CE TMC
Engineering Dept Service Block 6th Floor TMH Parel Mumbai
To provide the facility of CSSD (Central Sterile Supply Department) in RT Block 1st floor involving civil mechanical and electrical works at HBCH Sangrur
2023_TMC_778344_1
CSSD Sangrur
Open Tender
Civil Works
Works
75 days
HBCH Sangrur
Please refer Tender documents.
6 documents required · 6 mandatory
₹0
₹67,283
HBCHRC MULLANPUR
22 Dec 2023
27 Oct 2023
24 Nov 2023
27 Oct 2023
22 Nov 2023
6 Nov 2023
3 Nov 2023
Amount
Dismantling tile work in floors and roofs laid in cement mortar including For thickness of tiles 10 mm to 25 mm (15.23.1)
Dismantling aluminium/ Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable material and stacking of serviceable material with in 50 meters lead as directedby Engineer-in-charge (15.57)
Demolishing brick work manually/ by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-charge In cement mortar (15.7.4)
Half brick masonry with common burnt clay F.P.S. (non modular) bricksof class designation 7.5 in superstructure above plinth level up to floor V level (6.13.2)
Extra for providing and placing in position 2 Nos 6mm dia. M.S. bars at every third course of half brick masonry (6.15)
12 mm cement plaster: 1:4 (1 cement : 4 fine sand) ( 13.1.1.)
20 mm cement plaster 1:4 (1 cement : 4 fine sand) ( 13.3.1.)
Aluminium Gates Fixed Portion (21.1.1.2)
For Shutters Door Window (21.1.2.2)
P/F 12mm thick Prelaminated particle board (21.2.1)
Removing White Or Color Wash By Scrapping And Sand Papering and preparing the surface smooth (13.88)
Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete.
Distempering with 1st quality acrylic distemper, having VOC (VolatileOrganic Compound ) content less than 50 grams/ litre, of approvedbrand and manufacture, including applying additional coats whereverrequired, to achieve even shade and colour Two coats (13.81.2
1:2:4 (1 cement : 2 coarse sand (zone-III) derived from natural sources : 4 graded stone aggregate 20 mm nominal size derived from natural sources)
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand),jointing with grey cement slurry @ 3.3 kg/ sqm including grouting the joints with white cement and matching pigments etc., complete Size of Tile 600x600 mm 11.41.2
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. 8.31
Providing and fixing G.I. pipes complete with G.I. fittings and clamps i/c cutting and making good the walls etc.50 mm dia nominal bore 18.10.6
Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.
25 mm nominal dia
32mm nominal dia
40 mm nominal Dia
Providing and fixing double scaffolding system (cup lock type) on the exterior side of building/structure, upto 25 metre height, above ground level, including additional rows of scaffolding in stepped manner as per requirement of site, made with 40mm dia M.S. tube, placed 1.5 metre centre to centre, horizontal & vertical tubes joint with cup & lock system with M.S. Tubes, M.S. tube challis, M.S. clamps and staircase system in the scaffolding for working platform etc. and maintaining it in a serviceable condition for execution of work of cleaning and/ or pointing and/ or applying chemical and removing it thereafter. The scaffolding system shall be stiffened with bracings, runners, connecting with the building etc, wherever required, if feasible, for inspection of work at required locations with essential safety features for the workmen etc., complete as per directions and approval of Engineer-in-charge. Note:- (1) The elevational area of the scaffolding shall be measured for payment purpose. (2) The payment will be made once only for execution of all items for such works. (24.3)
Steel reinforcement for R.C.C. work including straightening, cutting,bending, placing in position and binding all complete above plinth level.Cold twisted bars 5.22A 3
Centering and shuttering including strutting, propping etc. and removal of form for Lintels, beams, plinth beams, girders, bressumers and cantilever 5.9.5
Reinforced cement concrete work in beams, suspended floors, roofs having slope up to 15° landings, balconies, shelves, chajjas, lintels, bands, plain window sills, staircases and spiral stair cases above plinth level up to floor five level, excluding the cost of centering, shuttering, finishing and reinforcement with 1:1.5:3 (1 cement : 1.5 coarse sand(zone-III) derived from natural sources : 3 graded stone aggregate 20 mm nominal size derived from natural sources). 5.3
Earth work in excavation by mechanical means (Hydraulic excavator)/manual means over areas (exceeding 30 cm in depth, 1.5 m in width as well as 10 sqm on plan) including getting out and disposal of excavated earth lead upto 50 m and lift upto 1.5 m, as directed by Engineer-in-charge. 2.6
Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead up to 50 m and lift upto 1.5 m.
1:4:8 (1 Cement : 4 coarse sand (zone-III) derived from natural sources : 8 graded stone aggregate 40 mm nominal size derived from natural sources) 4.1.8
Concrete of M25 grade with minimum cement content of 300 kg /cum 4.20.2.4
Centering and shuttering including strutting, propping etc. and removal of Suspended floors, roofs, landings, balconies and access platform 5.9.3
Brick work with common burnt clay machine moulded perforated bricks of class designation 12.5 conforming to IS: 2222 in superstructure above plinth level up to floor five level in cement mortar 1:6 (1 cement : 6 coarse sand) : With Modular bricks 6.3.2
Providing and laying Vitrified tiles in floor in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS:15622, of approved brand & manufacturer, in all colours and shade, laid on 20 mm thick cement mortar 1:4 (1 cement: 4 coarse sand) jointing with grey cement slurry @3.3 kg/sqm including grouting the joints with white cement and matching pigments etc. The tiles must be cut with the zero chipping diamond cutter only . Laying of tiles will be done with the notch trowel, plier, wedge, clips of required thickness, leveling system and rubber mallet for placing the tiles gently and easily. Double charge vitrified tile polished finish of size Size of Tile 600 x 600 mm 11.41A.1.1
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement slurry mixed with pigment to match the shade of the slab,including rubbing and polishing complete with base of cement mortar 1 : 4 (cement : 4 coarse sand) : 25 mm thick 11.26.1
Providing and fixing on wall face unplasticised Rigid PVC rain water pipes conforming to IS : 13592 Type A, including jointing with seal ring conforming to IS : 5382, leaving 10 mm gap for thermal expansion, (i) Single socketed pipes 110 mm dia 12.41.2
Providing reinforced by organic fibres and/or inorganic synthetic fibres cement 6 mm thick corrugated sheets (as per IS: 14871) roofing up to any pitch and fixing with polymer coated J, or L hooks, bolts and nuts 8 mm dia. G.I. plain and bitumen washers or with self drilling fastener and EPDM washers etc. complete (excluding the cost of purlins, rafters and trusses), including cutting sheets to size and shape wherever required
Supply, laying and erection of aluminium conductor XLPE insulated PVC sheathed armoured and served cable 1100 volts grade as per IS:7098 (Part-1)1988 to be laid (On Surface) as per PWD General Specifications:-
Overall size 120sq.mm (3½ Core) Armoured (On-Surface)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. Make: COMMET/ BELIGA/PEECO/GRIPWELL/DOWELLS 3½ X 120 sq. mm (45mm)
Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubical type) in the existing Cubical Panel (confirm to IEC:60947-2) having Ics=100% Icu, 100% neutral with spreader terminal links, Extended rotary handle and relevant PWD general specifications complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with suitable size of thimbles etc:- MCCB Four Pole 250amp., 415volts, ≥25kA Fixed Magnetic and Adjustable Thermal Setting
FRLS insulated single core unsheathed enameled copper conductor 95 sqmm
Supply and erection of heavy duty Copper thimbles/lugs for cable end termination duly crimped including making necessary connections etc. in existing bus bar pannel completely:- Copper thimble cable Core size 95sq.mm
Supply and erection of sheet metal double door vertical distribution boards IP 43-IK09 metal door (dust protected) as per IS:8623-1&3, IEC 61439-1&3 suitable for flush mounting with fully insulated copper busbars for each phase, 2 Nos. shrouded neutral bars, 2Nos. earth bars, cement spill protector, color-coded interconnecting wire set, cable ties, blanking plates and circuit identifications label and of required no. of ways for mounting MCCB's as incomer and outgoings SP/TP miniature circuit breakers in the distribution board as per PWD General specifications including connections with suitable size of thimbles and bonding to existing earth etc.:- Make: L&T/Schneider/ABB/Legrand TP&N Double Door Vertical DB's 12 way each (With provision of FP MCCB 200- 250amp.) (Incomer)
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. (Outgoing) Make: L&T/Schneider/ABB/Legrand
Single pole and neutral 20A a. Plasma sterilizer - 1-Ф, 3kW b. Drying Cabinet - 1-Ф, 1kW c. Spare
Single pole and neutral 40A a. Plasma sterilizer - 1-Ф, 5kW b. Drying Cabinet - 1-Ф, 6kW c. Spare
Triple pole and neutral 32A a. Washer disinfector - 3-Ф, 9kW b. Spare
Supply and erection of Miniature Circuit Breaker MCB's for circuit protection against overload and short circuit current fault suitable for 240/ 415 volts 50cycles AC supply with breaking capacity of 10kA, Curve-C and low watt losses as per IS/IEC 60898-1, energy limitation class-3, true contact indication, label holder facility in the existing MCB distribution board as per PWD General Specifications including connections with suitable size of thimbles/lugs:- Make: L&T/Schneider/ABB/Legrand
MCB Four Pole 63amp. (10kA, Curve-C) a. Auto Clave - 3-Ф, 27kW b. Spare c. Power Load (ACs / Exhaust / Powerpoints) d) Air Comprassor
Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray cable tray with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc as required.
300 mm width X 50 mm depth X 1.6 mm thickness
Supplying and fixing DP sheet steel enclosure on surface/ recess along with following rating 240 volts “C” curve DP MCB complete with connections, testing and commissioning etc. as required. (Equipment Side) Make: L&T/Schneider/ABB/Legrand
20A SPN a. Ultrasonic cleaner - 1-Ф, 3kW b. Sealing Machine - 1-Ф, 1kW
32A SPN a. Plasma sterilizer - 1-Ф, 5kW b. Drying Cabinet - 1-Ф, 6kW
Supplying and fixing TP sheet steel enclosure on surface/ recess along with following rating 415 volts “C” curve TP MCB complete with connections, testing and commissioning etc. as required. Make: L&T/Schneider/ABB/Legrand
32A TPN for Washer disinfector - 3-Ф, 9kW
63A TPN for Auto Clave - 3-Ф, 27kW
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
4c X 10 sq. mm Annealed Copper Cable (For Washer Disinfector, Auto Clave or Air Compressor)
4 X 4 sq. mm + 2 X 4 sq. mm earth wire for Power Points & ACs
2 X 6 sq. mm + 1 X 6 sq. mm earth wire for Other equipment
2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire for Lighting circuit
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recesse medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.
Group C (Primary Point)
Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc as required.
Group C (Secondary Point)
Supplying and fixing suitable size GI box with modular plate and cover in FRLSont on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required. (3Module for Power Points) Make: Panasonic/Legrand/Goldmedal/Havells/L&T
Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required (For UPS Points)
5/6 amps switch
3 pin 5/6 amp socket outlet
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.
6 Module (200mmX75mm)
Recessed mounted LED Light 36W (600mm x600mm). Make: Wipro/Crompton/Surya/Philips
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.
Providing and fixing 25 mm X 5 mm copper strip in 40 mm dia G.I. pipe from earth electrode including connection with brass nut, bolt, spring, washer excavation and re-filling etc. as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed steel/ PVC conduit as required.
2 run of Cable
Supplying and drawing following pair 0.5 mm dia FRLS PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.
SITC of RJ-45 Socket outlet alongwith the backbox, faceplate and all other required accessories.
SITC of RJ-11 Socket outlet alongwith the backbox, faceplate and all other required accessories.
SITC of 5 HP oil free reciprocating air compressor (Make Anesta iwata)
SITC of Air receiver (500 ltr)
SITC of air Dryer
SITC of filteration system
SITC of auto drain valve system
SITC of filter regulator system
Isolation valve (make RN/Pax)
SITC Medical grade copper pipe 15mm ( Make Mexflow)
Medical grade copper pipe 12mm ( Make Mexflow)
Outlet connection ( nut ,nipple)
SITC Inline fan with single skin cabinet for exhaust 1000cfm( Carrier nicotra)
SITC Inline fan with single skin cabinet for supply fresh air 750 cfm ( Carrier nicotra)
SITC Inline fan with single skin cabinet for exhaust 1000 cfm ( Carrier nicotra)
24 g ducting sheet
Bird screen with gravity louver
SITC of Grill (600 x 600 mm ) with control damper
SITC of 3 core(2.5 mm) copper cable
SITC MCB with wheather proof box 6amp
dogging pump
SS Chamber with all fittings
SLIDER Approx
Designing of MGPS Rooms And Drawings 5% of MGPS Rooms Cost
Rattan Builders pvt Ltd
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .