Special Repair Works of replacement of Existing Transformer at JNV-1 in the District of Malkangiri and JNV Jajpur, Odisha.
NBCC/SBG/ODISHA/NIT/26-27/28
NBCC/SBG/ODISHA/NIT/26-27/28
Open Tender-Domestic
Electrical Work
Malkangiri, Odisha
₹2,950
₹24,923
12 Aug 2026
22 Jul 2026
12 Aug 2026
12 Aug 2026
ABSTRACT OF COST
Sl.No. Description Unit
Special Repair Works of Existing
Transformer at JNV Jajpur, Odisha
Special Repair Works of Existing
2 Transformer at JNV-1 in the District of ₹ ₹10,80,378.48
Digitally signed by JAYA
Special Repair Works of Existing Transformer at JNV Jajpur, Odisha
Bill of Quantities
Sl No. Description Unit Quantity Rate (Rs.) Amount (Rs.)
Supplying, installation, testing and commissioning of following capacity (continuous loading) BEE 4 Star rated
(Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433 KV step down, 3 Phase, 50 Hz,
Dyn 11 vector group, ONAN (Oil Natural Air Natural) copper wound transformer (Electrolytic grade 99.9% pure
copper, Core made of first grade Cold Rolled Grain Oriented (CRGO) Core grade MOH or better, suitable for out
door/indoor applications with Offload Tap Changer/ On Load Tap Changer (OLTC) ( below 500 KVA offload and
above 500 KVA On Load Tap Changer) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for
automatic sensing of incoming voltage, automatic 134DELHI SCHEDULE OF RATES (E&M)-2025operation of OLTC
and facility for remote and manual operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having
cable end boxes on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking
arrangement on LV side including supplying and laying of copper conductor multicore control cable from
transformer to HT breaker/panel for safety tripping, complete with all accessories and safety provisions as per
relevant IS Code including first filling of filtered dehydrated oil, i/c supplying and grouting of suitable M.S. Channel
with all accessories and transformer shall be confirming to IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD
specifications complete in all respects etc as required at site. The maximum flux density in any part of the core and
yoke at rated voltage and frequency shall be such that the flux density with + 12.5 percent combined voltage and
frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible temperature-rise
shall not exceed 35 0C for oil and 40 dg. C up to 200 KVA and 40 0C for oil and 45 0C for above 200 KVA for
winding. Inside of tank shall be painted with varnish or liquid resistant paint. For external surfaces one coat of
thermo setting powder paint or one coat of epoxy primer followed by two coats of polyurethane base paint shall be
used. IS: 1180 (Part 3) shall be referred to for paint thickness for normal to medium corrosive atmosphere. For
highly polluted atmosphere and special application external paint work shall be as per direction of Engineer-in-
Charge. Design ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c) Seismic Zone as
1 NDSR per location of site, d) Altitude asper location/site. Noise level Shall not exceed limits asper NEMA TR-1 with all
accessories runningmeasured as per IEC 551 / NEMA standard. Thetransformer should have QR code which
shouldcontain drawing, test report OEM manual, Geo- Tag ofmanufacturing location etc. Marking Each
transformershall be provided with rating plate made of anodizedaluminium/ stainless steel material securely fixed
onthe outer body, easily accessible, as per IS: 1180Part-3. The entries on the rating plate shall beindelibly
marked.Fitting and Accessories : The following fittings shall be provided:- a) Two earthing terminals with the
earthing symbol b) Oil level gauge indicating oil level at minimum, 30°C and maximum operating temperature; c)
Air release device (for non-sealed type transformers) d) Rating and terminal marking plates; e) Silica gel breather f)
Drain-cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel with plug for three phase
transformers; g) Thermometer pocket with cap; h) Oil filling holes having (1¼″ nominal size thread) with cover (for
sealed type transformers without conservator); i) Lifting lugs for the complete transformer as well as for core and
winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k) One filter valve on the upper side
of the tank (for transformers above 200 kVA); l) Unidirectional flat rollers (for transformers above 200 kVA); m)
Inspection hole (for transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV bushing
terminal is connected to earth); o) Buchholz relay for transformers above 800 kVA. p) Arcing horns or suitable
rating lightning arrestors for HT side – 3 Nos. q) Bird guard; r) Oiltemperature indicator and winding temperature
indicators for transformers above 200 kVA with suitable tripping mechanism above permissible limit s) Jacking pads
(for transformer above 1 600 kVA); t) Additional Neutral separately brought out on bushing for earthing. u)
Magnetic oil level gauge (for transformer above 1600 kVA) with low oil level alarm contact; v) Non return valve (for
conducting pressure test); w) Pressure relief device or explosion vent x). Monogram Plate y) Inspection cover z).
Detachable type radiators with top and bottom shutoff valve. aa) Oil Conservator with Oil level indicator, minimum
level marking and drain plug for all transformers of capacity 50 KVA and above. bb) Necessary hardware, clamps,
lugs etc. for termination on HV/MV etc. for all transformers.
Removal of Existing Transformer , unwanted cables and related serviceable accessories from defined Location and
transporting to desired location of Storage to Client for their use as per direction of Engineer-In-Charge/Client
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in
ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
3.1 22.1.2 Above 120 sq. mm and upto 400 sq. mm Meter 50 694 34,700.00
Supplying and making outdoor cable end jointing with cast resin compound, including lugs and other jointing
materials, for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories
including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories
including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :
Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct
in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
7.1 10.1.3 Above 95 sq. mm and upto 185 sq. mm Meter 100 497 49,700.00
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC
insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Supplying and making outdoor end termination with cast resin compound including aluminium lugs and other
9 11.2 jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV
grade as required
Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials
for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry
11 5.4 enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke Each 1 8351 8,351.00
and salt as required.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry
12 5.6 enclosure with cover plate having locking arrangement and watering pipe of 2.7 Meter long etc. with charcoal/ coke Each 1 13733 13,733.00
and salt as required.
Supplying and laying 25 mm X 5 mm copper strip at 0.50 metre below ground as strip earth electrode, including
13 5.8 connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and Meter 30 1024 30,720.00
with 2 sets of brass nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection
with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
15 5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. Meter 10 1246 12,460.00
Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earth electrode, including
16 5.9 connection/ terminating with G.I. nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping Meter 30 160 4,800.00
and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with
G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
18 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. Meter 10 287 2,870.00
Termination of existing overhead lines with inew transformers as required, along with execution of all associated
and miscellaneous electrical works as directed by the Electrical Authority / Client / Engineer-in-Charge.”
Coordination with Local Electrical Authority for necessary clearance, inspection and charging of the new transformer
19 NDSR as per local electrical norms and procedures and obtaining clearance from State Electrical Authority including LS 1 100000 1,00,000.00
Processing Fees.
Digitally signed by JAYA
Execution of Special Repair Maintenance Work - SITC of 250 kVA Transformer at JNV Malkangiri, Odisha
Special Repair Works of Existing Transformer at JNV-1 in the District of Malkangiri
Bill of Quantity
S. DSR/ NS DSR-2023/ DSR-2023/
Description of items Unit Qty
No. Item No. DSR-2025 DSR-2025/
I Sub Head - I - Supply, Installation, Testing and Commisioning of Transformer
Supplying, installation, testing and commissioning of following capacity (continuous loading) BEE 5
Star rated (Corresponding Level as per BIS amended upto date of receipt of tender) , 11/0.433
KV step down, 3 Phase, 50 Hz, Dyn 11 vector group, ONAN (Oil Natural Air Natural) Copper wound
transformer (Electrolytic grade 99.9% pure copper, Core made of first grade Cold Rolled Grain
Oriented (CRGO) Core grade MOH or better, suitable for out door/indoor applications with Offload
Tap Changer/ On Load Tap Changer (OLTC) ( below 500 KVA offload and above 500 KVA On Load
Tap Changer) on HV side having AVR relay and Remote Tap Changer Control (RTCC) for automatic
sensing of incoming voltage, automatic operation of OLTC and facility for remote and manual
operation of OLTC HV side in range of +5% to -15% in steps of 2.5%, having cable end boxes
1 24.9 on HV side suitable for 3x300 sq.mm XLPE cable of 11 KV grade, including bus trunking
arrangement on LV side including supplying and laying of copper conductor multicore control cable
from transformer to HT breaker/panel for safety tripping, complete with all accessories and safety
provisions as per relevant IS Code including first filling of filtered dehydrated oil, i/c supplying
and grouting of suitable M.S. Channel with all accessories and transformer shall be confirming to
IS : 2026 (Part 1 to Part 5), IS : 1180 and as per CPWD specifications complete in all respects etc
as required at site. The maximum flux density in any part of the core and yoke at rated voltage
and frequency shall be such that the flux density with + 12.5 percent combined voltage and
frequency variation from rated voltage and frequency does not exceed 1.9 Tesla. The permissible
temperature-rise shall not exceed 35 0C
temperature-rise shall not exceed 35 0C for oil and 40 dg. C up to 200 KVA and 40 0C
for oil and 45 0C for above 200 KVA for winding. Inside of tank shall be painted with
varnish or liquid resistant paint. For external surfaces one coat of thermo setting
powder paint or one coat of epoxy primer followed by two coats of polyurethane base
paint shall be used. IS: 1180 (Part 3) shall be referred to for paint thickness for
normal to medium corrosive atmosphere. For highly polluted atmosphere and special
application external paint work shall be as per direction of Engineer-in-Charge. Design
ambient condition : a) air temperature 50 0C, b) Relative Humidity 90 % Max, c)
Seismic Zone as per location of site, d) Altitude as per location/site. Noise level Shall
not exceed limits as per NEMA TR-1 with all accessories running measured as per IEC
551 / NEMA standard. The transformer should have QR code which should contain
drawing, test report OEM manual,Geo- Tag of manufacturing location etc. Marking
Each transformer shall be provided with rating plate made of anodized aluminium/
stainless steel material securely fixed on the outer body, easily accessible, as per IS:
Part-3. The entries on the rating plate shall be indelibly marked.
Fitting and Accessories : The following fittings shall be provided:- a) Two earthing
terminals with the earthing symbol b) Oil level gauge indicating oil level at minimum,
30°C and maximum operating temperature; c) Air release device (for non-sealed type
transformers) d) Rating and terminal marking plates; e) Silica gel breather f) Drain-
cum-sampling valve (¾″ nominal size thread, IS 554) preferably steel
with plug for three phase transformers; g) Thermometer pocket with cap; h) Oil filling
holes having (1¼″ nominal size thread) with cover (for sealed type transformers
without conservator); i) Lifting lugs for the complete transformer as well as for core
and winding assembly; j) Pressure relief device or explosion vent above 200 kVA; k)
One filter valve on the upper side of the tank (for transformers above 200 kVA); l)
Unidirectional flat rollers (for transformers above 200 kVA); m) Inspection hole (for
transformers above 200 kVA); n) HV side neutral grounding strip (where one of the HV
bushing terminal is connected to earth); o) Buchholz relay for transformers above 800
kVA. p) Arcing horns or suitable rating lightning arrestors for HT side – 3 Nos. q) Bird
guard; r) Oil temperature indicator and winding temperature indicators for
transformers above 200 kVA with suitable tripping mechanism above permissible limit
s) Jacking pads (for transformer above 1 600 kVA); t) Additional Neutral separately
brought out on bushing for earthing. u) Magnetic oil level gauge (for transformer
above 1600 kVA) with low oil level alarm contact; v) Non return valve (for conducting
pressure test); w) Pressure relief device or explosion vent x).
Monogram Plate y) Inspection cover z). Detachable type radiators with top and bottom
shutoff valve. aa) Oil Conservator with Oil level indicator, minimum level marking and
drain plug for all transformers of capacity 50 KVA and above. bb) Necessary
hardware, clamps, lugs etc. for termination on HV/MV etc. for all transformers.
2 NSI-1 Providing & fixing GI chain link fencing with in mesh size 50x50mm SQM 30 3,666.30 1,09,989.00
3 NSI-2 Removal of Existing Old Transformer Job 1 35,000.00 35,000.00
Total Carried to Summary Sheet for SubHead I 7,67,276.00
II Subhead - II - Earthing
Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and
4 5.2 providing masonry enclosure with cover plate having locking arrangement and Sets 2 7,658.00 15,316.00
watering pipe etc. with charcoal/ coke and salt as required.
Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories,
5 5.4 and providing masonary enclosure with cover plate having locking arrangement and Sets 2 8,351.00 16,702.00
watering watering pipe 2.7 metre long etc. with charcoal/ coke and salt as required.
Earthing with Cu. earth Plate 600mm x 600mm x 3mm thick including accesssories,
and providing masonary enclosure with cover plate (CI heavy duty) having locking
arrangement and watering pipe pipe of 2.7 mtr long etc. with charcoal or coke and
salt) as required.
Authorised Signatory
Bidder BoQ Page 3 of 5 Digitally signedNBCC
Execution of Special Repair Maintenance Work - SITC of 250 kVA Transformer at JNV Malkangiri, Odisha
S. DSR/ NS DSR-2023/ DSR-2023/
Description of items Unit Qty
No. Item No. DSR-2025 DSR-2025/
Supplying and laying 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth
7 5.11 electrode, including connection with G.I. nut, bolt, spring, washer excavation and Mtrs. 10 755.00 7,550.00
refilling etc. as required.
Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for
8 5.14 connections etc. as required. 2 nos used for 50 x 5 for the Neutral earthing of Mtrs. 20 1,246.00 24,920.00
Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections
etc. as required.
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing etc.
Total Carried to Summary Sheet for SubHead II 1,01,076.00
III Subhead - III - Supplying & Laying of Cable
Supplying and laying of following size DWC HDPE pipe ISI marked along with all
accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete
11 15.16 with fitting and cutting, jointing etc.direct in ground (75 cm below ground level)
including excavation and refilling the trench but excluding sand cushioning and
protective covering etc., complete as required.
Supplying and laying of following size DWC HDPE pipe ISI marked along with all
12 15.15 accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete
with fitting and cutting, jointing etc. in the existing trench, complete as required.
Laying of one number PVC insulated & PVC sheathed/ XLPE Power cable of 1.1 KV
grade of following size in the existing RCC/HUME/METAL pipe as required.
13.4 10.5.4 Above 185 sq.mm and upto 400 sq.mm 0 170.00 -
Supply of following sizes of XLPE insulated Aluminum conductor strip/ wire Armoured,
14 11.1 overall PVC sheathed 1.1 KV grade cables conforming to relevant IS-7098 Code and
technical specifications.
14.1 NSI-3 6 sq. mm 4 core 0
Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in ground
15 15.14 complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand)
including trenching (75 cm deep) and refilling etc as required.
16 NSI-4 Supply of First Aid box as directed by Engineer Incharge No 3 4,370.72 13,112.16
Supply of tool kit with 1 pair 11 KV rubber hand gloves as directed by Engineer
Supplying & fixing standard shock treatment charts in English & Hindi duly framed and
covered with glass as directed by Engineer Incharge.
Authorised Signatory
Bidder BoQ Page 4 of 5 Digitally signedNBCC
Execution of Special Repair Maintenance Work - SITC of 250 kVA Transformer at JNV Malkangiri, Odisha
S. DSR/ NS DSR-2023/ DSR-2023/
Description of items Unit Qty
No. Item No. DSR-2025 DSR-2025/
Providing Safety mat made of elastomeric polymers Material (Class B) 1.2 M wide with
thickness 2.5 mm to withstand 12KV dielectric strength AS PER relevant IS Code
Providing a mat made of elastomeric polymers Material (Class A )1.2 M wide with 2
mm thickness to withstand 1.1 KV dielectric strength AS PER relevant IS Code
Total Carried to Summary Sheet for SubHead III 2,12,026.48
Authorised Signatory
Bidder BoQ Page 5 of 5 Digitally signedNBCC
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
NIT.pdf
Tender Document
GCC_2026.pdf
Tender Document
SCC.pdf
Tender Document
BOQ.pdf
Tender Document
Technical Specification.pdf
Tender Document
List of Approved Makes.pdf
Tender Document
Technical Circular_31.pdf
Tender Document
Milestone.pdf
Tender Document
corrigendum-5367-Corrigendum02.pdf
pdf • 0.11 MB
corrigendum-5327-Corrigendum01.pdf
pdf • 0.09 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .