Augmentation of Power Supply by Provision of compact sub station capacity 2x500 KVA at UTS substation under jurisdiction of Dy.CEE/Colony.
06-2026-COLONY~NER
06-2026-COLONY
Open
Works - General
9 Months
Gorakhpur, Uttar Pradesh
₹0
₹1.9 L
2 Jul 2026
10 Jun 2026
18 Jun 2026
Supply, installation, testing and commissioning of 1 x 500 KVA 11/0.415 KV, 500 KVA dry type Transformer (OFTC) Compact Substation outdoor duty, plinth mounted type complete with HT Section Comprising of 1 No. 11KV 3- way RMU (3 Nos. VCB). LT section Incomer - ACB 800A FP Electrical Draw out type 50KA- 1 No, Incomer Change over switch 800 Amp, Bus Coupler- ACB 800A 01 FP Electrical Draw out ACB 50KA - 1No, Outgoing - MCCB 400A-3 Nos., MCCB 250A FP Manual Fixed Type- 5 Nos, CSS enclosure should be duly type tested for internal Arc Test by CPRI (21 KA for 1Sec.) and as per CEE/NER Spec No. CEE/CSS/17/June -2017 with latest Amendment. (with civil work as making foundation, proper fencing etc. complete in all respect) shall be inspected at OEM's premises by the RITES. Cost for the inspection shall be borne by the contractor. Both CSS and D.G. set should be mechanically & electrically interlocked and coupler so that load of one CSS can be shifted to other CSS in case of failure of one CSS and in case of failure of both CSS the load can be shifted to D.G. set. Interlocking should be capable to isolate anyone of VCB in case of third VCB is made ON by mistake. Above/
Laying of one number LT/HT cable open/air with clamping arrangement as per site requirement complete in all respect concerning to IS: 1255:1983, including end terminations with Aluminium crimping socket/lugs testing and commissioning as required. (L.T./H.T. cable will be supplied by the Railway) Above/
Laying of one number additional LT/HT cable open/air with clamping arrangement as per site requirement complete in all respect concerning to IS: 1255:1983, including end terminations with Aluminium crimping socket/lugs testing and commissioning as required. (L.T./H.T. cable will be supplied by the Railway) Above/
Excavation of cable trench in all types of soil upto depth of one meter and width of 400 mm and refilling the trench complete in all respect. Above/
Laying of LT cable through Double walled corrugated (DWC) pipe/high density Polthelene pipe complete in all respect at a depth of not less than 1 mtr. the ground level as required complete in all respect concerning to IS: 1255:1983. Above/
Supply of Double walled corrugated (DWC) pipe (Elex/Telerex/Optirex or similar) for under ground power/communication/signal/OFC/protection with IS: 14930 part-II mark on duly printed at every one meter interval it along with the socket/coupler and T joint with "IP 67" protection for coupling wherever required. The DWC pipe shall be rodent proof and fire resistant and size of outer Dia 120 mm. Above/
Supply of Double walled corrugated (DWC) pipe (Elex/Telerex/Optirex or similar) for under ground power/communication/signal/OFC/protection with IS: 14930 part-II mark on duly printed at every one meter interval it along with the socket/coupler and T joint with "IP 67" protection for coupling wherever required. The DWC pipe shall be rodent proof and fire resistant and size of outer Dia 160 mm. Above/
Supply of 1.5" high density Polthelene pipe with leak free, corrosion resistant, ductile etc and at a depth of not less than 1 mtr. the ground level as required complete in all respect as per concerning to IS: 1255:1983. Above/
Supply and making outdoor end termination with heat shrinkable jointing kit conforming to IS:13573/1992 (latest version) complete with all accessories including aluminium lugs suitable for 3 core 120 sq. mm HT XLPE aluminium conductor cable of 11 KV (Earthed) grade complete in all respect as required. Above/
Supply & laying of ISI marked Galvanised Steel Tube (Plain ended)., CLASS: Medium, NOMINAL BORE SIZE 80 mm conforming to IS: 1239 PT-I, 2004 or latest as per site requirement. Above/
Supply,fixing & grouting of Cable route marker on stone as per attached Drg. No.DY.CEE/W/LJN/2011/01 complete in all respect. Above/
Supply and making Maintenance free earthing arrangement, Length of Electrode 3000 mm O shell dia 50 mm, O shell thickness 3.25 mm, Inner shell dia = 25 mm, Inner shell thickness 3.25 mm,Terminal size 30 x 10/12 x 12. Earthing will be as per CEE Specification No.CEE/ Maintenance free earthing/July 2009 including Amendement No.1 or Latest complete in all respect as per site requirement. (All material will be supplied by the Contractor).
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
HTML
nit.pdf
NIT
SPECIALTERMSANDCONDITIONS.pdf
ATTACHMENT
ExplantorynoteUTSCSS.pdf
ATTACHMENT
PCEESpecificationfor11KVCSS_1.pdf
ATTACHMENT
GCCApril2022.pdf
ATTACHMENT
RouteMarker.pdf
ATTACHMENT
ACS1toACS11.pdf
ATTACHMENT
Annexuressheet.pdf
ATTACHMENT
CEESpecforMaintenanceFreeEarthing.pdf
ATTACHMENT
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .