Loading…
Loading…
Tender Value
₹20.9 L
EMD Value
₹41,877
Closing Date
25 Aug 2026, 3:00 pm2d left
Executive Engineer (E)
EEE PWD DHC and ND/Central G.F. MSO Bldg. ND
RMO E, M Services installed at Trade , Tax Building ITO, Delhi-110002 (SH- SITC of precision type air conditioner in UPS room.)
2026_PWD_297013_1
104/EE(E)/PWDDHC,ND/C/2026-27
Open Tender
Electrical Works
Works
30 days
New Delhi1
Please refer Tender documents.
16 documents required · 16 mandatory
₹0
₹41,877
25 Aug 2026
14 Aug 2026
25 Aug 2026
14 Aug 2026
25 Aug 2026
14 Aug 2026
This is a percentage-rate BOQ. The schedule below shows estimated quantities and rates. Bidders quote a single percentage above or below the total estimated cost.
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 1 | SITC of floor mounted high performance precision packaged cooling units suitable for high sensible loads of electrical panels. Each unit shall facilitate installation in Small Areas, shall feature robust design to run 24x7, Auto-Restart function, Monitoring with Unit-to-Unit Communication and Ease of service. The discharge of cold air shall be from top front and suction from lower front face.
The Indoor unit shall comprise of Metallic Body construction, Scroll compressor, Evaporator Coil with Hydrophilic Coating, Evaporator fans, HDPE Washable Filters, Expansion Valve, R407c refrigerant, Heater, Humidifier, Microprocessor Controller, G4 Filter, Suction and Discharge piping, Internal power and Control wiring, HP/LP Cutouts, Power and Control contactors, RS485 card for monitoring, and Other Electrical & safety accessories. Outdoor cabinet consists of Fan with single phase motor and Condenser coil.
The Air-cooled High Performanc AC unit shall be designed as per following conditions:
• Inside Design condition : 23 Deg C ±2 Deg C and Max 50% RH
• Ambient air design temperature : 43 Deg C
• Actual Capacity : As per Requirement
• Air Quantity : 500 to 600 CFM / TR
• Filters Efficiency : 90% efficiency down to 10 Microns.
•Type of load : High sensible heat load (Sensible heat factor above 0.90)
Fault Failure changeover
Cascading Effect
Sequencing of above Units
Sequencing of above Units
Make of PAC- Vertive/ Emerson/ schinder
1.01) 12.5 KW | 2 | Jobs | 8,62,100 | ₹17,24,200 |
| 2 | Low side accessories for Installation & Commissioning of Precision AC:-
a) Supply and charging of refrigerant gas R-410a/R-407 for above PAC System. | 20 | Kgs. | 1,468 | ₹29,360 |
| 2.01 | b) Supplying and Interconnecting Copper piping between indoor & outdoor unit. Copper piping will be duly insulated with 13mm thick nitrile rubber insulation. Copper piping should be epoxy coated.
(i) Supply and laying Hot gas line dia (3/4) & Liquid line( 1/2)-18 Guage Hard Copper with fittings, accessories etc for above PAC System. | 20 | Meters | 2,281 | ₹45,620 |
| 2.02 | c) Supply & Laying and Interconnecting Copper cable between indoor & outdoor unit to be laid on existing cable tray for above PAC System. | 25 | Kgs. | 342 | ₹8,550 |
| 2.03 | d) Supply & laying Incoming Copper Cable from Incoming Isolator to PAC Unit (4c x 6 Sqmm CU A) to be laid on existing cable tray. | 30 | Meters | 1,083 | ₹32,490 |
| 2.04 | e) Supplying and installing following size of perforated painted with powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc. as required.
(a) 150 mm width X 50 mm depth X 1.6 mm thickness | 20 | Meters | 686 | ₹13,720 |
| 3 | Supplying and installing of drain pipe of 25mm/32mm dia pipe of PVC heavy duty with nitrile insulation as required. | 25 | Meters | 795 | ₹19,875 |
| 4 | Supplying, Installation, Testing and Commissioning of Air Cooled Floor standing Tower type split Air conditioners complete with Indoor unit(IDU), Out door unit (ODU),surface / concealed copper Refrigerant piping with insulation (closed cell elastomeric nitrile rubber tubular pipe section) upto 5 Mtr (IDU to ODU), copper power cable upto 5.5 Mtr (IDU to ODU), i/c drain pipe of suitable length and size. R-32/R-410/R-407C Green Refrigerant, wireless Remote control, suitable for working between 180-260V with low & high voltage cutoff and 50 hz ,1 phase AC supply capable of performing cooling, dehumidification, air circulation of following capacity with Scroll / rotary with min 5 year Original Equipment Manufacturer (OEM) warranty both compressor and Printed Circuit Board (PCB). as specified. The system shall be able to deliver 100% of the rated capacity as per relevant IS Code. The lab testing reports as per IS: 1391 shall be submitted from National Accreditation Board for Testing and Calibration Laboratories (NABL) accredited as per International Electrotechnical Commission (IEC) 17025 standards /Central Power Research Institute (CPRI)/ Electrical Research and Development Association (ERDA)with Original Equipment Manufacturer (OEM) etc. complete as per CPWD specification and as per IS: 1391 as required. a) 3.8 TR BEE 5 Star Rating | 2 | Nos. | 1,10,025 | ₹2,20,050 |
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.76 MB
BOQ_395563.xls
BOQ • 0.35 MB
amendmentcorrigendum.pdf
PDF • 0.71 MB
dateextendcorrigendum.pdf
PDF • 0.30 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at [email protected].