Loading…
Loading…
Tender ID
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.5 LAccepted-AOC | L1 | Accepted-AOC Lowest bidder | |
| 2 | L2₹14.6 L+₹10,929 (0.75%)Rejected-Finance | L2 | Rejected-Finance Other than L1 | |
| 3 | L3₹15.2 L+₹75,122 (5.18%)Rejected-Finance HYDERPORA NEAR ELLAQUAI DEHATI BANK SRINAGAR KASHMIR J K 190014 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190014 | L3 | Rejected-Finance Other than L1 | |
| 4 | L4₹16.3 L+₹1.8 L (12.1%)Rejected-Finance | L4 | Rejected-Finance Other than L1 |
| Sl No | Description | Qty | Unit | CHINAR CONSTRUCTION TRADERS L1 | M/S M.A.S ELECTRICALS L2 | M/S ZAHOOR AHMAD KHAN L3 | M/S NEW ROYAL CONSTRUCTION CO L4 |
|---|---|---|---|---|---|---|---|
| 1.00 | Supply, installation, testing and commissioning of 58.5 KVA liquid cooled silent diesel engine driven generating set water cooled Diesel Engine Model 4R810ETA 4G1 (CPCB-IV+) Norms compliance Developing 74 BHP @ 1500 RPM & 58.5 KVA 3 phase, 415 Volts, 50 hz 0.8 power factor @ 1500 RPM at an altitude of 6835 feet above MSL with integrated control panel having meters, and sound proof canopy as per CPCB-IV+ norms of approved make as per OEM and with necessary foundation as recommended by OEM, mounted on common base plate with flexible coupling with and including accoustic insulated chamber to maintain noise level as per CPCB-IV+ norms complete inbuilt with all accessories and totally enclosed type with silencer pipe protected with asbestos rope from engine to outside the building, 1.0 mtr and independently supported AVM pads, battery starter type, DG set should be capable of operating in temperature range (-)15˚ to (+)40˚ Celcius with and including the following :-
NOTE :-
(a) AMF Panel (cost deemed to be included).
(b) Cost of foundation of DG set as per manufacturer's size and specifications shall be deemed to be included in quoted rates.
(A) Diesel Driven Engine :- Vertical diesel engine of suitable capacity 58.5 KVA, water cooled type closed, circuit as per BS-649 or IS-10002, direct injection type turbo charged, battery starting system having rated speed 1500 RPM. The DG set shall be capable of running 24 hours continuously with 10% over loading for one hour in every 12 hours run as per BS-5514/BS-649. Engine shall be equipped with all standard fittings as per manufacturer's recommendation & mounted common plate through flexible coupling with following fittings :-
(a) RPM cum hour meter.
(b) Battery charging ammeter.
(c) Ignition key and starting with button switch.
(d) Lubricating oil pressure gauge.
(e) Mechanical/ electirc governor controlling.
(f) Oil temperature gauge.
(g) Safety control with tripping facility for the following :-
(i) Low lubricant oil pressure.
(ii) Over speed.
(iii) High water temperature.
(h) Starting equipment comprising of following :-
(i) Battery as per manufacturer's recommendation.
(ii) Battery, charging alternator with inbuilt regulator
(iii) Battery leads of copper cable of suitable size brass thimbles and terminals. | 1 | Each | 10,00,000 ₹10,00,000 | 8,99,999 ₹8,99,999 Lowest | 11,00,000 ₹11,00,000 | 10,60,000 ₹10,60,000 |
| 1.01(B) Alternator :- Alternator's rating 58.5 KVA, 3 phase, 50 cycle, 415 volts, 4 wire supply at NTP 0.80 power factor, running @ 1500 RPM self excited, self regulated, mounted on strong steel fabricated steel suitable for mounting on a permanent foundation to be coupled with above engine. The alternator shall be conforming to BS-2613 OR IS 4722. (C) Control Panel :- Alternator control panel inbuilt with internal copper wiring for 58.5 KVA alternator, 415 volts, 3 phase, 4 wire, 50 cycle, fabricated out of 2.0mm thick MS sheet painted externally and internally with two coats of synthetic enamel paint over one coat of primer all as per manufacturer's design including provision of following accessories :- (i) Suitable scaled flush mounted AC voltmeter with selector switch 0-500 volts - 01 Set. (ii) Suitable scaled flush mounted ammeter with selector switch & CT's of suitable range - 01 Set. (iii) Frequency meter - 01 No. (iv) KW and KWH meter. (v) Power factor meter - 01 No. (vi) MCCB 4 pole of suitable capacity - 01 No. (for incoming) as recommended by manufacturer. (D) Other fitting (E) AMF Panel (i) Battery charger - Battery charger having electric circuit consisting of triodes, rectifier, capacitor and resistance etc. The battery charger should be able to charge the battery at all the time whenever electric supply given to battery charges through control panel or electric power point. (ii) Fuel tank made up of MS Sheet of suitable capacity as per manufacturer's instructions capable to store fuel for 12 hours running of DG set fixed as per manufacturer's design and return fuel pipe with all pipes connecting upto fuel pump including oil level indicating gauge, drain plug for cleaning and air vent plug etc. (iii) Accousite enclosure with natural air circulation without loss of any power for ventilation fan. The enclosure shall be modular in construction with hinge bolted structure to provide easy dismantling and shall be made out of high quality CRCA sheet steel of 1.6mm thick with sufficient accessories for maint work, open able and lockable door with air light rubber gasket, interior lighting arrangment. | |||||||
| 2.00 | Supply, laying, commissioning, testing of XLPE underground LT cable 1100 volts grade of size 95Sqmm 3.5 core armoured, PVC sheathed with aluminium conductor heavy duty laid in trenches, fixing on wall, under road crossing through protection pipe etc complete all as specified and directed. | 278 | RM | 800 ₹2,22,400 | 725 ₹2,01,550 | 710 ₹1,97,380 Lowest | 800 ₹2,22,400 |
| 3.00 | Excavation in trenches n exc 1.5m wide and n exc 1.5m deep for foundation of poles/ stay/ cable etc including getting out in any type of soil complete all as specified and directed. | 28.8 | Cum | 150 ₹4,320 | 275 ₹7,920 | 100 ₹2,880 Lowest | 200 ₹5,760 |
| 4.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n exc 25cm complete all as speicified and directed. | 16.06 | Cum | 60 ₹963.6 Lowest | 100 ₹1,606 | 100 ₹1,606 | 200 ₹3,212 |
| 5.00 | Removing surplus excavated material to a distance n exc 50m and depositing where directed at a level n exc 1.5m above the starting point complete all as specified and directed | 12.74 | Cum | 60 ₹764.4 | 50 ₹637 Lowest | 100 ₹1,274 | 200 ₹2,548 |
| 6.00 | Sand cushioning to cable with dry fine sand in trenches 8cm below the cable and 15cm above the cable after laying complete all as specified and directed.
NOTE :- Punned thickness shall be measured for payment purposes. | 10.82 | Cum | 800 ₹8,656 Lowest | 1,050 ₹11,361 | 800 ₹8,656 Lowest | 2,500 ₹27,050 |
| 7.00 | Bricks laid in trenches flat with width equal to length of brick for cable protection well burnt sub class 'B' laid across the cable complete all as specified and directed. | 1.39 | Per 1000 Nos | 8,000 ₹11,120 | 11,000 ₹15,290 | 5,000 ₹6,950 Lowest | 7,000 ₹9,730 |
| 8.00 | Supply, laying, jointing and testing in trenches, 100mm glavanised iron water tubing medium grade (ISI marked) including provision of all necessary steel fittings/ accessories complete all as specified and directed. | 12 | RM | 550 ₹6,600 | 2,200 ₹26,400 | 350 ₹4,200 Lowest | 550 ₹6,600 |
| 9.00 | Supply, fixing, testing and commissioning of CPRI approved LT distribution panel outdoor type of size minimum 100 x 80 x 160cm (length x width x height) or larger suitabl size weather/ vermin proof, made out of 3.15mm thick CRCA sheet duly powder coated, mounted on 65 x 65 x 6mm (ISA6565) iron angles frame of height 45cm from PCC bedding, factory assembled compartmentalised construction, free standing type, including 3 phase and neutral 400 amps current carrying capacity copper bus bas with epoxy insulated coating with colour code and insulated support, cable galleries inter connecting bus bar connection/ linkage complete and conforming to IS 8623 and IP 54 class of protection as per IS 2147 complete, including making connection of cables of incoming and outgoing with thimble/ lugs, including the accessories as below complete and mounting thr panel on ground/ floor with PCC (1:3:6) bedding upto a height of 30cm above ground level complete all as specified and directed.
(a) Copper bus bar 400 amps for 3 phase & neutral - 01 Set.
(b) MCCB 4 pole 250 amps 35 KA at 415 v - 01 No (incoming).
(c) MCCB 4 pole 100 amps 25 KA at 415 v - 01 No (outgoing).
(d) MCCB 4 pole 63 amps 25 KA at 415 v - 02 Nos (outgoing).
(e) MCCB 4 pole 32 amps 25 KA at 415 v - 03 Nos (outgoing).
(f) Digital voltmeter with selector switch 0 to 500 volts - 01 No.
(g) Digital ammeter with selector switch suitable size CTs - 01 No.
(h) LED type indicator lamps (R<Y<B) - 01 set | 1 | Each Job | 1,50,000 ₹1,50,000 | 2,45,000 ₹2,45,000 | 1,18,000 ₹1,18,000 Lowest | 1,70,000 ₹1,70,000 |
Tender Value
₹14.6 L
EMD Value
₹29,120
Closing Date
9 Oct 2025, 6:00 pmClosed
Eligibility, documents, scope and key termsEligibility, required documents, scope of work and key terms of this tender, in one click.
Cdr, HQ 134 Wks Engrs
HQ 134 WE C/o 56 APO PIN-914134
Provision of 1 x 58.5 KVA Generator Set with automatic panel under revenue works at drang under GE 861 EWS
2025_MES_728464_1
134 WE-63(T)/2025-26
Open Tender
Civil Works - Others
Item Rate
180 days
GE 861 EWS
As per tender documents
8 documents required · 8 mandatory
₹500
GE 861 EWS
₹29,120
2 Nov 2025
29 Aug 2025
13 Oct 2025
29 Aug 2025
9 Oct 2025
20 Sept 2025
29 Aug 2025 - 5 Sept 2025
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .