| # | Company | Quoted % | Amount | Rank | Status |
|---|---|---|---|---|---|
| 1 | L1₹11.8 LAdmitted-Finance | -21.99% | ₹11.8 L | L1 | Admitted-Finance |
| 2 | L2₹13.4 L+₹1.6 L (13.7%)Admitted-Finance | -11.33% | ₹13.4 L+₹1.6 L (13.7%) | L2 | Admitted-Finance |
| 3 | L3₹13.9 L+₹2.1 L (17.6%)Admitted-Finance | -8.25% | ₹13.9 L+₹2.1 L (17.6%) | L3 | Admitted-Finance |
| 4 | L4₹14.6 L+₹2.8 L (24.0%)Admitted-Finance G 15 PKT 2 NARAINA VIHAR NEW DELHI 110028 | NEW DELHI | DELHI | 110028 | -3.30% | ₹14.6 L+₹2.8 L (24.0%) | L4 | Admitted-Finance |
Tender Value
₹15.1 L
EMD Value
₹30,295
Closing Date
29 May 2026, 3:00 pmClosed
EE,ELD-4,DDA
EE,ELD-4,DDA
Supply/Replacement of the accessories of existing Fire Fighting system and other electrical accessories at Pocket-7, Sector-A1-A4, Narela.
2026_DDA_909669_1
13/EE/ELD-4/DDA/2026-27
Open Tender
Electrical Works
Works
60 days
NARELA
Please refer Tender documents.
14 documents required · 14 mandatory
₹0
₹30,295
25/05/2026 at 11.30 A.M. in the chamber of EE/ ELD
4 Jun 2026
21 May 2026
29 May 2026
21 May 2026
29 May 2026
26 May 2026
25 May 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Supply, installation, testing and commissioning of ABS plastic shut off nozzle for hose reel complete as required. | - | Nos. | 276 | - |
| 2 | Supplying and fixing single headed internal hydrant valve with instantaneous Gunmetal/Stainless Steel coupling of 63 mm dia with cast iron wheel ISI marked conforming to IS 5290 (Type -A) with blank Gunmetal/Stainless Steel cap and chain as required.
Single headed Stainless steel | - | Nos. | 6,632 | - |
| 3 | Providing and fixing M.S. dead plate/blank flange cover for missing landing valve outlet of internal fire fighting system, fabricated from minimum 6 mm thick mild steel plate of suitable size conforming to landing valve outlet dimensions, including rubber insertion gasket, nuts, bolts, washers and necessary drilling/threading complete, duly painted with one coat of red oxide primer and two coats of synthetic enamel paint of approved fire red shade, properly fixed to prevent leakage and maintain integrity of the fire fighting line etc. complete as required. | - | Nos. | 1,081 | - |
| 4 | Supplying and replacement of heavy duty rechargeable battery of 180 AH, 12 Volt suitable for DG set/UPS/fire alarm or other approved application, complete with all necessary connections, terminals, accessories, transportation, installation, testing and commissioning as required. The battery shall be of approved make and conform to relevant IS specifications, with warranty period of 36 months comprising 18 months free replacement warranty and further 18 months warranty on pro-rata basis, cetc. complete as required. | - | Nos. | 16,483 | - |
| 5 | Supplying, installing, testing and commissioning automatic battery charger suitable for charging 180 AH, 12 Volt rechargeable battery, complete with input/output connections, charging indicators, protection against overload, short circuit and reverse polarity, housed in suitable powder coated metal enclosure, compatible for DG set/UPS/fire alarm or approved application, conforming to relevant specifications, including all accessories and wiring required for proper functioning etc. complete as required. | - | Nos. | 6,156 | - |
| 6 | Supply, installation, testing and commissioning of 4 Pole, 1000 Amps electrically operated draw-out type Air Circuit Breaker (ACB), suitable for 415 Volts, 50 Hz, AC supply, having minimum breaking capacity of 50 kA at 415 Volts, complete with microprocessor based release with adjustable Over Load (O/L), Short Circuit (S/C), Instantaneous and Earth Fault protections, LED indications, ON/OFF/TRIP indications, shunt trip, under voltage release, motorized spring charging mechanism, auxiliary contacts and all standard accessories, conforming to relevant IS/IEC standards, including dismantling/removal of existing defective ACB, modification of panel if required, connection with existing bus bars/cables, complete wiring, testing, commissioning and making the system fully functional and complete as required at site with a minimum warranty of 12 months. | - | Nos. | 1,81,414 | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 1.60 MB
NIT13.pdf
Tender Documents • 1.58 MB
BOQ_956081.xls
BOQ • 0.28 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .