| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹37.9 LAccepted-AOC PLOT NO DSS 170 HUDA SHOPPING COMPLEX SECTOR 31 FARIDABAD FARIDABAD HARYANA FARIDABAD HARYANA 121003 | FARIDABAD | HARYANA | 121003 | L1 | Accepted-AOC LOWEST RATE QUOTE | |
| 2 | L2₹38.7 L+₹77,802 (2.05%)Rejected-AOC | L2 | Rejected-AOC HIGHER RATE QUOTE | |
| 3 | L3₹40.3 L+₹2.4 L (6.31%)Rejected-AOC | L3 | Rejected-AOC HIGHER RATE QUOTE | |
| 4 | L4₹41.9 L+₹3.9 L (10.4%)Rejected-AOC | L4 | Rejected-AOC HIGHER RATE QUOTE | |
| 5 | L5₹42.5 L+₹4.6 L (12.0%)Rejected-AOC 11TH FLOOR ECO CENTRE BUSINESS TOWER P NO 4 EM BLOCK SECTOR V KOLKATA 91 | KOLKATA | 24 PARAGANAS NORTH | WEST BENGAL | 700091 | L5 | Rejected-AOC HIGHER RATE QUOTE |
Tender Value
₹63.1 L
EMD Value
₹1.3 L
Closing Date
24 Feb 2020, 6:00 pmClosed
AGM (E-E)
Civil Airport, Gorakhpur
Provision of Air-Conditioning of Terminal Building for RCS Operation at Kushinagar Airport
2020_AAI_42770_1
AAI/Kushi./E-E/VRF/2019-20/
Open Tender
Electrical Works
Item Rate
60 days
Kushinagar Airport
Please refer Tender documents.
7 documents required · 7 mandatory
₹1,180
Revenue collection (Lucknow Airport)
₹1.3 L
13 Jun 2020
12 Feb 2020
28 Feb 2020
12 Feb 2020
24 Feb 2020
12 Feb 2020
12 Feb 2020 - 18 Feb 2020
Amount
Supply, lifting,shifting,local transport,port clearance,insurance,installation, testing and commissioning, of VRV/VRF outdoor units (ODU) with R410A refrigerant complete with hermetic SCROLL Inverter compressor, anti corresive fin heat exchanger, refrigerant shut off valves,safety devices, inverter controller, multi step function to meet load fluctuation, axial flow quiet operation condenser fans, MS support stand suitable for ODU with 2 coats of synthetic primer and 1 coat of enamel paint , starter panel, microprocessor based control panel, modular type construction, safety devices, controls, fault alarm indications, memory storage, hydrophilic coated condenser coil with copper tube and copper header, condenser guard, fan guard, CRC coated outer casing, vibration isolators, compressor jacket; as per the specification The VRV sytems should have both heating & cooling modes. The COP at AHRI conditions shall not be less than 3.1 & IEER not less than 6.5. The ODU must deliver COP of minimum 4.7 at 50% load. Contractor need to get the COP tested at NABL/AHRI Certified Laboratory. The unit shall deliver the rated capacity at AHRI Conditions and work even at 50 Deg C Ambient temperatures without tripping. The capacity shall be as indicated below. MAKE --- LG / Mitsuibishi Electric / Voltas/Equivalent AAI approved make
Terminal Building for Departure:- 80 HP with All inverter compressor (20 HP 4 nos only or any other combination totalling to 80HP as suggested by OEM )
Guest House at Arrival:- 20 HP with All inverter compressor
Terminal Building for Departure - For Treated Fresh Air:- 22 HP with All inverter compressor
VRV / VRF INDOOR UNIT:- Supply, installation and commissioning of 4-way cassette type direct expansion indoor units with individual blade control for all the four directions including blower, TEFC blower motor, suitable for operation on 240 ± 10% volts, 1 phase, 50 Hz A.C. supply, copper tube aluminium finned direct expansion cooling coil, pre filters, electronic expansion valve with cordless remote and control wiring, drain connections with anti-vibration mountings, Fresh Air connection etc., as required and as per schedule of equipment and specifications. Cooling Capacity MAKE --- LG / Mitsuibishi Electric / Equivalent AAI approved make
1.0 TR Nominal Capacity
1.28 TR Nominal Capacity
1.57 TR Nominal Capacity
2.0TR Nominal Capacity
4TR Nominal Capacity
VRV / VRF PIPING & ELECTRICAL WORK:- Supply & installation of 18G, hard drawn copper Refrigerant piping, duly insulated with closed cell elastomeric nitrile rubber insulation, class-o, covered with fiber glass cloth and two layers of shield coating, complete with elbows, T joints, sleeves etc., with GSS slotted rail supporting arrangement and GI clamp for individual pipes.
54.1 mm OD (Insulation = 19mm thick)
41.3 mm OD (Insulation = 19mm thick)
34.9 mm OD (Insulation = 19mm thick)
28.6 mm OD (Insulation = 19mm thick)
22.2 mm OD (Insulation = 13mm thick)
19.1 mm OD (Insulation = 13mm thick)
15.9 mm OD (Insulation = 13mm thick)
12.7 mm OD (Insulation = 13mm thick)
9.5 mm OD (Insulation = 13mm thick)
6.4 mm OD (Insulation = 13mm thick)
Supply, fixing and commissioning of imported refrigerant joint / Branch distibutors indoor to outdoor complete with nitrile rubber insulation, supporting etc.
Supply, Installation & testing of PVC pipes for drain pipes with 9 mm thick insulation upto the shaft as per specifications and approved drawings from the each indoor unit to respective drain pointed as indicated in the layout drawing.
50 mm dia
40 mm Dia
32 mm Dia
25 mm Dia
Supply & installation of 2 coreX 1.5 Sq.mm control cum transmission wiring interconnecting outdoor units to all indoor units wiring through PVC FRLS conduit .
Electrical power & Control cabling complete with earthing .The isolator switch to the outdoor units . Power & control cable should be 1.1 KV grade Cu conductor, PVC armoured cables . Cable price should include cost of end termination also. Please note power shall be terminated through a suitable isolator near the outdoor unit by other agency.
4C x 25 sqmm - CU Armoured
4C x 16 sqmm - CU Armoured
4C x 10 sqmm - CU Armoured
4C x 6 sqmm - CU Armoured
Electrical power & Control cabling complete with earthing for indoor unit. Power & control cable should be 1.1 KV grade Cu conductor, PVC Flexible cables . Cable price should include cost of end termination also. Please note power shall be terminated through a suitable isolator near the Indoor unit by other agency.
3C x 6Sqmm - Cu Flexible cable
3C x 4Sqmm - Cu Flexible cable
3C x 2.5Sqmm - Cu Flexible cable
Supply and fixing of following GI flats / wires including all necessary fixing accessories and effective connections with copper riveting / welding etc as approved
8 SWG GI wire
SITC of circular/cabinet inline fan complete with motor, cabling between starter and fan etc.
500CFM with 10mm Static
400CFM with 10mm Static
300CFM with 10mm Static
200CFM with 6mm Static
100CFM with 6mm Static
M.S. Structure/ Work
Supplying,Installing,Testing and Commissioning of MS structure work which will make the entire system as complete and functional and prove the practical results as per the design guidelines with all lead and lifts, M.S.plate /channels etc.for fixing different equipments as per instruction of Consultant/Engineer-in-charge.Inclusive of 2 coats of red oxide paint and black finish as per standards to avoid rusting of MS steel.
Electrical panel for AC
Sai Cooling Point Private Limited
UNITY ENGINEERS
M/S COOLING CENTER
Blue Star Limited
VOLGA AIR TECHNOLOGIES
VOLKS ENERGIE PVT LTD
Ingenious Industries
SAI H.V.A.C. SYSTEM
Industrial Traders
Shambhavi Enterprises
stage.html
html • 0.07 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .