour, design and pattern laid over 50mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete including cost, conveyance, taxes of all materials, T&P, labour, etc. as per direction of Engineer-in-Charge.
(a)Ground Floor
Providing and laying of P.C.C. work of M-15(1:2:4) grade with 20mm and down grade black hard granite (crusherbroken) stone chipswashed and screened sharp sand of approved quality from approved quarry including hoisting, lowering, laying the concrete, ramming, watering and curing etc. complete to required thickness including cost of all materials, conveyance, loading, unloading, royalties, cost of labours, T&P, hire & running charges of concrete mixer, etc. all complete as per the direction of the Engineer -in -charge.
(a)Ground Floor
Construction of cement concrete kerb with top and bottom width 115 and 165 mm respectively, 250 mm high in M 20 grade PCC on M-10 grade foundation 150 mm thick, foundation having 50 mm projection beyond kerb stone, kerb stone laid with kerb laying machine, foundation concrete laid manually, all complete as per clause 408
(a)Ground Floor
Painting two coats after filling the surface with Synthetic Enamel Paint in all shades on new plastered concrete surfaces as per section 800 of MoRTH specifications for Road & Bridge works (5th revision) and instruction of Engineer in charge.
(a)Ground Floor
ELECTRICAL WORKS
CIRCUIT CUM WIRING:
Recessed wirring to light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor of ISI marked Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI with 20 mm dia HMS FRLS PVC conduit ISI marked Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal 6A modular type switch ISI marked Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) and ceiling rose ISI marked of modular type G.I box with metallic cover plate (both side) Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) of suitable size, modular box with 1.5 sq. Mm FRLS PVC insulated single core multistandard copper conductor as earth wire including all accessories and connection as per direction of Engineer -in -Charge. . All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free after sales service within warranty period for acceptance of materials. N.B: None of the points/ switchboard shall be given inside the store room. All the lights are to be controlled from switchboards located outside the store room. No provision of ceiling fans are to be given in the store room.Provision of only smoke ventilation fans of suitable CFM are to be given in the store rooms.
Group-A
Group-B
Group-C
Supplying ,fixing of 6A Plug on the same board in existing switch board with complete fitting by 01 no of 6A switch & socket (modular type)( (flame retradant type)) & other required accessories of ISI marked as approved as per direction of Engg. -in -Charge. Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.
Supplying,fixing of 6A Plug on the separate board with complete fitting by 01 no of 6A switch & socket(modular type)( (flame retradant type)) with suitable size modular box & cover( falme retradant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge..Make-Schneider(Zencelo)/legrand( Myrius) /Panasonic (vision) .(Maximum 02 nos point in one circuit).All the switches & sockets should be warrantied for a period of 2 years against manufacturing defects against which ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.
Supplying,fixing of 1x16A Plug on the separate board with complete fitting by 01 no of 16A switch & socket(modular type)((flame retradant type)) with suitable size modular box & cover(flame retradant type) including supplying of all required accessories of ISI marked as approved as per direction of engg-in-charge.. Make-Schneider(Zencelo)/legrand( Myrius)/Panasonic (vision) (For equipement power)All the switches & sockets should be warrantied for a replacement period of 2 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.
Supplying and installation of AC Point having 16-20A DP MCB, C series with enclosure, Schneider/Siemens/Legrand/ABB c of suitable size as required as per direction of Engg.-in-Charge .All the Components should be warrantied for a replacement period of 1 years against defects with ncessary test report & Warrnaty certificate to be submitted to the department for genuinity of product & to avail free aftersales service within warranty period for acceptance of materials.
Supplying and fixing 32 amps, 240 volts, SPN, industrial type socket outlet, with 2 pole+E-DP plug & socket DB with 32A DP MCB,C series,10ka as per IEC-61439-3 ,suitable for flush & surface mounting,supplied with neutral link with provission for mounting modular devices as per direction of Engg.-in-Charge. Make-Legrand/ Siemens/Schneider/ABB
Supplying and fixing 63 amps, 415 volts, TPN, industrial type socket outlet, with 4 pole+E-4P plug & socket DB with 63A 4P MCB,C series,10ka as per IEC-61439-3 ,suitable for flush & surface mounting,supplied with neutral link with provission for mounting modular devices as per direction of Engg.-in-Charge.Make-Legrand/ Siemens/Schneider/ABB
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 1.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor. In 20 mm dia non metallic heavy duty conduit (LDB to LSB/LIGHT CKT)(2X1.5+1X1.5)
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 2.5 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit.(BDB to LSB/LIGHT CKT/5A PLUG/UPS POINT ) (2X2.5+1X1.5)
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 4 sq. mm copper wire for phase and neutral and 01 no of single core 1.5 sq. mm copper wire for earth continuty conductor in 20 mm dia non metallic heavy duty conduit .(PDB to PSB/ POWER POINT/AC POINT) (2X4+1X1.5)
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 2 nos single core 6 sq. mm copper wire for phase and neutral and 01 no of single core 2.5 sq. mm copper wire for earth continuty conductor in 25 mm dia non metallic heavy duty conduit .(LFDB TO LBDB/UBDB) (2X6+1X2.5)
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 4 nos single core 6 sq. mm copper wire for phase and neutral and 02 nos of single core 4 sq. mm copper wire for earth continuty conductor in 32 mm dia non metallic heavy duty conduit.(LFDB TO LBDB/Medical equipement) (4X6+2X4)
Recessed wiring for circuit/submain wiring with the following mentioned size PVC FRLS insulated, copper conductor, single core cable Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI in recessed HMS FRLS PVC conduit of mentioned size Make-AKG/BEC/Precision/Norpak/Anchor/Kinjal as required as per direction of Engg.-in-Charge. 4 nos single core 10 sq. mm copper wire for phase and neutral and 02 nos of single core 6 sq. mm copper wire for earth continuty conductorin 32 mm dia non metallic heavy duty conduit .(LFDB TO FLOOR PANEL TO TPN BDB power) (4X10+2X6)
Fan & indoor Fixtures
SITC of energy efficient LED tube light fittings with decorative alluminium batten and LED tube light having power rating not more than 20 watt and lumen output not less than 2200 lumen complete with electronic driver and all other accessories with diffuser having 2 years warranty i/c connection etc as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj). The luminaire should be Replacement Warranty will be 2 years .
SITC of High-efficiency IP66 flame proof wellglass with pressure die-cast housing and glass lens in front designed to meet the stringent requirements of ensuring safety in hazardous locations classified as Zone 1 and Zone 2 with Gas Groups IIA and IIB.Built with advanced flameproof technology, this luminaire is engineered to operate safely in areas with potential exposure to flammable gases, vapors, or dust having power rating not more than 30 watt and lumen output not less than 3000 lumen complete with electronic driver and all other accessories with diffuser having 2 years warranty i/c connection etc as required as per direction of Engg.-in-Charge. (Make: Orient Electric/Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj). The luminaire should be Replacement Warranty will be 2 years .
Supplying and fixing of Energy efficient surface /recess mounted square /round shape 18 W LED luminaire of dimension of consists of white powder coated , die-cast Alluminium housing with high quality frosted diffuser for glare-free uniform lighting distribution with wattage not more than 18 watt and lumen output of 1800 lumens, , CRI not less than 80,CCT of 6000 degree K,THD less than 10%, with electronic driver, internal surge protection of 3 KV , L70 B50: 50000 hrs and all other accessories suitable for operation on 220 V to 240 V supply as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj).The luminaire should be Replacement Warranty will be 2 years
Supplying an fixing of recess/surface mounted 2'x2' 36 W(595mmx595mmx70mm) square shaped LED with lumen efficacy not less than 130lm/W, CRI not less than 80, CCT of 5700-6500 degree K, THD less than 10%,internal surge protection of 3 KV, complete with Non integrated isolated electronic driver (protects the output /secondary side from any disturbance on the input / primary side ensuring safe operation)and all other accessories suitable for operation on140- 270 V, 50 Hz ,L70 @50,000 burning hrs (5 years warranty) as required as per direction of Engg.-in-Charge (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) . The luminaire must be Replacement Warranty will be 5years.
SITC of Sleek LED 10 watt mirror light fitting with extruded polycarbonate housing,High optically efficient diffuser,above wash basin complete with all accessoriesetc. directly on wall, including connection with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required as per direction of Engg.-in-Charge. (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj)The luminaire should be Replacement Warranty will be 2 years
Supplying, Erection, Fixing, connection & testing of LED BOUNDRY WALL Light of elegant look (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) 60 W LED street light having die cast aluminium housing with toughened glass having lumen efficacy of 110 lm/w or more (As per LM 79 report of third party NABL lab) ,IP 65 protection or more , LED street light model having warrantied for a period of 5 years . The luminaire should be supplied along with bracket maintenance free for inspection as required as per direction of Engg.-in-Charge.
Supplying, Erection, Fixing, connection & testing of 40W LED GATE Light of (Make: Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj) maintenance free having 2 years warranty G.I P ipe with braket including MCB box & including with foundation as per the Drawing for inspection as required & as per direction of Engg.-in-Charge.
Supplying, Erection, Fixing, connection & testing of wall mounted 10W LED Bulkhead wall fitting of Panasonic/LT/Havells /Philips/Wipro /Crompton/Bajaj. The luminaire should be Replacement Warranty will be 2 years
Supplying, installation, testing and commssioning of 1200 mm sweep Copper wound BLDC ceiling fan with aluminium blades having wattage not more than 28W and air delivery ≥215m3/min Make-Crompton Energion Groove /Havells Efficiencia Neo/Usha Technix /Bajaj Turbo Pro 12DC5 ) including wiring the down rod of standard length (upto 30 cm) with 1.5 sq mm PVC insulated, copper conductor, single core cable etc. as required as per direction of Engg.-in-Charge,Replacement Warranty will be 4 years.
Supplying, installation, of heavy duty 400 mm sweep 1400 rpm wall fan(Make- Havells/Crompton/Usha/Orient/Bajaj ) including fixing & conntection .as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years.
Supplying, installation, of exhaust fan of heavy duty 300 mm sweep 1400 rpm with louvers (Make- Havells/Crompton/Usha/Orient/Bajaj ) of exhaust fan in the existing wall, including fixing & conntection as required as per direction of Engg.-in-Charge. Replacement Warranty will be 2 years.
S/F of 5 step type Modular electronic Fan Regulator ISI Marked with all connection complete in all respect as per direction of Engineer in charge (Make: legrand Myrius /Schneider(Zencelo)/Panasonic(Vision))
Supplying and fixing extra conduit down rod of 20 cm length G.I. pipe 15 mm dia, heavy gauge including painting etc. as requiredas required as per direction of Engg.-in-Charge . (Note : More than 5 cm length shall be rounded to the nearest 10 cm and 5 cm or less shall be ignored)of ISI mark as approved.
Panels, MDBs, DBs. MCBs
MAIN CONTROL PANEL AT GF
S/I/T&Commissioning of LT indoor floor mounted cubical type electrical main panel (for both light and power circuit) made out by 2mm CRCA steel sheet duly derusted & painted by siemens gray powder cote paint is designed as G.A drawing as per direction of Engg.-in-Charge.Warrentee period of replacement of panel & accessories must be 1 years & compelete test certificate must be submitted along with panel board including component list. ON/OFF/TRIP indication for all the incoming and outgoing feeders.50X10MM Separate Aluminium Earth bus bar should be installed. Make of MCCB- ABB(Formula)/Siemens(3VA)/SCHNEIDER(CVS)/Legrand(DPX3) Make of MCB- ABB(SB 200)/Siemens(Betaguard)/SCHNEIDER(Acti 9 AN9)/Legrand(DX3)
In commer-1-01 number of 400A 4P Icu=100%Ics,36Ka LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS (FROM TRANSFORMER)
In commer-2-01 number of 400A(250-400) 4P Icu=100%Ics,36kA LSIG MCCB with micro processor based release Electrical locking for normal & DG ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS) From DG
1 no. 400A onload change over. Make-Legrand/ABB/Siemens/Schneider
Busbar- 04 numbers of 500 Amps AL bus bar Electrolytic busbar duly sleeved by color coded PVC sleeve & supported by suitable size DMC insulator.
Out going- 02 numbers of 250A 4P MCCB,25Ka MCCB with TMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB-FORMULA)
Out going- 07 numbers of 100A 4P MCCB,25Ka MCCB with TMR based release with adjustable overload ,Icu=100%Ics( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB-FORMULA)
Out going- 04 numbers of 63A 4P MCB 10kA, C series( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB-FORMULA)
Out going- 09 numbers of 40A 4P MCB 10kA, C series. ( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB-FORMULA)
Instrument- (i) 06 numbers phase indicating lamp with toggle switch & HRC fuse.
(ii) Digital Meter Displays Current, line to neutral & line to line Voltages, frequency & Power Factor. (VA & PF - Phase Wise & Average) (SECURE/ Legrand ) for all the incomers
(ii) 02 set of 4 pole (3P+N) 65 KA SPD type 1+2 with 63 A 4 P Mcb, C series 10kA (Make : Schneider (ACTI 9 ) /legrand (DX 3)/siemens (Betaguard)/ABB SB200
SITC of LT indoor floor mounted cubical type electrical main panel made out by 2mm CRCA steel sheet duly derusted & painted by simens grey powder coated paint is designed as G.A drawing. (FOR LIFT)as per direction of Engg.-in-Charge. Warranty period of replacement of panel & accessories must be 1 year & compelete test certificate must be submitted along with panel board including component list.Type 2 SPD(3P+N) 40ka shall be installed in the incomer. 20X10MM Separate Aluminium Earth bus bar should be installed. 63amp panel board having 63A Amp 16KA 4P MCCB TMR based release with adjustable overload ,Icu=100%Ics as incommer, 100 amp electrolyte cu bus ba-1 Set, 63A Amp 4P RCCB 30mA- 1 No,25A Amp DP RCCB 30mA- 2 No,6-32A DP MCB 10ka, c series -2 No as Outgoing with ampere meter, voltmeter, toggler switch,three nos led indicator,Drum insulator,transparent isolation glass,danger Board and Rubber Mat as per the direction of site engineer in charge (make of mccb :-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB FORMULA) Make of MCB-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB200(Lift Panel)
Supplying and fixing of following mentioned way, three pole/single pole and neutral, sheet steel,double door MCB distribution board, 415 volts/240 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB ITUS as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years
4 Way(8+12) Way TPN MCB DD DB Horizontal Type as per IEC 61439-3 suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door(FOR LIGHT,POWER INDOOR,3-PH,POWER LOAD) Warranty on DB is 3 years.
8 Way(8+24) Way TPN MCB DD DB Horizontal Type suitable for Flush mounting and Surface mounting with 100A Copper Bus Bar for each phase, with neutral Bus bar, Earth Bar & Cable ties for cable management, prefitted masking sheet, IP43-IK09 with metal door(FOR POWER & INDOOR AC DB)Warranty on DB is 3 years.
Supply and fixing of 12 way DD single pole and neutral sheet steel MCB distribution board 250V on surface/recess complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, detachable gland plate, interconnections, phosphatized and powder painted including earthing etc. as required (but with out MCB/ RCCB/ Isolator) (ALL LIGHT WITH CORRIDOOR/COMMON AREA,EM LIGHT,UPS LOAD, EM LOAD LIGHT LOAD,POWER LOAD ) Warranty on DB is 3 years.
Supplying and fixing 6-32 Amps rating, C series,10KA breaking capacity,SP, 230 volts, MCB . Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. .. The MCB should be Replacement Warranty will be 1 year..
Supplying and fixing 40 amps rating, 415 volts, C series,10KA breaking capacity, FOUR poles MCB of Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9 /ABB SB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. .Warranty on MCB is 1 year.
Supplying and fixing 40 Amps rating, RCCB 30mA . Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections, testing and commissioning etc. as required as per direction of Engg.-in-Charge. . The RCCB should be Replacement Warranty will be 1 year.
Supplying and fixing 40 amps rating, 240 volts, C series,10KA breaking capacity, Double poles MCB of Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge. .Warranty on MCB is 1 year.
Supplying and fixing 63Amps 4P 415 volts MCB 415 volts, C series,10KA breaking capacity, Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB SB 200 in the existing MCB DB with connections as per direction of Engg.-in-Charge..Warranty on MCB is 1 years.
Supplying and fixing 63Amps 4P 415 volts RCCB 30 mA Make-LEGRAND-DX3 / Siemens-Betaguard/ Schneider- Acti 9/ABB FB 200 in the existing MCB DB complete with connections as per direction of Engg.-in-Charge..The RCCB should be Replacement Warranty will be 1 year.
Supplying and fixing of following mentioned way, three pole and neutral, sheet steel,double door VTPN distribution board, 415 volts shall be as per IEC 61439-3,integrated door earthing system offering additional safety to the user,High quality polyurethane Gasket,the box and cover shall be fabricated to withstand IK09,the DB should be properly pre-treated with 7 tank process and duly powder coated, phosphatized with powder coated finish, on surface/recess, complete with terminal blocks,with suitable size FR PVC insulated copper conducter up to terminal blocks, tinned copper busbar, neutral busbar, earth bar, din bar. Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9 /ABB -ITUS as per direction of Engg.-in-Charge. The Distribution boards should be Replacement Warranty will be 3 years.
Floor Ventilation DB(8 Way VTPN DB) Make-LEGRAND-Ekinox3 DB/ Siemens-Betaguard/ Schneider- Acti 9/ABB ITUS with 100A 4P adjustable thermal based MCCB with Ics=100%Icu (16KA)( Make-LEGRAND-DPX3 / Siemens-3VA Model/ Schneider- CVS/ABB Formula) as Incomer, Outgoings-6-32A TP MCB 10 KA breaking capacity,C series, (Make-LEGRAND-DX3/ Siemens-Betaguard/ Schneider- Acti 9/ABB SB200) -8Nos.Warranty on DB is 3 years.Warranty on switchgear shall be 1 year.
CABLE TRAY
Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 200mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.
Supplying,fixing of perforated cable trays with horizental & vertical bends,reducers ,tees,crossover,brakets & other accessories ar requited confirming to IS-IEC -61537 ,the cable tray shall be galvanised for corrosion protection confirming to DIN EN 10346/ISO 1461. Size 60mm(H) x 300mm(W) of MAKE- Profab/OBO/Neidax.The Load bearing capacity of the Cable Trays should be minimum of 104.8Kg/meter at the span of 1.5Meter as per UL specifications as required as per direction of Engg.-in-Charge.
Cables, Cable Laying & Termination
Supplying of one number PVC insulated armoured and PVC sheathed XLPE property AL. conductor power cable of 1.1 KV grade Make- Finolex/Polycab/HAVELLS/RR KABLE/KEI/Gloster of following size cables as per direction of Engg.-in-Charge.
3C X 6 sqmm (External wall mounted & gate fixtures)
4C X 16 sqmm (Water Supply & STP)
3.5C X35 sqmm (Lift Panel)
3.5C X185 sqmm (Main LT Panel)
LAYING OF CABLE
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand cushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 25 SQ. MM but not exceeding 120 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand cushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size exceeding 120 SQ. MM but not exceeding 400 SQ. MM direct in ground in the trench in one horizental formation including excavation ,sand cushing protection covering and refilling the trench etc as required as per direction of Engg.-in -charge.
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 25 SQ. MM in surface/tray with shaddle and screw etc as required as per direction of Engg.-in -charge.
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 120 SQ. MM From 25 SQ. MM in surface/tray with shaddle and screw etc as required as per direction of Engg.-in -charge.
Laying of PVC Insulated PVC Seated /XLPE power cable of 1.1 kv grade size not exceeding 400 SQ. MM From 120 SQ. MM in surface with shaddle and screw etc as required as per direction of Engg.-in -charge.
TERMINATION OF CABLES
Supply & Making end Termination with brass compression gland and Cu/aluminium lugs for PVC insulated and PVC sheathed cable of 1.1 kv grade (without cost of Cable)
3C X 6 sqmm(19 mm)
4C X 16 sqmm(28mm)
3.5C X 35 sq. mm (32mm)
3.5C X 185 sq. mm (54mm)
Providing,fixing and laying of fallowing dia HDPE pipe (medium class) in ground complete with fitting incl. trenching(75 mm depth)and refilling as per direction of Engg.-in-Charge.
200 mm dia (OD-200 mm & ID-175 mm nominal) (for Road crossing)
LIGHTNING PROTECTION:
Supply of 8 mm Aluminum Round Conductor.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB
Supply of Roof conductor holder for parapet- Polyamide Conductor holder:With M8 female thread or diameter 7mm, M8 Screw to connect the conductor holder.Weather and temperature resistant from -35 to +90 degree Celsius tested. Conductor holder @ 1 meter distance.Tested as per IEC 62561. as per direction of engineer in charge.Make-OBO/Dehn/ABB
Supply of Polyamide roof cable holder for flat roof: DIN 48829 Form B1. Closed form with bottom. Filling weight 1Kg (frost-resistant concrete). Sleeve from polyethylene, black@ 1 meter distance. Tested as per IEC 62561. Make-OBO/Dehn/ABB
Supply of Connector: For T cross and parallel connectors. Quick installation using hexagonal bolt M10X30 high-grade hot dip galvanised. Tested as per IEC 62561.(2nos/expansion piece ).Make-OBO/Dehn/ABB
Supply of 1 mtr vertical air terminal with mounting accessories on the flat surface to meet the requirements of IS/IEC 62305. Tested for Electrical , mechanical and chemical as per IECb 62561. Tested for 100kA lightning current. Make-OBO/Dehn/ABB
Supply of Vertical air terminal with accessories:Providing of Air terminals as per IS-IEC -62305 part-3 Nominal size Ø10/16 mm aluminium rod: 3 Mtr Airterminal: semi-hard (E-AlMgSiO5 corresponds to DIN 48801) Suitable for high wind load. Tested as per IEC 62561. Make-OBO/Dehn/ABB
Supply for Providing of Stand for Fang Fix system 16 kg with base and clamp ,made up of frost resistant concrete and clamp tested upto 100KA lightning current . Make-OBO/Dehn/ABB
Supply for Providing of Stand for Fang Fix system 16 kg made up of frost resistant concrete. Make-OBO/Dehn/ABB
Supply of Test Joint (Folding Clamp) suitable to connect 8mm round conductor and max by 30x3 mm GI strip as specified in drawing and directed by Engineer. Tested for 100kA lightning current. Make-OBO/Dehn/ABB
Supply of IP 66 Poly Propylene Junction Box. Installation at 1Mtr Height For Test Joint .Internal dimensions: 100x100x48 mm Make-OBO/Dehn/ABB
Supply of Galvanised Steel Flat 30X3 mm thickness from earth electrode directly in ground as required. Flat conductor Hot Dipped Galvanized. Tested as per IEC 62561. Make-OBO/Dehn/ABB
Supply for Providing of Cross connector for Flat: Suitable for 30mm Galvanised steel strip. Installed with 4 nos of hexagonal plate. Tested for 100kA lightning current. Make-OBO/Dehn/ABB
Supply of flat conductor holder- Fit: FL 30, With mounting hole 6.2 x 22 mm, With 2 cylinder bolts M6 x 16 and over-piece from hot-dip galvanised steel, Bottom section from polyamide, black. Tested as per IEC 62561. Make-OBO/Dehn/ABB
Supply for Providing of Plastic Corrosion Protection strip: Approx 1.1 mm thick. Width 50mm. Made of petrolatum- coated chemical fibre fabric. Make-OBO/Dehn/ABB
Supply of UL Listed maintenance free ,Low carbon copper coated earth rod of 3 metre electrode having diameter of 17.2 mm with copper coating thickness of 250micron tested as per IEC 62561-2 Make-OBO/Dehn/ABB
Supply of universal clamp made of SS to connect rod with flat conductor Make-OBO/Dehn/ABB
Supply of Earth conductivity enhancing mineral compound shall be of 25 kg/pit tested as per IEC 62561-7,TCLP tested Make-OBO/Dehn/ABB
Supply of The above arrangements shall be provided with Heavy duty earth champer of 5000kg load bearing capacity to ensure the safety of earthing system Make-OBO/Dehn/ABB
Installation of The above arrangements including all accessories as per Direction of Engg. In charge.
EARTHING SYSTEM:
S/IT/C of materials and installation of GI earth plate 600mmx600mmx6mm thick ISI marked with G. I. nut bolts & washers including cost of burnt wood charcoal, salt, foreign soil, water pouring arrangements, brick masonary enclosure on top with removable RCC cover complete with labour for excavation of pit in all kinds of soil & rock as required and as per direction of Engineer-in-charge.
Providing and fixing 4 mm dia copper wire on surface or in recess for loop earthing as required.as per direction of Engg.-in-Charge.
Providing and fixing 25mm x 5 mm GI strip on surface or in recess for connections etc. as required as per direction of Engg.-in-Charge.
SPLIT AC & OTHER ACCESSORIES:
1.5 TR high wall 5 star inverter type split A.C machine (BTU/Hr-18000)with copper condensor & evaporator having ambient temperature 52 degree celcius with comprehensive 1 year warranty,5 years warranty on PCB, 5 years warranty on compressor (Make:O-General/Diakin/Mitsubishi/Hitachi/Carrier)
REFRIGERANT PIPING
Supply,installation of hard/soft copper refregrant piping of size 5/8 inch and 1/4 inch for suction and liquid line with 3 corex4 sqmm FRLS Copper control cable alongwith 25 mm weather proof closed cell nitrile insulation ,complete with fitting of bends and other nesessary material to complete the job.
1 TR to 3 TR high wall split A.C
FRAME WORK
Supply,installation & fabrication of MS base frame for both indoor and outdoor unit and other nesessary material to complete the job.
1 TR to 3 TR high wall split A.C
DRAIN PIPING
Supply,installation & fabrication of Insulated drain water piping from indoor to nearestdrain point separate to all and other nesessary material to complete the job.
25mm nom. Dia pipe
CONTROL CABLE
Supply and fixing of 4kVA Voltage stabilizer (Make-V-Guard/Microtek
LAN SYSTEM:
SITC of 4 pair Cat6 23 awg U/UTP LSZH Cable in the existing surface/ recessed steel/ PVC conduit as required: The 4 pair Unshielded Twisted Pair cable shall be UL Listed,exceeds the requirements of ANSI/TIA-568-C.2 and ISO/IEC 11801 Class E , 4 twisted pairs separated by internal PE Cross Separator. Full separator. Half shall not be accepted. Rip Cord is must,Insertion Loss of 32.8 db/100m at 250 MHz ,Cable should support operating temperature from -20° to +70°C Cable support Conductor Resistance ≤ 9.38 Ω/100m Max., Cable support Delay Skew: < 45 ns/100m, Operating Voltage: 72V , Impedance: 100 ± 15 Ω @100 MHz. and Propagation Delay @250 MHz : 536 ns/100m, ETL Verified 4 connector channel performance up to 700 MHz , RoHS Compliant. Make: Systimax, Legrand, Panduit
SITC of Cat6 I/O with Single Face plate: The Outlet shall meet or exceed requirement as per ANSI/TIA 568C.2,ISO/IEC 11801, & EN50173. The information outlet NEXT, PSNEXT, FEXT, ELFEXT, PSELFEXT and return loss should be verified for CAT6 @ 250Mhz & CAT6A @ 500Mhz. The information outlet connector shall be of gold/nickel, thickness of gold > 0.8 μm. The connectors shall be compatible as per IEEE 802.3af standard for POE application. The PVC material of Face plate should complie ABS /UL94-V-O certified. Make: Systimax, Legrand, Panduit
SITC of Cat 6, 24-port loaded, 1U Modular Jack Panel Should accommodate Cat6 with Rear Cable Management and Front removable Tooless Information outlet. Should have easy clip management with labels and clear label covers, Made with of Dicast Aluminium Alloy Material and Non Corrosive with Cat6 toolless RJ45 x 24 ports with color code front panel with patch cord locking. Make: Systimax, Legrand, Panduit
SITC of Cat6 UTP 24 AWG Patch Cord Patch cord: 6 UTP Patch Cords are Factory Tested for Better Quality and Suitable for the High Speed Data Transmission. Complies to the Standard ANSI/TIA/EIA-568-C.2 Standard. Supports Data Networks Speeds Up to 10/100-Base-T and 1000-Base-T. Available In LSZH Jacket- Reduced Toxic Gasses Emitted During Combustion , RJ45, 8P8C, 2 FORK 50μ’’ Gold Plated Contacts , 100% Factory Tested , Transparent Boot Cable Assemblies. Make: Systimax, Legrand, Panduit(1 mtr length)
SITC of Cat6 UTP 24 AWG Patch Cord Patch cord: 6 UTP Patch Cords are Factory Tested for Better Quality and Suitable for the High Speed Data Transmission. Complies to the Standard ANSI/TIA/EIA-568-C.2 Standard. Supports Data Networks Speeds Up to 10/100-Base-T and 1000-Base-T. Available In LSZH Jacket- Reduced Toxic Gasses Emitted During Combustion , RJ45, 8P8C, 2 FORK 50μ’’ Gold Plated Contacts , 100% Factory Tested , Transparent Boot Cable Assemblies. Make: Systimax, Legrand, Panduit(2 mtr length)
SITC of 24 Port Layer 2 PoE+ Switch having 24 x 10/100/1000 Mbps Ethernet PoE+ ports with 4 x 1/10Gig SFP+ ports ,1 x RJ45 port console port ,Switching Capacity 128 Gbps , Throughput 96 Mpps ,MAC Address 16k , Switch should support IEEE 802.3af (15.4W) & IEEE 802.3at (30W). Total PoE power: 370W or above , Switch should support DHCP server/relay/client, DHCP snooping/option82 , Switch should support Console, Telnet, SSH v1/2, HTTP, HTTPS, SNMP v1/v2/v3, RMON , TFTP, FTP, SFTP, NTP, ZTP, SPAN, RSPAN,Switch should support support ICMPv6, DHCPv6, ACLv6 ,IPV6 Telnet ,Temperature 0°C -50°C ,Power Supply AC: 100-240V. Make: Digisol, Cisco, HP
SITC of 9U/500D Wall Mount Rack with Accessories: The rack size should be 600W x 500D, Front frame integrated with top, bottom, front and two side panels for better rigidity and strength, Front Glass Door with Lock loaded, Compliance with standards shall be UL 2416., DIN 41494, IEC EN 60529, IEC EN 62262 , IEC EN 60068-2-11 , ISO 9001:2008 including Power Distribution Unit (06/16 Amp Indian-Standard - 06 Socket - Single Pole / Screw Mountable / 16 Amp MCB / Alternating Current - 16 Amp 3 Pin Plug with Power Cable 2.5 sq.mm 3 meter Lengt), 1 cooling Fan(230V AC - 90 CFM, dB 42), 2nos 1U Metal Cable manager with Plastic cable loops and H/W screw. Make:Valrack, Rittal, Legrand
SITC of 24U 600/650D UL Listed Floor mount Rack with Front perforated door with 3 point lock, Rear mesh door with Cam lock and 3inch Castor Wheel included with 2 no 6/16 Amp Indian-Standard - 06 Socket - Single Pole / Screw Mountable / 16 Amp MCB / Alternating Current - 16 Amp 3 Pin Plug with Power Cable 2.5 sq.mm 3 meter Length, 4nos 1U Metal Cable manager with Plastic cable loops, 2nos CFM FAN set, 1no Monitor Tray - Ventilation - 495W - 375D and H/W screw920sets). Make:Valrack, Rittal, Legrand
SITC of 6 core Single mode OS2 Unitube Armoured Optical fiber cable through existing conduit: The Fiber should be OS2 Single Mode Optical Fiber Cable of Size 9/125µm. Outdoor Corrugated Steel tape Central loose tube. ( Standard Approved: ISO 11801 2nd edition/ EN 50173-1:2002 / IEC 60794-1/IEC 60793-2-50 class B1.3 / EN 60793-2-50: class B1.3 / ITU Recommendation G.652.D - the oder ITU designations A, B and C are also fulfilled / OS1/ISO/IEC 24702:2006, cat. OS2; also OS1 requirements are fulfilled/IEEE 802.3 - 2002 incl. 802.3ae ) Jacket. Make: Systimax, Legrand, Panduit
SITC of Rack mount Draw Type Loaded 6 port LIU available in Standard 19” ,Dimensions (mm) : 430 X 220 X 1U , Cold Rolled Steel as Raw Material , Consist of Top Cover and Bottom Panel , Easy to Assemble and Dissemble , Three Types of Input Holes Cable Entry Through Water Proof Cable Clamp , 12 Duplex SC or LC Adapter Interface , Splice 24 Fibers at Most with 1 Tray ,Adaptor, SM, Duplex SC, PC Type ,Pigtail, Support the TIA/EIA Telecommunication Wiring Standards. Compact Design , Telcordia GR-326-Core . Make: Systimax, Legrand, Panduit
SITC of OFC Patch Cord, SM (OS2), Duplex LC-SC, LC-LC PC Type, 3M, LSZH Fiber Optic Single Mode OS2 Patch Cords are offered in LSZH Jackets with Corning Fiber,Insertion Loss : <= 0.2 db, Max 0.3db/MTRJ: Max 0.5db Return Loss : PC>= 45db, UPC>=50db, APC>=60db. Make: Systimax, Legrand, Panduit
SITC of 1G-LX/LH SFP transceiver module,SMF, 1310nm, 9/125 um Single mode Fiber Type up to 20 KM. Make: Cisco, Digisol, Netgear
SITC of Gate way Router with Built-in firewall provides anti-virus, layer 3-7 IDS/IPS, DPI, SSL detection, and more. Built-in VPN router supports 2.5Gbps or 3Gbps to allow easy remote access. 2 x 2.5 Gigabit SFP port and 10 x Gigabit Ethernet ports *3x Fixed WAN. 2.5Gbps Router. 4 x PoE out ports, IEEE802.3af/at, Maximum PoE Wattage: 36W. Make: Grandstream, Ruijie, HP
IP-CCTV SYSTEM:
Supply, Installation, Testing & Commissioning of 5MP IP Network TDN Low-Light IR Fixed Lens Dome/Bullet Camera, 1/2.8" CMOS or better, 5MP (2592 x 1944) @ 25fps or better, triple stream at various resolution & Frame Rates, Min. Illumination required 0.007 lux (color), 0 Lux IR On, 2 IR LEDs, Smart IR with upto 50m IR distance, Auto ICR (Infrared Cut Filter) 120dB True WDR, S/N Ratio 50db, Shutter Speed 1/8 - 1/30,000; Adavance Video Compression technology such as H.265, H.264 & MJPEG , Fixed Lens 2.8mm, Field of View FoV H:90°, V:62°, BLC, HLC, WDR, 3DNR, White Balance - Auto/Manual, Minimum Edge Intelligence Video Analytics : Video Motion Detection, Tampering, Loitering, Intrusion, & People Counting, 4 Privacy Mask, 8 Region Of Intreset, Defog, HTTPS, IP Filter, TLS1.2, AES-128/256, SSH/Telnet closed, Stream Encryption, 2-Way Audio Full Duplex Line IN/Out, 256GB SD card support, Alarm: 1In/1out, PoE (802.3 af) and 12V DC, Max 5W, IP 66/67 & IK10 with Die Cast Aluminium Housing, Having Operating temp range : –40°C to 60° C. Certifications: ONVIF Profile S/G/T compliant,, CE (EN 50130-4), FCC Part 15, EN 55032 & RoHS (EN63000)/NDA/STQC compliant. Make-Honeywell(Series 35), Pelco/ Axis/ BOSCH
Supply , Installation, testing , commissioning of 32 Channel NVR with 4 SATA; 384 Mbps incoming bandwidth, Up to 8 Megapixels Resolution Display and Recording, H.265 video compression technology with real time encoding, Full function CMS (Central monitoring software) supported, Two way audio supported, Dual streaming technology to encode recording stream and network stream separately, Supports remote monitoring on Mobile Client (Android, IOS), TCP / IP, PPPoE, DHCP, DNS, DDNS, UPnP, NTP, SMTP, Time/ Date, Alarm, Motion Detection & Exact Search (accurate to second), Record Snapshot, FTP, Preset Calling, Email notification supported, Manual/ Alarm/ Motion Detection/ Continuous, CE, FCC, RoHS).STQC compliant Make-Honeywell series 35/Pelco/Axis/Bosch
Supply, Installation,Testing & Commisioning of Surveliance 10 TB HDDMake:- WD/Segate/Toshiba
SITC of 55" UHD IPS Commercial Digital Display for Small Size Discussion & Chambers: Brightness (440 nits or higher), Dynamic Contrast Ratio (Dynamic MCI (Hz)):1000000:1), 1000000:1, Static (Panel) Contrast Ratio-1200:1, Response Time (G to G)-8 ms, Refresh Rate.-60 Hz, Life span (hrs)-30,000, Speaker (Sound Output):10W + 10W, Speaker System: 2.0 ch, DVB-T2/C Broadcasting System, Commercial Smart UX, webOS version (webOS 6.0), BIS Certification with 3 years onsite warrenty. Make: LG/Samsung/Sony
Supply,Installation, Testing & Commissioning of of 1.5 Ton Goods lift gearless with Machine room Capacity,Elevator G+3 Floors with ACVVVF drive/Control for constant load ARD >=1MPS,(shaft size not less than 3000mm(Front to back)x2150mm(Left to right) ) SS honeycomb interior ,2hr fire rated door with simplex operation without attendant car position indicators,battery operated alarm bell & emegency light,SS honeycomb finish door finished car interior, recess Granite flooring ,power operated centre opening automatic sliding SS honeycomb finish doors for car entrance & hoist way entrance etc .All the SS material shall be of grade SS -304 and of minimum thickness not less than 1.6mm. Machine beams,buffer support channels,facia plate including sills pit ladder metal screen in Elevator pit etc.as per specifiaction including cost of (i)Overload detection,(ii)Voice announcement,(iii) Intercom,(iv)Braille Buttons, (v) Lift Panel , (vi) Interconnection with all Civil & Electrical works required for installation of Elevator in the existing lift well and machine room,scaffolding ,floor cutting including Fireman's switch complete in all respect.The Elevator should be suitable for physically handicapped person. make:OTIS/Mitsubishi/Johnson/Schindler
FIRE FIGHTING AND FIRE ALARM SYSTEM:
EXTINGUISHER SYSTEM
Providing and fixing carbon-di-oxide type fire extinguishers consisting of welded M.S cylindrical body, squeeze lever dischange valve fitted with pressure indicating gauge internal discharge tube, 30cms long high pressure discharge hose, discharge nozzle, suspension bracket, conforming to IS : 2878 finished externally with red enamel paint and fixed to wall with brackets complete with internal charge.Make- Safex/ Fireshield/Kanex/ Ceasefire .4.5 kg capacity
Supplying, installation, testing and commissioning of ABC type fire extinguishers of 6 kg capacity including cost of all material & labour etc complete. Make-Safex/Fireshield/Ceasefire
Supplying and installing at approved location approved make fire buckets at 24 gauge galvanized stseel sheet, standard 9 liters capacity and of round bottom shape, painted white inside and red outside and black on the bottom, inscribed with letter "FIRE" in black and gold. Cost shall be inclusive of Providing MS stand duly painted over a coat of primer (one stand shall be suitable for hanging 5 buckets.
Providing and Fixing of of 2 kG capacity Eco Friendly, Stored pressure type filled with HFC 134 A ( clean agent fire extinguishant having Zero Ozone depletion potential ) Clean Agent Fire Extinguishers with safety seal, pressure guage, controllable discharge mechanism, helium leak detection tested and conforming to IS 15683 complete with initial charge as required.Make-Safex/Fireshield/Ceasefire
AUTOMATIC FIRE ALARMING SYSTEM
Supply, Installation,Testing & Commisioning of Microprocessor based 2 loop Addresable fire alarm control panel , fully networkable with each loop capable of taking 99 devices, 8 line x 40 character alpha- numeric liquid crystal display .The panel shall be soft addressable type . The panel shall be able to give pin point location of all fire/fault conditions. Further, the panel must be able to automatically switch off respective control switches when ever any alarm is triggered. The panel shall have integral SMF lead acid batteries with sealed cells of 24 V capable of running for a minimum of 8 hours with integral battery charger complete as required and as per specification. The fire alarm panel shall be suitable for software integration with BMS & PA system.Make-Morley IAS/Siemens/Bosch/Schneider/GST/Notifier
Supplying, installing, testing and commissioning of photo electric adressable multi sense smoke detector with inbuilt isolator module/isolator base ,base, junction box and other accessories.Make-Morley IAS/Siemens/Bosch/Schneider/GST/Notifier
Supply, Installation, Testing & commissioning of Addressable Manual Call Point soft addressable type with in built fault isolator as required. Make-Morley IAS/Siemens/Bosch/Schneider/GST/Notifier
Supply, Installation, Testing & commissioning of Addressable Loop Powered Hooter cum Strobe (sound output of minimum 90db) cum strobe (strength of light 10cd) complete with inbuilt isolator as required. Make-Morley IAS/Siemens/Bosch/Schneider/GST/Notifier
Supplying, installing, testing and commissioning of 2C x 1.5 mm², armoured, single stand, outer sheathed, FRLS, PVC insulated copper conductor cable confirming to specified IS standards .Make- Finolex/Anchor/Polycab/HAVELLS/RR KABLE/KEI
SIGNAGES
SIGNAGES:-Providing and installing in position the following type of sign boards made out of 3mm thick flexyle photoluminescent based glow in dark sheeting with luminous properties enclosed in a weather proof Uvstabilized film with UV screen printing by imported links pasted over3 mm thick cast acrylic from front side with 6 mm thick acrylic, -20 to+80 deg C, Suitablefor indoor use, greenish yellow, glow visible upto 4-6 hr in total darkness.Make-Prolite/Bajaj
Illumination Glow light for Exit Indication with Battery Back-up.
VENTILATION SYSTEM
Supply, installation, testing and commissioning of factory fabricated unit floor mounted type fabricated out of extruded aluminum section with 0.6mm pre-plasticized / pre-coated Galvanized steel sheet outside. Motor Kw is indicative only, actual as per requirement to be included during installation.
Cabinet type double skin Exhasut/Fresh Air Unit , with 25 MM thick Puf panel, 0.6 MM Pre coated Outer sheet & 0.6 MM plain inner sheet, complete with Fan section with DIDW centrifugal forward curved fan (with bearings mounted on the scroll and not on the fan casing) Fan motor, Class 'H', IP-55 rated motor , belt driven, drive guard, fan inlet with damper, base frame, spring type /turret mount vibration isolator, powder coated weather-proof canopy,The fan should be low noise level not exceding 55 dB(A) at 3 meter distance. Fan Motor shall be energy efficient squirrel-cage, totally-enclosed, fan cooled, standard frame, constant speed, continuous duty, single winding, suitable for 415±10% volts, 50 cycles, 3 phase AC power supply, provided with class `H’ insulation and 120 minutes fire rating. Motor shall be specially designed for quiet operation.The cost including the Panel for the Fans. Necessary copper earthing should also be included. Cabling and earthing as required from Fan Elec.Panel to Fan motor shall be considered as included in this scope & no separate measurements shall be considered for this lumpsum item.Fans shall be BMS compatible. The rate is inclusive of starter panel. Make-Krugger/Airflow/Nikotra
Air Quantity :4500 CFM( EXHAUST ) Static Pressure : 15 mm wg
Air Quantity :2200 CFM( FA ) Static Pressure : 10 mm wg
Air Quantity :1800 CFM(EXHAUST) Static Pressure : 15 mm wg
Air Quantity :900 CFM( FA ) Static Pressure : 10 mm wg
P.H. WORK
Supplying all materials, labour, T&P and Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes conforming to IS:15778, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer-in-Charge (Supreme/Ashirvad/Oriplast)
In ground floor = 20mm dia C-PVC pipes
25mm dia C-PVC pipes
In 1st. floor = 20mm dia C-PVC pipes
25mm dia C-PVC pipes
In 2nd. floor = 20mm dia C-PVC pipes
25mm dia C-PVC pipes
In 3rd. floor = 20mm dia C-PVC pipes
25mm dia C-PVC pipes
Supplying all materials, labour,T&Pand providing and fixing to wall or ceiling and floor pvc pipes conforming to ASTM-D-1785/04 (Sch-80) and pipe fittings of the following nominal bore with clamps including making good the wall, ceiling and floor all complete as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast) In Ground Floor 25mm UPVC ASTM Pipe
32mm UPVC ASTM Pipe
In 1st Floor- 25mm dia UPVC ASTM Pipe
32mm dia UPVC ASTM Pipe
In 2nd Floor- 25mm dia UPVC ASTM Pipe
32mm dia UPVC ASTM Pipe
In 3rd Floor- 25mm dia UPVC ASTM Pipe
32mm dia UPVC ASTM Pipe
In 4th Floor- 40mm dia UPVC ASTM Pipe
50mm dia UPVC ASTM Pipe
Supplying all materials, labour, T&P and cutting holes through existing brick work including making good the damages in cement mortar (1:4) for taking GI pipes and fittings/ PVC pipes and fittings etc all complete as per PH specification and direction of the Engineer in charge.
In ground floor - 250mm thick wall
In 1st. floor - 250mm thick wall
In 2nd. floor - 250mm thick wall
In 3rd. floor - 250mm thick wall
Supplying all materials, labour, T&P and cutting hole in R.C.C floors, roofs, etc upto 19 cm thick for passing G.I. Pipes / P.V.C pipes and fittings etc and repairing the holes after insertion of pipes etc with cement concrete (1:2:4 ) including finishing complete so as to make it leak proof as per direction of the Engineer in charge.
In ground floor
In 1st. floor
In 2nd. floor
In 3rd. floor
In 4th. floor
Supplying all materials, labour, T&P and cutting holes through existing brick or laterite masonry wall for taking HCI pipes and fittings including making good the damages etc all complete as per PH specification and direction of the Engineer in charge.
250mm to 375mm thick wall.
Supplying all materials, labour, T&P and cutting grooves in pucca floors and walls for taking GI/ PVC pipes and making good the damages as per the direction of the Engineer in charge.
In ground floor
In 1st. floor
In 2nd. floor
In 3rd. floor
Supplying all materials, labour, T&P and fitting and fixing Brass/CP/CPVC/PVC fittings of the following nominal bore with supply of all jointing materials complete as per specification and direction of the Engineer in charge
15mm dia CP Bib cock (Jaquar) FLR-CHR-5047N
15mm dia CP Long body Bib cock (Jaquar) FLR-CHR-5047NG
15mm dia CP Pillar cock (Jaquar) FLR-CHR-5015
15mm dia CP Angle stop cock (Jaquar) FLR-CHR-5053N
15mm dia CP Two way Bib cock (Jaquar) FLR-CHR-5041N
25mm CPVC Ball Valve
32mm CPVC Ball Valve
40mm CPVC Ball Valve
50mm CPVC Ball Valve
150mm dia CP Revolving Shower (Jaquar) OHS-CHR-1803
160mm Long CP Shower Arm (Jaquar) SHA-CHR-477
15mm dia CP Health Faucet (Jaquar) ALD-CHR-573
15mm dia CP Flange
15mm dia CP Extension Piece
125mm dia CP Gratting
32mm Full Thread Waste Coupl. (Jaquar) ALD-CHR-705
32mm dia CP Urinal Flush valve (Jaquar) PRS-CHR-073
Supplying all materials, labour, T&P and fixing Wash Down Water Closet (European type W.C pan) with integral ‘S’ or ‘P’ trap to the floor with wooden plug and chromium plated screws including jointing the trap with soil pipe in cement mortar (1:1) etc all complete as per specification and direction of the Engineer in charge
One Piece Closet "Elba" Star Rated (Hindware) Cat No-92048
Supplying all materials, labour, T&P and fixing bowl pattern urinal including connecting the urinal with waste pipe by means of white lead mixed with chopped hemp etc all complete as per specification and direction of the Engineer in charge.
Half stall urinal DYNA with BI (Hindware) Cat No-60010
Supplying all materials, labour, T&P and fixing wash basins with hole for pillar taps conforming to IS:2556-part-4-2004 with cast iron or M S brackets painted white including cutting holes in walls and making good the damages with supply of wooden plugs, screws and cement etc, fixing pedestal for wash basin recessed at the back for the reception of pipes and fittings, fixing PVC waste pipe of 32mm nominal diameter for wash basin including brass check nut complete, fixing pillar taps capstan head screw down high pressure lettered ‘Hot’ and ‘Cold’ with long screws, shanks and back nuts of 15mm dia nominal bore(Jaquar Florentine Elbow Action make), fixing 15mm dia PVC inlet connection pipe and making connection with pillar cocks and supply mains for wash basin, fixing 32mm dia CP brass waste (Jaquar make-Allied), etc all complete as per specification and direction of the Engineer in charge
Integrated Pedestal Basin KYLIS (Hindware) Cat No-91053
Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No. 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer’s specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the Engineer in charge(Supreme/Ashirvad/Oriplast)
110mm dia U-PVC SWR pipe
110mm U-PVC Door Tee
110mm U-PVC Plain Tee
110mm U-PVC Y Bend
110mm U-PVC Plain Bend
110mm U-PVC Door Bend
110mm dia U-PVC 'P' trap
110mm U-PVC Cowl.
75mm dia U-PVC SWR pipe
75mm U-PVC Plain Bend
75mm U-PVC Door Bend
Supplying all materials, labour, T&P and fixing mirror of superior glass mounted on 6mm thick A.C sheet or plywood sheet and fixed to wooden plugs with CP screws and washers complete as per specification an direction of the Engineer in charge
Design Mirror (jaquar /cera)
Supplying all materials, labour, T&P and fixing standard sized glass-shelf with CP brass brackets and guard rails complete fixed to woden plugs with CP screws as per specification and direction of the Engineer in charge
600mm Glass Shelf (Jaquar) ACN-CHR-1171N
Supplying all materials, labour, T&P and fixing standard sized CP towel rail complete with CP brass brackets fixed to wooden plugs with CP screws as per specification and direction of the Engineer in charge
600mm long CP Towel Rail (Jaquar) ACN-CHR-1111NM
CP Towel Ring (Jaquar) ACN-CHR-1121N
Supplying all materials, labour, T&P and fixing CP soap holder complete with CP brass brackets fixed to wooden plugs with CP screws as per specification and direction of the Engineer in charge
CP Soap Holder (Jaquar) ACN-CHR-1131N
CP double coat hook (Jaquar) ACN-CHR-1161N
Supplying all materials, labour, T&P and fitting & fixing stainless steel AISI 304 (18/8) Library/Kitchen sink with drain board as per IS 13983 with cast iron or M S brackets painted white including cutting holes in walls and making good the damages etc all complete as per specification and direction of the Engineer in charge.
600x450x250 mm stainless steel kitchen sink(Nirali/ Prayag)
Factory made single leaf Solid WPC (Wood polymer) composite door shutter of 25mm thickcompacted with wood grain finish structural foam panel of 29mm thickness and a density of 20kg/cu.mtr shall be used as core material for fitting the metal fittings such as tower bolts, aldrops, handles etc shall be provided. A structural adhesive compatible with (EPS) foam shall be used for bending the core material, The material and process for manufacturing the door shutters shall conform to RV-TIFAC composites Design Centre's standards and specifications and the door shutters Conforming to relevant I.S.specification. The finish of door shutter will be plain colour white/ Ivory/ Beige/ Light grey/ Mahogany/ Teak wood or any other colour using high quality pigments. Three heavy whight mild steel butt hinges type-I(ISI marked) size 100mm are to be fitted on one side of shutter.
Ground Floor 2x0.70x2.00
First Floor 4x0.70x2.00
Second Floor 4x0.70x2.00
Third Floor 4x0.70x2.00
Factory made Solid WPC door frame of size 95mmx55mm fabricated. The door frame consist of four segments which are provided with plug-in-socket arrangement in-situ in the mould. The segments are plugged in and are joined together by means of screw. The WPC frame shall be provided with The material and process for manufacturing the door frames shall conform to Relavent I.S.specification. The finish of door frame will be plain colour white/ Ivory/ Beige/ Light grey/ Golden brown/Mahogany/ Teak wood/sand stone/Champagne/Pastel blue or any other colour using high quality pigments complete in all respect as per specification and direction of the Engineer in charge
Ground Floor 1x4.95
First Floor 4x4.95
Second Floor 4x4.95
Third Floor 4x4.95
Supplying all materials, labour, T&P and providing Vetrified mat finish tiles in floor, treads and landing on 25mm thick bed of cement mortar 1:1 (1 cement:1 sand) joined with neat cement slurry mixed with pigment to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. (Ceramic tile size 600mmx600mm, Kajaria-Fog parla/Somany/Johnson) plain/printed to be pre-approved by the Engineer in charge)
Ground Floor Toilet = 1x2.40x1.80
First Floor Attach Toilet = 2x1.60x2.40
Second Floor Attach Toilet = 2x1.60x2.40
Third Floor Attach Toilet = 2x1.60x2.40
Supplying all materials, labour, T&P and fixing porcelain glazed tiles in dados skirting on 12mm thick cement plaster (1:3) jointed with neat cement slurry mixed with pigments to match the shades of the tiles including rubbing and polishing complete as per direction of the Engineer in charge. (Glazed tile size 600mmx300mm, Kajaria-Duren Morfil/Somany/Johnson) plain/printed to be pre-approved by the Engineer in charge)
In ground floor
In 1st. floor
In 2nd. floor
In 3rd. floor
Supplying all materials, labour, T&P and providing cement concrete (1:2:4) with 12mm size hard broken granite chipsincluding watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In Ground floor = 4.47x0.08 =
In 1st. floor = 13.53x0.08 =
In 2nd. Floor = 13.53x0.08 =
In 3rd. Floor = 13.53x0.08 =
Supplying all materials, labour, T&P and providing brick work with Fly ash bricks having crushing strength not less than 75kg/cm² with dimensional tolerance ± 8 percent in cement mortar (1:4) including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
Fourth Floor(15x0.25x0.25x0.30 =
Supplying and fitting-fixing of UPVC Louvers fixed window/ventilator made of (small series) frame 47x50mm & mullion 47x68 mm both having wall thickness of 1.9± 0.2mm and single glazing bead of appropriate dimension (Area upto 0.75sqm) etc.all complete as per direction of the Engineer-in-charge.
In Ground floor = 1x0.6x0.6
In 1st. floor = 4x0.6x0.6
In 2nd. Floor = 4x0.6x0.6
In 3rd. Floor = 4x0.6x0.6
Providing and laying Sika top seal 109 hi over roof top slab and parapet, toilet inside after cleaning of surface and applied with a coat of Sika 109 hi primer as per approved specification. The Sika shall be laid between two coats of water proofing membrance and the entire application cover with Sika top seak hi curing,compound of all materials and cost of labour T&P etc.complete as per the direction of the Engineer-in-charge.
First Floor: Floor: Attach Toilet = 2x1.60x2.40
Second Floor: Measurement same as First Floor
Third Floor: Measurement same as First Floor
Supplying all materials, labour, T&P and providing fitting and fixing Dr.Aqua guard Magna UV+HD of size 316x251x462mm with wall hanging facility having storage of 7 ltrs. etc.with internal water supply connection complete as per direction of the Engineer-in-charge.
Supplying all materials,labour,T&P and providing Cubicle partition for urinal etc. all complete as per direction of the Engineer-in-charge.(Marino urinal partition)
Supplying all materials, labour, T&P and constructing gully trap chamber of the following inside size with 8cm thick R.C.C precast cover slab in cement concrete (1:2:4) mix using 12mm size h.g chips, foundation concrete (1:4:8) using 40mm size hard granite metal on bed and around trap, K.B brickwork in c.m (1:6) in F&P and inside 12mm thick cement plastering (1:3) finished with a floating coat of neat cement including fixing 100mmx100mm size HCI gully trap,150mmx150mm size C.I grating etc all complete as per approved drawing, specification and direction of the Engineer in charge
Gully trap chamber of size 250mmx250mm with R.C.C cover slab
Supplying all materials, labour, T&P and constructing inspection chamber of the following size with cement concrete(1:3:6) using 40mm size hard granite metal on bed, 1st class K.B brickwork in cement mortar(1:6),moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size h.g chips,12mmthick cement plaster (1:3) with punning to inside, cement flush pointing (1:3) to outside, R.C.C cover slab in (1:2:4) using 12mm size h.g chips with RCC man hole cover, earthwork in excavation in all kinds of soil and refilling the cavity around the chamber including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge
Inspection chamber Inside size 760mmx760mmx460mm
RCPC Cover (18" round)
Supplying all materials, labour, T&P and constructing man hole chamber of the following size with cement concrete(1:3:6) using 40mm size hard granite metal on bed, 1st class K.B brickwork in cement mortar(1:6), moulding and shaping the channel inside and benching with cement concrete (1:2:4) using 12mm size h.g chips,12mmthick cement plaster (1:3) with punning to inside, cement flush pointing (1:3) to outside, R.C.C cover slab in (1:2:4) using 12mm size h.g chips with RCC man hole cover, earthwork in excavation in all kinds of soil and refilling the cavity around the chamber including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge
Man hole chamber Inside size 910mmx910mmx910mm
RCPC Cover (24" round)
Supplying all materials, labour, T&P and constructing soakway pit of the following size with precast RCC rings joined loose, gravel backing in the rear of well steining, precast RCC cover slab in cement concrete (1:2:4) using 12mm size hg chips fitted with iron lifting handles including cutting hole in the rings for inlet pipe,earthwork in open well excavation in all kinds of soil and refilling of cavity around the pit & painting the iron works, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge
RCC rings soakway pit 1.22m dia x 2.10m deep
Supplying all materials, labour, T&P and laying in trenches (to level or slope) unplasticized PVC pipes conforming to IS: 4985/2000 of the following outside dia for class–3(0.60mpa) including jointing with supply of approved solvent cement by non-heat application method/as per manufacturer’s specification, providing and laying in trench cement concrete (1:4:8) with 40mm size hard granite metal in the Type C-1 standard bedding surrounding or encasing including concrete for bedding and curing etc all complete as per PH specification and direction of the Engineer in charge.
110mm dia u-pvc pipe alround concrete
160mm dia U-PVC Alround Concrete
Construction of 50 users RCC septic tank- 1 No
Earth work in excavation of foundation in all kinds of soil within 50m initial lead and 1.5m initial lift including rough dressing & breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.30m in depth and as per direction of the Engineer-in-Charge.
Extra lifts of 1.50 mtr or part thereof over the initial lift of 1.5 mtr in all kinds of embankments and road works and ordinary earthwork in general. 1x6.10x2.70x0.30
Excavation of foundation in laterite rock or any hard rock (other than granite or disintegrated rock) removed by chiselling including dressing and levelling the bed not exceeding 1.50 mtr. in depth and depositing the soil within initial lead of 50 mtr. and as per specification approved by the Department.
Supplying all materials, labour, T&P and filling in foundation and plinth with sand well watered and rammed including conveyance of all materials to worksite, payment of royalty, taxes etc.all complete as per direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing cement concrete (1:3:6) with 4cm size hard granite metal including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In ground floor
Supplying all materials, labour, T&P and providing 6mm thick cement plaster (1:4) on RCC work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In ground floor (inside/outside)
Supplying all materials, labour, T&P and providing cement punning including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In ground floor (inside/outside)
Supplying all materials, labour, T&P and providing rigid and smooth centering and shuttering for R.C.C works including false work and dismantling them after casting including conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
R.C.C floor and roof slabs up to 4.30m height
R.C.C beams,columns,girder and bressmer etc.
Supplying all materials, labour, T&P and providing M.S reinforcement for R.C.C work including cutting, bending, binding, and tying the grills and placing in position including cost of binding wire 18 to 20 gauge, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In Ground Floor per 0.80 qtl/cum
Supplying all materials, labour, T&P and providing cement concrete (1:1.5:3) with 12mm size hard broken granite chips for R.C.C works including hoisting, laying, watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
Supplying all materials, labour, T&P and providing cement concrete (1:2:4) with 12mm size hard broken granite chips including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In ground floor
Supplying all materials, labour, T&P and providing 12mm thick cement plaster (1:4) on brickwork including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
In ground floor
Supplying all materials, labour, T&P and providing brick work with Fly ash bricks having crushing strength not less than 75kg/cm² with dimensional tolerance ± 8 percent in cement mortar (1:4) including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
Supplying all materials, labour, T&P and making MS step iron in 20mm diameter MS steel bars and fixing into walls of man hole/septic tank duly embedded in cement concrete (1:3:6) complete as per specification and direction of the Engineer in charge.
Filling in foundation and plinth with excavated materials, moorum including watering and ramming as directed by the Engineer in charge
Supplying all materials, labour,T&P and providing 25mm thick grading concrete (1:2:2) on roof slab with 6mm size hard granite chips on new work including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
Supplying all materials, labour, T&P and providing shoring and shuttering foundation trenches, pits etc with close wooden planks or sheets shuttering etc all complete as per direction of the Engineer in charge.
Dewatering with 5 H.P diesel engine pump during excavation
Supplying all materials, labour, T&P and fitting and fixing S.W.Tee of size 150mx150mx150m as per P.H.D. specification and direction of the E.I.C.
Supplying all materials, labour, T&P and constructing vent base as per P.H.D specification etc all complete.
Supplying all materials, labour, T&P and fitting and fixing U-PVC SWR soil waste ventilating pipes and fittings of the following outside diameter conforming to ISI No 13592/1992 to walls with nails, bobbins and wooden plugs or laying in trenches including jointing with supply of approved rubber lubricant by non-heat application method/as per manufacturer's specification, testing, earthwork in excavation in all kinds of soil and refilling of trenches as per specification and direction of the engineer in charge. (Supreme/Ashirvad/Oriplast)
110mm diameter U-PVC SWR pipes(Supreme/Ashirvad)
110mm U-PVC cowl
Construction of 20000 litres under Ground water storage sump :
Earth work in All kinds of soil and gravels mixed with stone and boulder not exceeding 0.014 Cum in volume within 50m initiallead and 1.5 m initial lift including rough dressing and breaking clods to maximum 5cm to 7cm and laying in layers not exceeding 0.30m in depth and as per specification approved by the Department.
-do- with Ist additional depth of 1.50 m over the initial lead and lift
Supplying all materials, labour, T&P and filling in foundation and plinth with sand well watered and rammed including conveyance of all materials to worksite, payment of royalty, taxes etc.all complete as per direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing cement concrete (1:3:6) with 4cm size hard granite metal including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per specification and direction of the Engineer in charge
Supplying all materials, labour,T&P and providing cement concrete (1:1.5:3) for RCC work using 12mm HG chips including hoisting,laying,curring and conveyance of all materials to site etc complete.
Supplying all materials, labour, T&P and providing M.S.Reinforcement for RCC work including cutting, banding, binding, straightening and trying the grills and placing in position including cost of binding wire 18 to 20 gage.
Supplying all materials, labour, T&P and providing rigid and smooth centering and shuttering for RCC work including false work and dismantling then after casting including cost of materials complete in ground floor.
RCC floor roof, chajja etc
Supplying all materials, labour,T&P and providing 6mm thick cement plasster (1:4) over CC work including watering curring and conveyance of all materials to site.
Supplying all materials, labour, T&P and making MS step iron in 20mm diameter MS steel bars and fixing into walls of man hole/septic tank duly embedded in cement concrete (1:3:6) complete as per specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and fitting and fixing RCPC Cover all complete as per specification and direction of the Engineer in charge.
Supplying all materials, labour, T&P and providing, fitting and fixing submersible pump with squirrel cage induction type submersible type submersible electric motor to run on 3 phase/1 phase line voltage ranging from 320 volt to 450 volt conforming to IS: 8034/89 with following specifications with suitable control panel, jointing with GI/PVC/HDPE pipes, electrification, testing, commissioning, trial running, conveyance of all materials to worksite, payment of taxes etc all complete as per specification and direction of the Engineer in charge
2 HP three phase 3 stage head range 30 to 54 metres, discharge 155 to 110 L.P.M with outlet dia of 32mm Submersible Pump & Motor(Horizontal).
2.50sqmm flat cable
DOL Control pannel
Labour charges for lowering of submesible pumpset with pipes and cables etc. with testing and commissioning at site.
For installation
200mmx150mm dia Tube Well through DTH Rig.-1no.
Labour for drilling a perfectly vertical bore hole of specified dia for a specified depth below ground level through consolidated and unconsolidated rock with down the hole hammer drilling rig or combination rig as required to suit the site condition as per the direction of the Engineer in charge including use of own rig with its accessories, tools and plant and consumables etc for lowering of 200mm/150mm dia G.I/P.V.C/M.S casing pipes for housing fitted with socket and with or without well screen as per the necessity for soft, medium, hard and boulder formation(G.I/P.V.C/M.S casing pipes if required to prevent collapse of overburden is to be provided by the contractor including lowering and withdrawing after completion of the tube well), 200mm dia to 400mm dia in overburden portion including packing of gravel supplied by the contractor for 400mm dia bore only.
Drilling of 200mm dia bore 0mtr to 45mtr
Drilling of 150mm dia bore 41mtr to 120mtr
Lowering the following size of G.I/P.V.C/M.S housing pipes with or without slotted pipes as per the necessity from ground level up to 45.00m depth and fitted and fixed up in perfectly vertical position including cutting and threading of pipes and slotted pipes and supplying and fixing all jointing materials, tools and plant etc all complete and keeping the top of casing pipe threaded including plugging tube wells to prevent entry of foreign materials.
Lowering of 200mm dia GI/P.V.C/MS casing pipes 0 mtr to 30 mtrs
Lowering of 200mm dia GI/P.V.C/MS casing pipes 31 mtr to 45 mtrs
Cost of 200mm dia P.V.C schedule-80 pipe
Cleaning and developing the tube well with supply of compressor worked till clear and adequate discharge is obtained from the tube well including supply and use of all necessary equipment and labour as per direction of the Engineer in charge.
By DTH/Rotary Rig
Supplying all materials and labour,tools and plant and providing sanitary sealing by cement concrete grouting of annular space around GI/PVC/MS housing pipe upto 5 mtrs below ground level(as per drawing)to plug the bore hole excluding cost of cement all complete as per direction of the Engineer in charge. Minimum one metre of casing pipe to be inserted in the bore into the rock the bottom to ensure sanitary sealing(excluding cost of cement which willbe supplied by the Department)
Sanitary sealing upto 5mtrs below ground level.
CC(1:2:4)with 12mm chips for grouting upto 5 mtr.Depth in sanitary sealing.
Supply all materials, labour, T&P and providing,fitting and fixing submersible pump with squirrel cage induction type submersible type submersible electric motor to run on 3 phase/1phase line voltage ranging from 320 volt to 450 volt conforming to IS:8034/89 with following specifications with suitable control pannel, jointing with GI/PVC/HDPE pipes electrification, testing, commissioning, trial running, conveyance of all materials to worksite, payment of taxes etc all complete as per specification and direction of the Engineer in charge.
1 HP three phase 3 stage head range 30 to 54 metres, discharge 155 to 110 L.P.M with outlet dia of 32mm Submersible Pump & Motor.
DOL control panel
2.50sqmm cable
32mm dia steel short piece
Steel rope with cover
Well cap suitable for 8" bore well
50mm size CI bracket
20mm dia rigid UPVC pipes
32mm dia HDPE Pipe
Labour charges for lowering of submesible pumpset with pipes and cables etc. with testing and commissioning at site.
Supplying all materials, labour, T&P and constructing Bore well protection chamber of the inside size 650x650x1000hight with cement concrete (1:3:6) using 40mm size hard granite metal on foundation, 1st class Fly ash brickwork in cement mortar (1:3), with base cement concrete (1:2:4) using 12mm size h.g chips,12mmthick cement plaster (1:4) inside and outside, R.C.C cover slab in (1:1.5:3) using 12mm size h.g chips, earthwork in excavation in all kinds of soil and refilling the cavity around the chamber including watering, curing, conveyance of all materials to worksite, payment of royalty, taxes etc all complete as per approved specification and direction of the Engineer in charge.
Bore well protection chamber.
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.35 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 1.20 MB
BOQ_574364.xls
BOQ • 1.06 MB
DTCN1.pdf
Tender Documents • 4.02 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .