Executive Engineer (Elect)-II
OFFICE OF THE Ex. ENGINEER (ELECT)-II, SHAHDARA (N) ZONE, KeshavChowk, Delhi-110053
Provision of SHM Poles ( Two Nos) at Rehman chowk and Entry Gate of Kabristan in Shri ram colony to remove the dark spots in ward no 246, Shriram colony, Under Shahdara North Zone
2026_MCD_295174_1
EE(E)-II/SNZ/MCD/26-27/TC-19/2
Open Tender
Electrical Works
Percentage
120 days
As per NIT
Please refer Tender documents.
4 documents required · 4 mandatory
₹590
₹8,857
18 Nov 2026
21 Oct 2026
28 Oct 2026
21 Oct 2026
28 Oct 2026
21 Oct 2026
120 days
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required. | 4 | Nos | 5,958 | ₹23,832 |
| 2 | Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | 20 | Mtr. | 287 | ₹5,740 |
| 3 | Providing and fixing 6 SWG dia G.I wire on surface or in recess for for loop earthing as required. | 60 | Mtr. | 84 | ₹5,040 |
| 4 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing RCC/ HUME/ METAL pipe as required. (a) Upto 35 sq. mm | 60 | Mtr. | 47 | ₹2,820 |
| 5 | Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 kV grade of following size in the existing masonry open duct as required. (a) Upto 35 sq. mm | 20 | Mtr. | 36 | ₹720 |
| 6 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc..direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) | 60 | Mtr. | 289 | ₹17,340 |
| 7 | Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc. in the existing trench, complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal) | 20 | Mtr. | 136 | ₹2,720 |
| 8 | Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*10 sqmm | 80 | Mtr. | 116 | ₹9,280 |
| 9 | LED Flood Light, powder coated pressure die cast aluminum
+(System lumen efficacy ≥120 and <135 lm/Watt)
Supplying, installation, Testing & Commissioning of Flood Light, powder coated pressure die cast aluminum body with built in or separate driver as per the requirement with Driver efficiency >85%, Input voltage:Input voltage: 140-270 Volt AC, freq 50/60 hz, Operating temp range -15 deg to 50 deg centigrade, internal surge protection of 5 KV L,N,E as per IEC 61000-4-5, Driver efficiency >85%,THD < 10% as per IEC 61000-3-2 , PF.≥0.95, IP-66,IK-10, CRI >80 , under voltage and over voltage protection, EMI-EMC as per CISPR-15, lenses for beam angle 30 deg 120 deg as per the application and the project requirement deg, suitable tiltable fitting, life time (LED,Driver & electrical circuitry) of minimum 50000 Burning Hours with 70% of initial Lumen maintained till life ends as per LM80 extrapolation IES TM-21-11 report , CCT 3000°K / 4000°K /5700°K/6000°K/6500°K (As per ANSI Bin) ,DCM(Standard Deviation Color Matching) <5, Maximum power consumption should not more than the specified rating and Fixture shall be of relevant BIS standard complete in all respect i/c connections with 1.5 sq mm FRLS, PVC insulated copper conductor single core cable and earthing etc. as required with
Minimum 5 year OEM warranty. System lumen efficacy ≥120 and <135 lm/Watt output . LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as per BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement.(Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).(A) 150 WATT | 12 | Nos | 3,374 | ₹40,488 |
| 10 | Supply and fabrication of pole protection system made up of 8SWG steel wire mesh of size25mmx75mm rectangular with 50mmx50mmx6mm MS angle iron for supporting the mesh and grounding the protection system in suitable quality of CC etc as reqd. | 24 | PSq.mt | 1,108 | ₹26,592 |
stage.html
html • 0.02 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.23 MB
circular.pdf
Tender Documents • 9.28 MB
Conditions.pdf
Tender Documents • 0.04 MB
GCC2024.pdf
Tender Documents • 9.36 MB
BOQ_344061.xls
BOQ • 0.27 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart shows the information on this page on a best-effort basis and does not guarantee that it is accurate, complete or current. Check it against the buyer's official notice and documents before you act on it; the official record prevails. TenderKart is not liable for any loss or claim arising from the use of this information. If you notice any error or omission, please let us know at .