GE (AF) E/M Chakeri
GE (AF) E/M CHAKERI KANPUR 208008
COMPREHENSIVE MAINT OF FIRE FIGHTING SYSTEM IN TECH AREA AT AFS KANPUR
2022_MES_552542_2
8595/E8
Open Tender
Electrical and Maintenance Works
Item Rate
274 days
GE (AF) E/M CHAKERI
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE (AF) E/M CHAKERI
₹60,000
Yes
15 Feb 2023
28 Oct 2022
1 Dec 2022
28 Oct 2022
25 Nov 2022
11 Nov 2022
Amount
Comprehensive monthly maintenance of auto fire alarm system installed in Bearing Hospital in Tech Area at AF Stn Chakeri complete all as specified and directed. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operation of all the equipment of fire detection system should be maintained. (iii) The contractor will submit daily inspection report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through experienced technician. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Spare parts required for replacement will be measured and paid separately under respective items of BOQ. Note:- 1. The detail of fire detection & fire fighting system are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (200 device/loop card) - 01 No. (b) UL Listed intelligent addressable multi-criteria detector with base - 73 Nos. (c) UL Listed intelligent heat detector - 02 Nos. (d) Manual call point - 08 Nos. (e) Control module for hooter - 14 Nos. (f) Zone Monitor module - 14 Nos. (g) Fault isolator - 08 Nos. (h) Wall mounted hooter - 14 Nos. (j) Response indicator - 12 Nos. (k) IR Flame detector - 14 Nos. (l) UPS 500 VA - 01 No. 2. Testing of the entirefire detection and alarm system shall be carried out and report will be submitted regardinding functioning of the system.
Comprehensive monthly maintenance of auto fire alarm detection and fire fighting system installed in M-53 OF 4BRD in Tech Area at AF Stn Chakeri complete all as specified and directed. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operational of all the equipment of fire detection system should be maintained. (iii) The contractor will submit daily inspection report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through experienced technician. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Spare parts required for replacement will be measured and paid separately under respective items of BOQ.
Note:- 1. The detail of fire detection & fire fighting system are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (200 device/loop card) - 01 No. (b) UL Listed intelligent addressable multi-criteria detector with base - 4 Nos. (c) UL Listed intelligent heat detector - 02 Nos. (d) Auto dialer - 01 Nos. (e) External siren - 01 Nos. (f) Nitrogen gas cyclinder - 05 Nos. (g) Carbon di oxide cyclinder - 15 Nos. (h) Manual call point - 08 Nos. (i) Control module for hooter - 4 Nos. (j) Zone Monitor module - 4 Nos. (k) Fault isolator - 08 Nos. (l) Response indicator - 12 Nos. (m) IR Flame detector - 02 Nos. (n) UR Gas detector - 04 Nos. (o) Smoke detector - 02 Nos (p) UPS 500 VA - 01 No. 2. Detection system shall be tested monthly along fire fighting system. 3. Fire fighting system and complete system efficiency along with release of Carbon di oxide and Nitrogen shall be tested at least once in three month. 4. Weighing of Carbon di oxide and Nitrogen per month shall be done. 5. Testing of the entire fire system shall be carried out and report will be submitted regardinding functioning of the system.
Comprehensive monthly maintenance of auto fire alarm system installed in TTCLRE Hanger in Tech areaat AF Stn Chakeri complete all as specified and directed. The detail scope of work consists of the following:- (i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operation of all the equipment of fire detection system should be maintained. (iii) The contractor will submit daily inspection report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge. (iv) The maintenance shall be carried out through experienced technician. (v) Emergency visit will be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Spare parts required for replacement will be measured and paid separately under respective items of this schedule. Note:- The detail of fire detection & fire fighting system are as under:- (a) UL Listed auto fire alarm control panel having micro processor based two loop cards (200 device/loop card) - 01 No. (b) UL Listed intelligent addressable multi-sensor detector with heat & smoke combination - 492 Nos. (c) UL Listed intelligent heat detector - 04 Nos. (d) Manual call point - 82 Nos. (e) Audio visual indication of smoke or fire - 20 Nos. (f) Zone Monitor module (g) Fault isolator - 30 Nos (h) Wall mounted hooter (j) Response indicator -100 Nos. (k) IR Flame detector (l) UPS 500 VA 2. Testing of the entire fire detection and alarm system shall be carried out and report will be submitted regardinding functioning of the system.
S&F in replacement intelligent Analogue addressable multicriteria type heat with smoke detector with base complete all as specified and directed. Make: MOORLEY/APOLLO/Siemens/Honeywell
S&F in replacement intelligent Analogue addressable type manual call point with box resettable type complete all as specified and directed. Make: MOORLEY/APOLLO/Siemens/Honeywell
S&F in replacement Electronic hooter cum strove to provide audio visual indication of smoke or fire with public address system compatibility complete all as specified and directed. Make: MOORLEY/APOLLO/Siemens /Honeywell
S&F in replacement remote response indicator complete all as specified and directed. Make: MOORLEY/APOLLO/Siemens /Honeywell
S&F in replacement Fault isolator to prevent short circuit/open circuit complete all as specified and directed. Make: MOORLEY/APOLLO/Siemens /Honeywell
S&F in replacement for Nozzle 63 mm dia short bench pipe confirming to IS 2871 : 1983 made of cast copper alloy complete all as specified and directed. Make: New Age / Omex / CEASEFIRE / SAFEX / MINIMAX
M&L for repair of loop microprocessor based fully analog addressable type fire alarm repeater panel complying with BSEN 54 single loop panel of capacity upto 200 detector and module (per each loop) including replacement of faulty part complete all as specified and directed. Make: Honeywell/APOLLO/Siemens/Moorley
M&L for repair of Intransically safe Conventional photoelectric smoke Detector UL/FM/LPC approved with junction box and base complete to be fixed inside test rig with suitable fixing arrangement complete all as specified and directed. Make: Apollo Model Orbis Cat Part No ORB-OP-52027-APO / Systen Sensor Cat Part No JTY-GD-2151 EIS / Hochiki / BOSCH
M&L for repair of Intransically safe conventional heat detector class AIR, UL / FM / LPC approved with base complete all as specified and directed. Make: Apollo Model Orbis Cat Part No ORB-HT-51145-APO / Systen Sensor Cat Part No JTWB-BCD-5151EIS / Hochiki / BOSCH
S&F in replacement External Siren 2 KM range with control panel complete all as specified and directed. Make: Kheraj / KPT / National / System Sensor
S&F in replacement Nitrogen gas cylinder 4 Kg Pilot with nitrogen gas ISI marked complete all as specified and directed. Make: EKC / RAMA / CCOE
M&L for fabrication of mild steel flats iron clamp, angle iron, nut bolt and washer etc for supporting to CO2 gas pipe line including painting with one coat of synthetic enamel paint over a coat of red oxide primer complete all as specified and directed.
S&F in replacement of intrinsically safe and weather proof manual call point with push button fired bride box sealed with glass including necessary electrical connection complete all as specified and directed. Make: Agani / NSD / Agani Alarm / System Sensor
S&F in replacement of low intensity hooter for warning of fire connected with central contol panel installed in each zone inside the rooms complete all as specified and directed. Make: Agani / NSD / Agani Alarm / System Sensor
S&F in replacement Gun metal NRV 25 mm dia and fixing of NRV with MS pipe including cutting and welding work complete all as specified and directed. Make: KIRLOSKAR/SANT/LEADER/KARTAR/VENUS/UPADHYAY
S&F in replacement horn type stainless steel nozzle inner dia 15 mm, outer dia 20 mm and 65 mm long incuding fittings complete all as specified and directed.
S&F in replacement Single stage regulator (Two Gauge) Nitrogen Regulator complete with necessary connecting brass parts complete all as specified and directed. Make: ESAB india limited model INI 42B or other make as approved by GE
S&F in replacement of CO2 discharge indicator including fitting & accessories complete all as specified and directed. Make: Agani / NSD / Agani Alarm
S&F in replacement of CO2 release unit for manually operated with push button fired bride MS box duly painted sealed with glass including necessary electrical connection complete all as specified and directed. Make: Agani / NSD / Agani Alarm / System Sensor
M&L for power supply high current power supply that provides fire finder-XLS system with primary regulated 24 VDC, it should be rated at 12 A and built in charger & should be capable of charging up to 100AH batteries, should have microprocessor controlled transfer circuit, PSC-12 of Siemens complete all as specified and directed.
M&L for Programming Unit for programming and testing of Detector and devices of fire finders-XLS and wiring loops for ground faults and shorts circuits, communication of installed devices and addresses of all devices of Siemens complete all as specified and directed.
S&F in replacement of PCB loop cord suitable for self addressable fire finder system complete all as specified and directed. Make: Siemens/Honeywell/Agni
S&F in replacement optical type smoke detector, supply voltage 9 to 33 V DC, UL/FM/LPC approved with junction box and base to be fixed inside test rig with suitable fixing arrangement complete all as specified and directed. Make: Apollo/System Sensor/Siemens
S&F in replacement fixed cum ROR type heat detector class AIR supply voltage 9 to 33 VDC, UL/FM/LPC approved with base complete all as specified and directed. Make: Apollo /System Sensor/Siemens
S&F in replacement optical type Multisensor smoke with heat detector supply voltage 9 to 33 V DC, UL/FM/LPC approved with junction box and base to be fixed with suitable fixing arrangement complete all as specified and directed. Make: Apollo/System Sensor/Siemens
S&F in replacement of gun metal landing valve single headed 80 mm dia, flanged inlet 63 mm dia instant type female outlet with gun metal cap complete all as specified and directed. Make: G Tech/GEM/New Age/Flamex/ Omex
S&F in replacement of 63 mm dia RRL hose pipe 30.00 m long with instantaneous type gun metal 63 mm dia ISI marked male & female couplings bend riveted to hose pipe complete all as specified and directed. Make: New Age/Atasi/Omex
S&F in replacement of pneumatic actuator made of brass on CO2 cylinder ISI marked IS 3224 complete all as specified and directed. Make: KEW /Rotex or other make as approved by GE
S&F in replacement of electric solenoid operated actuator code 20126-1.2-2G-S8 DC 24 Volt 11 Watt type 6 Size II all as per IS 8935 for operating the value of nitrogen cylinder complete all as specified and directed. Make: Rotex / KEW or other make as approved by GE
S&F in replacement of wire braded high pressure discharge hose 3/8" WP 3024 PSI /210 BAR on CO2 cylinder complete all as specified and directed.
Supply and filling CO2 gas in fire extinguisher of different capacity including transportation for refilling from site to workshop on to & fro basis including testing of cylinder before filling the gas complete all as specified and directed.
Supply and filling N2 gas in fire extinguisher of different capacity including transportation for refilling from site to workshop on to & fro basis including testing of cylinder before filling the gas complete all as specified and directed.
S&F in replacement of low intensity hooter for warning of fire connected with central contol panel installed in each zone inside the rooms complete all as specified and directed. Make: Agani/NSD/Agani Alarm
Repair / Maintenance of Fire Zone panels / fire alarm panel in the 110 Block / ROH Flight by means of their cleaning, checking of circuits including recalibration to make the system serviceable complete all as specified and as directed. Note:- Spare parts measured and paid seperately under respective item of BOQ.
S&F in replacement of display card microprocessor based detecting system of CO2 flooding system for digital panel complete all as specified and directed.
S&F in replacement of zone card for digital panel complete all as specified and directed.
S&F in replacement of gas flooding control card of CO2 flooding system for digital panel complete all as specified and directed.
S&F in replacement of SMPS power supply including transformer of CO2 flooding system for digital panel complete all as specified and directed.
S&F in replacement of adaptor for N2 gas cylinder making all arrangement to arrest leakage of gas for digital panel complete all as directed.
S&F in replacement of lead acid battery of 12 Volt, 7 AH complete all as specified and directed. Make: EXIDE / OKAYA / AMRON /TATA
S&F in replacement of lead acid battery of 12 Volt, 32 AH complete all as specified and directed. Make: EXIDE /OKAYA / AMRON /TATA
S&F in replacement of lead acid battery of 12 Volt, 150 AH complete all as specified and directed. Make: EXIDE /OKAYA/AMRON/TATA
Repair, comprehensive and Preventive Maintenance of FIREALARM AND CO2 FLOODING SYSTEM 110 Block (22 Nos Rig each rig seprate zone panel, 83 Nos CO2 Cylinder and 22 Nos N2 Cylinder and 12 Zone Fire Alarm system conventional type) as per manufacturers reccomendation which include the following complete all as specified and directed:- (i) Checking and cleaning of smoke/ heat detectors ,nozzles /Co2 pipe line etc complete all as specified and directed. (ii) Checking of main control panel and control wiring complete all as specified and directed. (iii) Weighing of CO2 /N2 cylinders complete all as specified and directed. Note:- (a) If any defect noticed/found, the same should be rectify immediately and report to Engr-in-charge. (b) Spares shall be measured and paid separately under relavent item of BOQ. (c) If defect not rectified by contractor within stipulated period then penality @ 2500/per day will be recovered from RAR /BILL.
Repair, comprehensive and preventive maintenance of CO2 flooding system in ROH flight(one nos two zone panel, 8 Nos CO2 Cylinder and 01 Nos N2 Cylinder) as per manufacturers reccomendation which include the following complete all as specified and directed:- (i) Checking and cleaning of smoke/ heat detectors, nozzles/CO2 pipe line etc. (ii) Checking of main control panel and control wiring. (iii) Weighing of CO2 / N2 cylinders. Note:- (a) If any defect noticed/found, the same should be rectify immediately and report to Engr-in-charge. (b) Spares shall be measured and paid separately under relavent item of BOQ. (c) If defect not rectified by contractor within stipulated period then penality @ 2500/per day will be recovered from RAR /BILL.
Testing of CO2 flooding system in automatic and manual mode in Rigs of 110 Blocks/ROH flight by flooding of CO2 gas in rig and reinstalling filled CO2 gas cylinder, cleaning of smoke / heat detector and making system functional complete all as specified and directed.
S&F in replacement of Fire Extinguisher CO2 type 4.5 kg capacity Cylinder ISI marked IS : 15683 class 13 B type of fire fitted with PVC bend horn complete all as specified and directed. Make: Cease fire/Omex/Minimax
Supply, fix and installation in replacement ABC type fire extinguisher 9 kg capacity ISI marked confirming to IS 15683 with & discharge pipe etc as required complete all as specified and directed. Make: Cease fire/Omex/Minimax
Toping up / Refill and testing Dry chemical powder fire extinguisher ABC, 5 kg capacity ISI marked IS : 15683 with operating temp (+5) °C to (+55) °C for class 4 A type of fire filled wity MAP ABC Powder complete all as specified and directed. Make: Ceasefire /Omex/Minimax
Toping up / Refill and testing CO2 type fire extinguisher 4.5 kg capacity with squeeze grip valve operating temp (-30) °C to (55) °C for class 13 B type ISI marked confirming to IS : 15683 with PVC bend horn complete all as specified and directed. Make: Cease Fire /Omex/Minimax
Supply, fix and installation in replacement Mechenical Foam (AFFF) type fire extinguisher 9 litre capacity with ISI marked confirming to IS : 15683 etc complete all as specified and directed. Make: Cease Fire/Omex/Minimax
Repair and maintenance of automatic system of Fire pump house including replacement of control wiring, relay, contactor etc including replacement of minor parts to make functional and interlocking of jockey pump, main fire pump and fire engine pump set including testing complete all as specified and directed.
S&F in replacement of pressure switch universal type as per existing type complete all as specified and directed.
Supply and laying in replacement XLPE insulated PVC sheathed armoured copper conductor 1.5 Sqmm 2 core on surface with fitting complete all as specified and directed. Make: Fionlex/Plaza/Havells/Polycab
S&F in replacement PVC insulated, sheathed electric cable FRLS 1100V grade two core having multi stranded copper conductor of size 1.5 Sqmm nominal cross sectional area in non metallic rigid PVC concealed conduit complete all as specified and directed. Make: Fionlex/Plaza/Havells/Polycab
S&F in replacement PVC insulated FRLS type sheathed armoured copper conductor cable of size 1.5 Sqmm 2 core complete all as specified and directed. Make: Fionlex/Plaza/Havells/Polycab
Disconnecting the connection from prime mover including taking out of armature set of capacity 90 BHP from the existing position and strip opening, cutting the burnt out winding in feild coil, cleaning the stator and re-winding the same with super enameled copper winding wire of same gauge using top class of insulating material and over hauling of armature including lath / machine work for making housing of bearing, metaling, welding, turning surfacing, polishing of rotor shaft, and rethreading and replacement of bearing of required size (Make-NBC/SKF), bushes, rubber insertion sheet, nuts, bolts and washers including necessary other items for its smooth functioning and testing complete reassembling the same and re-fixing back in its original position complete all as specified and as directed.
S&F in replacement sluice valves 150 mm dia class PN-1.0, IS : 14846 with flanged ends, stainless steel spindle and iron wheel including nut bolts and rubber packing complete all as specified and directed. Make: Kirloskar / Upadhaya / GDPA / Kartar
All as per item No 60.00 above but 100mm dia.
Cleaning of semi under ground water sump of capacity 20000 Gallons approx inside by Mechanised de-watering by using industrial submersible pump, scrapping sludge and removal by using industrial sludge pumping, cleaning of all dust particle, sterilization of sump by using chlorination chemical on internal surfaces of wall including preperation of surfaces, writing date of cleaning of sump with white paint on black base complete all as specified and directed.
Repair and preventive maintenance of 55 KW centrifugal pump which include replacement of bearing, gland etc. and tightening of nuts bolts, washers greasing etc for proper running of pump and checking of all electrical connections from engine to panel and make it functional in manual/auto mode complete all as specified and directed. Note: Spare parts shall be measured and paid separately under respective item of BOQ.
Repair and preventive maintenance of Centrifugal fire pump 15 KW, which include replacement of bearing, gland etc. and tightening of nuts bolts, washers greasing etc for proper running of pump and checking of all electrical connections from engine to panel and make it functional in manual/auto mode complete all as specified and directed. Note: Spare parts shall be measured and paid separately under respective item of BOQ.
Supply only Bearing of centrifugal pump 55 KW exsisting size complete all as specified and directed. Make: SKF/Tata/NBC
Supply only Bearing of Centrifugal fire pump15 KW exsisting size complete all as specified and directed. Make: SKF/Tata/NBC
Supply only rubber bush for coupling complete all as specified and directed.
Supply only Gland bush set complete all as specified and directed.
Supply only Gland packing including nut & bolts suitable for 15/55 KW fire pump and engine set complete all as specified and directed.
Repair and preventive maintenance of fire diesel engine pump set 93BHP capacities which include tightening of battery terminals, checking of oil level, greasing, filling of distilled water in battery etc and any minor repair to make engine set functional complete all as specified and directed.
S&F in replacement Rubber hose pipe engine set 93 BHP complete all as specified and directed.
S&F in replacement Oil pressure pipe of Engine set 93 BHP complete all as specified and directed.
Supply and filling Coolant for radiator of any type of DG set complete all as specified and directed. Make: Castorl/Servo/HP
Supply only Lub Oil filter of engine set 93 BHP complete all as specified and directed. Make: Mico/Kirloskar/Fleet guard
Supply only Diesel filter of engine set 93 BHP complete all as specified and directed. Make: Mico /Kirloskar/Fleet guard
Repair and overhauling and servicing of self starter 12 V by replacement of clutch, carbon bush etc complete all as specified and directed.
Supply and filling of Engine oil 20W40 complete all as specified and directed. Make: Castrol/Servo/HP
S&F in replacement of battery 12 volts 180AH including battery terminals complete all as specified and directed. Make: Exide/Amron/SF/Tata
S&F in replacement MS ERW pipe 200 mm bore class C heavy duty including cutting and welding, fittings for fire pipe line in pump house complete all as specified and directed. Make: Jindal / TATA / PRAKASH SURYA
All as per item No. 79.00 above but pipe size 100 mm.
All as per item No. 79.00 above but pipe size 80 mm.
All as per item No. 79.00 above but pipe size 65 mm.
All as per item No. 79.00 above but pipe size 40 mm.
All as per item No. 79.00 above but pipe size 25 mm.
M&L for two coats painting of plant MS platform angle/pipe/channel support MS tank from out side cable tray and other related surface using Synthetic enamel paint of existing colour including removing rust/dust and oil from surface and writing letters etc complete all as specified and directed.
Prime Technology
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .