Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Tender Value
₹1.5 Cr
EMD Value
₹2.2 L
Closing Date
5 Feb 2026, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Col Pawan Kumar, CWE
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
AUGMENTATION OF EXTERNAL ELECT SUP INCL UPGRADATION OF EXISTING TRANSFORMER AT SI LINES UNDER GE BHOPAL
2025_MES_740870_1
84114/E8
Open Tender
Civil Works
Item Rate
180 days
Bhopal
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹1,000
Yes
GE Bhopal
₹2.2 L
Yes
21 Nov 2025
21 Nov 2025
7 Feb 2026
21 Nov 2025
5 Feb 2026
15 Jan 2026
21 Nov 2025 - 3 Jan 2026
S & F of 33 KV, ISOLATOR 600 mm (Turn and twist type) complete all as specified and directed.
S & F of 33 KV(104.98 SQMM) AL-59 ACS XLPE Covered Conductors as per EN:50397, p-1:2020, SS4240813,SS 4240814, IEC 1232 WITH 95 C CONTINUOUS OPERATING TEMPERATURE of ACS class 20S A/ Grade A extruded semi conducting Material, with MVCC Accessories(1 KM Cond.) complete all as specified and directed.
M & L for Stone Block/ Pre cast block for base peddding (450X450X75MM) complete all as specified and directed.
M & L for Concreting of Rail/Hibeam [email protected] per pole including muffing of pole complete all as specified and directed.
S & F Concreting of stay (20mm /25mm)@0.3 cmt per stay complete all as specified and directed.
M & L of Aluminium Paint complete all as specified and directed.
S & F Stay GI Wire 7/4.00 MM(7/8 SWG) complete all as specified and directed.
S & F Anti Climbing devices (Barbed wire 2.24mmdia, 14 SWG) complete all as specified and directed.
S & F Earthing coil of 115 turns of 50MM Dia and 2.5 Mtr lead of 4.0mm GI wire complete all as specified and directed.
S & F M.S.nuts with Bolts complete all as specified and directed.
S & F 33 KV Strain hardware (T&C type) fittings complete all as specified and directed.
H-Beams 152X152mm, 37.1 Kg/mtr -15Mtr, Long-565.5 Kg complete all as specified and directed.
H-beams 152X152mm, 37.1 Kg/mtr -13Mtr, Long-482.3 Kg complete all as specified and directed.
S & F 33 KV V cross-arms 75x75x6mm angle (Each weight 1.92 Kg) complete all as specified and directed.
S & F Back Clamps for H-Beams of MS Flat 65x8mm (Each wt 1.92Kg) complete all as specified and directed.
S & F 33 KV Top clamps 75x75x6mm Angle complete all as specified and directed.
S & F of D.C Cross -arms 8 ft center to center(100x50x6mm) Channel complete all as specified and directed.
S & F of 33 KV Slide cross arm complete all as specified and directed.
S & F of Stay set 20 mm complete without Stay wire (Painted) complete all as specified and directed.
S & F of Stay Clamp 50x6MM flat for fixing U Clamp complete all as specified and directed.
S & F of Clamp 65x8mm Flat of MS Flat for H-Beam(Each wt 3.2 Kg) complete all as specified and directed.
S & F of 33 KV Single Pole Cut Point Channel(100x50x6mm MS Channel) 1.65 Mtr long complete all as specified and directed.
Danger Boards Enamelled 33 KV complete all as specified and directed.
S & F of 33 KV Pin Insulator Polymer Composite (10 KN) complete all as specified and directed.
S & F of 33 KV (45 KN) Composite Polymer Disc Insulators complete all as specified and directed.
M & L for Red Oxide Paint complete all as specified and directed.
Depositing of supervision charges of amount Rs/- 3,91,114.00 to MPMKVVCL is compulsary for execution of this work complete all as specified and directed. Note :- Super vision charges of MPMKVVCL may be varried depending upon latest charges)
M & L for Enhancement of CMD from 900 KVA to 1100 KVA ( Depositing charges of amount Rs/- 8,54,980.00/ for 33 KV bulk connection at MRS SI Line from MPMKVV Co. Ltd) complete all as specified and directed. Note :- Super vision charges of MPMKVVCL may be varried depending upon latest charges)
Supply, fixing, testing and commissioning of Digital Power Meters a) All electrical Parameters with harmonic measurement (THD-V%, THD-I%, up to 31th harmonic for current and voltage separately) 3 Phase 4 wire Digital Power Analyzer with following Features complete all as specified and directed. b) The meter displays and communicates V, I, Hz, PF, KW, Kwh, KVAh, KVArh, THD-V, THD-I, Neutral Current & more. c) The meter is equipped with RS 485 Communication Port. d) Alarm contact Output & 4-20mA Analog Output for PLC's. e) Displays Maximum & Minimum Demand Values. f) Data Logging with Internal Memory) Parameters and demand values are stores even if supply voltage is cut off. g) Real Time Clock. h) Confirming IEC- 62053-24
Supply,fixing,testing and commissioning of ACB, 4Pole of Microprocessor Based with breaking capacity of 50kA, Ics=100% Icu, Inbuilt or External Instantaneous Protection and Inbuilt Ground Fault Protection Individual Fault Indication LEDs incl Suitable size of CTs asper site requirement Suitable Size of ACB it must be minimum of 1.3 times of Tx. including Shunt Release system with suitable size of panel cabinet made of CRCA sheet of 2 mm thickness Loading Current where PTR 1.6 MVA (33/11kV) complete all as specified and directed.
Supply,fixing,testing and commissioning of MCCB, 4Pole of Microprocessor Based with breaking capacity of 50kA, Ics=100% Icu, Inbuilt or External Instantaneous Protection and Inbuilt Ground Fault Protection Individual Fault Indication LEDs incl Suitable size of CTs asper site requirement & Suitable Size of MCCB it must be minimum of 1.3 times of Tx. including Shunt Release system complete all as specified and directed. Note :- Provn of suitable size of panel cabinet made of CRCA sheet of 3.15 mm thickness in case of non availibilty space for mounting arrangement of MCCB on existing Panel is deemed to be included in the quoted unit rate.
All as per item No. 31 here-in-before but DTR 63 KVA (33/0.415 KV), 100A
All as per item No. 31 here-in-before but DTR 100 KVA (11/0.415KV) , 200A
All as per item No. 31 here-in-before but DTR 160 KVA (11/0.415KV) , 250A
All as per item No. 31 here-in-before but DTR 200 KVA (11/0.415KV), 315A
All as per item No. 31 here-in-before but DTR 250 KVA (11/0.415 KV), 500A
All as per item No. 31 here-in-before but DTR 400 KVA (11/0.415 KV), 630A
Supply,fixing,testing and commissioning of Energy Management System Software (SCADA) with Following Features:- Data base Integration Software,Monitoring of all connected meters, Daily/ weekly / Monthly Report generation for analysis Graphical Analysis of all electrical parameters of each meter & also main Meter,Alarms -User Define alarms for Low PF/ Maximum Demand overshoot etc complete all as specified and directed. Make: Siemens / Allen Bradley / Delta Electronics /Honey well /L & T Note :- System Integretor shall ensure that the SCADA/EMS and RTU/Master Controll Unit should be same make asper mentioned in NIT.
Supply,fixing,testing and commissioning of Data Line Converter with Ethernet complete all as specified and directed.
Supply,fixing,testing and commissioning of Life Time License Software to Monitor and Control from Main Control Room PC as seen any abnormal condition occurs and technology must be used GPS/GPRS with VPN Network Creation SIM Charges Monthly/Yearly born by Contractor complete all as specified and directed.
Supply,fixing,testing and commissioning of Desktop Mounted Industrial type PC: Processor: i7 /2.8GHz, PCI Slots and 2 LAN card, 4USB, VGA/HDMI, Hard disk: 1TB & 1TB Built-in SSD, RAM 16GB,with Monitor, Keyboard/Mouse, Window 7/10 operating System(OS), With Antivirus, Fan Less Design complete all as specified and directed.
Supply,fixing,testing and commissioning of Online UPS Battery with 2 Hrs backup incl battery rack & inter link Cable at master controll room as per master controll PLC Loading current complete all as specified and directed.
Supply,fixing,testing and commissioning of Multi Option Laser Printer for report printing complete all as specified and directed. Make : HP/Canon/Epson
Supply,fixing,testing and commissioning of Eathernet Network Switch of 8 ports complete all as specified and directed. Make : Scheinder/Axis/D- Link/ Delta Electronics
Supply,fixing,testing and commissioning of HD Smart LED Screen greater than 42” with HDMI/Communication Port complete all as specified and directed. Make : Sony/LG/Samsung
M & L for fixing of Armoured Ethernet Wire Cat 6 for network connection
Supply,fixing,testing and commissioning of RTU Units with required Digital I/Os and Analogue I/Os at each location with minimum 3hr backup complete all as specified and directed. Note :- System Integretor shall provide the OEM auth Certificate as mentioned in the NIT.
Supply,fixing,testing and commissioning of Master Control Units contains each RTUs with minimum 3 hr backup complete all as specified and directed. Note :- System Integretor shall provide the OEM auth Certificate as mentioned in the NIT.
M & L for PVC Insulated,shielded 2 Core copper beldon wire for meter Data communication connection as required complete all as specified and directed.
S & F of 25 mm heavy duty (HMS) PVC conduits,ISI marked concealed / surface in shaft as required including all accessories i.e. bends, junction boxes with cover plates of approved make and design (Wherever required) complete all as specified and directed.
M & L for installation of Static IP at master controll room incl Network SIM card at Each RTU location complete all as specified and directed.
Installation, commissioning & Training for complete SCADA system all as specified and directed.
M & L for Non Comprehensive Maintenance & Monitoring,mangement of SCADA Based EMS system for smoothly functioning of 3 Years AMC (Two year under warranty period and one year of non comprehensive type incl per month One Visit of Auth SCADA system integreator for routine maintainance and submit a log book report to the resp authurity and one tech rep detl in General Shift ) including carrying out maintenance and servicing of PLC & SCADA Panel and all connected circuit and accessories as required for all the modernised electric supply system as described at SI Line under GE Bhopal - MP complete all as specified and directed.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.32 MB
BOQ_829601.xls
BOQ • 0.26 MB
84114TenderDocuments.pdf
Tender Documents • 1.25 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .