| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.7 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹18.7 L+₹4.0 L (27.4%)Rejected-Finance | L2 | Rejected-Finance Other than lowest |
Tender Value
₹19 L
EMD Value
₹38,000
Closing Date
3 Oct 2022, 6:00 pmClosed
GE(I) 873 EWS
Garrison Engineer (Indep) 873 Engineer Works Section PIN 913 873 C/O 56 APO
PROVN OF REPAIR/REPLACEMENT OF UG CABLES AND PROVN OF 13 EXHAUST FAN AT KISHTWAR UNDER GE (I) 873 EWS
2022_MES_549965_1
NIT-50 of 22-23
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Bhaderwah
As per NIT
7 documents required · 7 mandatory
₹500
GE(I) 873 EWS
₹38,000
Yes
11 Oct 2022
5 Sept 2022
6 Oct 2022
5 Sept 2022
3 Oct 2022
19 Sept 2022
Amount
Excavating in trenches, not exceeding 1.5metre wide and not exceeding 1.5metre depth for foundation, etc., and getting out in any type of soil, complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25 cm thick any type of soil, complete all as specified and directed.
Removing excavated soils to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
Sand cushioning to underground cables using new dry river sand laid in trenches 8cm thick below the cable and 15cm thick above the cable after laying and stretching the cable complete, punned to 18cm, complete all as specified and directed Note : Punned thickness of 18cms shall be measured for payment.
Supply and laying brick covering with width equal to length of bricks as mechanical protection to underground cable using old size sub class 'B' bricks, laid flat size 230mm x 115mm x 75 mm with width of brick perpendicular to length of cable, all as specified and as directed.
Steel pipe galvanised light grade, 80 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
Steel pipe galvanised light grade, 50 mm bore laid in trenches or under ground/floor or road of fixed with pole for protection of cable including GI clamps with bolts nuts and washers complete all as specified and directed.
Demolition of cement concrete in ground floors and paving not exceeding 15cm thickness (below or above ground level) un-reinforced, complete all as specified.
Cement concrete type B-2 1:2:4 (using 40mm graded crushed stone aggregate) as in foundation filling and mass concrete, paving, hardstanding, road, complete all as specified and directed.
Cross arm bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, drilling holes for bolts, in any shape or size as indicated or directed and also inclusive of two coats of aluminium paint over one coat of red oxide primer all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 2 core fixed with suitable thimble and gland laid in trenches, under floors or on poles including taking down old cable, complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 16 Sqmm 4 core fixed with suitable thimble and gland laid in trenches, under floors or on poles including taking down old cable, complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 35 Sqmm 3.5 core fixed with suitable thimble and gland laid in trenches, under floors or on poles, complete all as specified and as directed.
XLPE insulated armoured heavy duty electric cable with aluminium conductor 1100 volts grade ISI marked cross sectional area 50 Sqmm 3.5 core fixed with suitable thimble and gland laid in trenches, under floors or on poles, complete all as specified and as directed.
Point wiring with 1.5 Sqmm, multistrand, FRLS copper conductor cable, PVC insulated and unsheathed, drawing in and including PVC casing-N-caping of appropriate size (having wall thickness not less than 0.90mm), surface type, for one light point controlled by one, one way switch, terminated in terminated in cast iron or pressed steel terminal boxes appropriate size, covered with 3mm thick plastic laminated sheet top cover for mounting switches, sockets, regulators etc. and continuous PVC insulated and unsheathed 1.5 Sqmm copper conductor cable multistrand as earth wire, complete all as specified.
Point wiring with 2.5 Sqmm, multistrand, FRLS copper conductor cable, PVC insulated and unsheathed, drawing in and including PVC casing-N-caping of appropriate size (having wall thickness not less than 0.90mm), surface type, for one light point controlled by one, one way switch, terminated in terminated in cast iron or pressed steel terminal boxes appropriate size, covered with 3mm thick plastic laminated sheet top cover for mounting switches, sockets, regulators etc. and continuous PVC insulated and unsheathed 2.5 Sqmm copper conductor cable multistrand as earth wire, complete all as specified.
Switch piano flush button 5 Amp single pole, one way, complete all as specified.
Switch piano flush button 15 Amp single pole, one way, complete all as specified.
Ceiling rose surface type, bakelite 65mmx50mm, 3 terminals, complete all as specified.
Stepped type electronic fan regulator flush type, complete all as specified.
Ceiling fan of size 1200mm sweep, five star rating, 230 volts (single phase) including provisioning of three core flexiable copper cord of size 23/0.0076 of required length from ceiling rose or connector to ceiling fan for connection, complete all as specified & directed. Make: Crompton/Bajaj/Havells/Usha
Exhaust fan metallic body with louvers of size 300mm sweep, 900 RPM, 230 volts (single phase) complete with bolts, nuts & washers, embedded in the wall, including provisioning of three core flexiable copper cord of size 23/0.0076 of required length from ceiling rose or connector to Exhaust fan for connection with and including cutting holes throuh walls and making good the surface as per existing, complete all as specified & directed. Make: Crompton/Bajaj/Havells/Usha
Exhaust fan metallic body with louvers of size 250mm sweep, 900 RPM, 230 volts (single phase) complete with bolts, nuts & washers, embedded in the wall, including provisioning of three core flexiable copper cord of size 23/0.0076 of required length from ceiling rose or connector to Exhaust fan for connection with and including cutting holes throuh walls and making good the surface as per existing, complete all as specified & directed. Make: Crompton/Bajaj/Havells/Usha
Sub main wiring with 4 Sqmm multi strand copper conductor two single core cable PVC insulated and unsheathed drawing into in and including PVC surface conduit of appropriate size (having wall thickness not less than 1.80mm) with 2.5 Sqmm PVC insulated and unsheathed copper conductor cable as continuous earth wire, complete all as specified. Note: Two run of 4sqmm wire, one run of 2.5sqmm wire ans 1 run of PVC conduit shall be measured as one unit length.
Sub main wiring with 6 Sqmm multi strand copper conductor two single core cable PVC insulated and unsheathed drawing into in and including PVC surface conduit of appropriate size (having wall thickness not less than 1.80mm) with 4 Sqmm PVC insulated and unsheathed copper conductor cable as continuous earth wire, complete all as specified. Note: Two run of 6sqmm wire, one run of 4sqmm wire ans 1 run of PVC conduit shall be measured as one unit length.
Sheet metal enclosures for DB’s, single door, (when MCBs are to be used) single pole and neutral 4 way, 240 volts with 200 Amp rated bus bar, complete all as specified.
Sheet metal enclosures for DB’s, single door, (when MCBs are to be used) single pole and neutral 6 way, 240 volts with 200 Amp rated bus bar, complete all as specified.
Sheet metal enclosures for DB’s, single door, (when MCBs are to be used) single pole and neutral 8 way, 240 volts with 200 Amp rated bus bar, complete all as specified.
Isolator, triple pole and neutral, 63 Amp, 415 Volt, complete all as specified.
MCB, single pole and neutral, 20 to 32 Amp, 10 KA, 240 Volt, complete all as specified.
MCB, single pole and neutral, 40 to 63 Amp, 10 KA, 240 Volt, complete all as specified.
MCB, single pole, 63 Amp, 10 KA, 240 Volt, complete all as specified.
MCB, single pole, 6 to 32 Amp, 10 KA, 240 Volt, complete all as specified.
Earthing complete with galvanized mild steel earth plate electrode size 600mm x 600mm x 6mm thick buried directly in ground (preferably in vertical position) earth pit not less than 2.25 meter below normal ground level with top edge of the earth plate not less 1.5 meter (BGL) connected to galvanized iron earth lead wire 4mm dia by means of bolts, nuts, check nut and washer of galvanized iron including PCC pit in RCC 1:2:4 type B-1, precast RCC cover with suitable handle, excavation and earth work in any type of soil, 20mm bore “medium grade” galvanized iron water tubing fixed with cast iron funnel and wire mesh and 15mm bore “light grade” galvanized iron protection pipe for earth lead wire upto 5m length, charcoal, common salt, complete all as shown in EP No 3 of SSR 2009 Part-I, connected to test point complete, all as specified and testing on completion.
Earthing complete with GI earth plate electrode of size 600mm x 600mm x 6mm thick buried directly to ground vertically to a depth not less than 2.25 Mtr below the ground level with top edge of earth plate not less than 1.65 Mtr below normal ground level connected to GI strip 32 x 6 mm size and earthing lead protected with 50 mm bore GI pipe, light grade, filling around with charcoal dust and salt including excavation, returning, filling of earth and disposal of surplus soil to a distance not exceeding 50 mtr and connected to GI strip by means of GI nuts, bolts and washers strip connected to earth plate including chamber PCC 1:3:6 type C-1 using 20mm graded crushed stone aggregate in concrete pit pre-cast RCC 40 mm thick reinforced with 6 mm dia round at 75 mm C/C both way with 12 mm dia mild steel plain bar lifting handle 2 Nos funnel with wire mesh 20 mm dia GI pipe light grade watering pipe and frame work complete all as shown in electrical plate No. 3 of SSR Part-I 2009 including testing on completion complete all as specified and as directed.
Supplying, installing, designing, testing and commissioning of LT Outdoor type Panel Board, Factory made, (Cubical Kiosk type), weather, dust and vermin proof IP-65, CPRI approved with locking arrangement made out of CRCA sheet 3.15 mm thick with suitable size of channel for base complete with aluminium bus bar of 100 Amps rated with cable gland of suitable size and in adequate Nos, cabinet for housing mounting switch, disconnection fuse unit, metering equipments, prewired with suitable size of copper conductor and duly powder coated in Siemens grey colour mounted on PCC platform of PCC 1:2:4 type B-1 on angle iron frame which is made out of 50 x 50 x 6mm thick angle iron duly marked the incoming outgoing controls, complete all as specified and directed and comprising of the following :-
(i) Incoming (a) MCCB 100 Amps, breaking capacity 25 KA, FP, 415V (Adjustable Thermal and Magnetic setting) - 01 No (ii) Outgoing (a) MCCB 63 Amps, breaking capacity 25 KA, TP, 415V (Adjustable Thermal and Magnetic setting)- 04 Nos (b) Front operated onload change over switch, TP, 125 Amps- 01 No (c) Timer switch 3 Phase 415 volts, 40Amp rating, programmable time switch 24 hrs 4128 12-Analogue type 24 hrs, time switches, 500h working reserve possible, 3 pole power contactors 40 A- 01 No (d) Three Phase Digital Voltmeter 0-500 Volts with suitable size of CTc- 01 No (e) Three Phase Digital Ammeter 0-100 Amps with suitable size of CTc- 01 No (f) LED pilot lamp RYB (Set of three)-01 No
(g) Complete control panel wiring with suitable size stranded copper conductor Make of Panel : DV Electromatics Private Limited / Simon Fabricators / Electricfield Co / Adhunik Switchgear / Universal Switchgear Make of MCCB : L&T / Legrand / Schneider / Havells Make of Change over switch : L&T / Legrand / Schneider / Havells Make of Timer switch : Legrand / ABB / Havells Make of Voltmeter / Ammeter / Multifunction Meter : SECURE / L&T (RISHAB) / C&S ELECTRIC / MECO
M/S Builders Indias
Bidder Name
SWASTIK TRADERS
M/S Builders Indias
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .