| Sl No | Description | Qty | Unit | Mark Air-Particulate control systems L2 | SPECDEL ENGINEERING PRIVATE LIMITED L4 | ICEBERGS L1 | SM ENTERPRISES L3 |
|---|---|---|---|---|---|---|---|
| 0.00CRE - SUPPLY, INSTALLATION , TESTING , COMMISSIONING & VALIDATION | |||||||
| 1.00CEILING SUSPENDED LAMINAR AIR FLOW UNIT (CLAF) - S. I.T.C & V | |||||||
| 2.00Supply,installation, testing, commissioning and validation of Ceiling Suspended Laminar Air Flow Unit (CLAF) conforming to ISO 14644-1 Class 5 (Grade A) . The unit shall be of the recirculating, vertical unidirectional airflow type, designed for ceiling suspension with a heavy-duty SS 304 Grade (minimum 1.2 mm) structural hanging framework with mirror-polished finish as per site requirement. The scope of work and per-unit costing shall include the SITC of the accessories listed below; quantities of accessories per unit shall be determined in accordance with standard design requirement: Double-width double-inlet (DIDW) forward-curved centrifugal blower. The pre-filtration stage shall consist of a 5-micron EU5-grade pre-filter. The terminal HEPA filter shall be H14 Grade as per EN 1822. LED lamp shall be provided with minimum ≥500 LUX at work surface, The control panel enclosure shall be fabricated from SS 304 Grade, minimum 1.5 mm thick sheet, 240 grit electropolished finish with a satin matt surface, IP54 rated or better, with all edges and corners radiused for cleanability. The panel shall house and integrate the following functional elements: The unit shall be fitted with magnehelic differential pressure gauges for HEPA filter range 0–500 Pa—with high and low pressure alarm indication and visual/audio alert for filter choke, all inclusive of pnenumatic tubing. A Feather-touch ON/OFF switch panel with HMI-type controls for blower, . A Poly Alpha Olefin (PAO) upstream test port shall be provided for HEPA filter integrity testing. Atmospheric pressure port shall also be provided. Air velocity sensing device shall be provided with display on control panel, Speed controller for blower motor shall be of solid-state type. Blower failure visual and audio alarm indication shall be provided. An emergency stop switch (mushroom-head, lockable, IP55) shall be incorporated. The interconnecting pipe between CLAF and control panel shall be of SS304, Electrical supply shall be 230V, 1 Phase, 50 Hz with MCB protection. Hanging arrangement shall be designed for safe working load with minimum 4 suspension points and shall be approved structurally. All works shall include mechanical fixing, electrical connections to existing DB, pneumatic tube connections for gauges, levelling and alignment. Testing and commissioning shall include installed HEPA filter integrity test, non-viable particle count, airflow velocity uniformity and pattern test, pressure drop verification across each filter stage, lux level measurement, sound level measurement. Validation documentation (DQ, IQ, OQ) shall be submitted as per HBL approved format. | |||||||
| 3.00BCG Block | |||||||
| 4.00 | Size (Overall) in mm: 2260 x 3065 x 650 - SITC | 1 | Nos | 6,88,500 ₹6,88,500 | 5,72,150 ₹5,72,150 | 3,81,532.5 ₹3,81,532.5 Lowest | 7,55,000 ₹7,55,000 |
| 5.00 | Size (Overall) in mm: 2260 x 965 x 650 - SITC | 1 | Nos | 3,10,500 ₹3,10,500 | 3,92,850 ₹3,92,850 | 1,23,075 ₹1,23,075 Lowest | 3,55,000 ₹3,55,000 |
| 6.00 | Size (Overall) in mm: 1100 x 1400 x 650 - SITC | 1 | Nos | 2,48,600 ₹2,48,600 | 2,00,200 ₹2,00,200 | 86,152.5 ₹86,152.5 Lowest | 2,55,000 ₹2,55,000 |
| 7.00VVF Block | |||||||
| 8.00 | Size (Overall) in mm: 2590 x 1250 x 650 - SITC | 1 | Nos | 3,45,500 ₹3,45,500 | 2,84,850 ₹2,84,850 | 1,78,458.75 ₹1,78,458.75 Lowest | 4,20,000 ₹4,20,000 |
| 9.00 | Size (Overall) in mm: 2590 x 1350 x 650 - SITC | 1 | Nos | 3,45,500 ₹3,45,500 | 3,11,500 ₹3,11,500 | 1,90,766.25 ₹1,90,766.25 Lowest | 4,55,000 ₹4,55,000 |
Tender Value
₹78.9 L
EMD Value
₹2.0 L
Closing Date
19 Jun 2026, 3:00 pmClosed
Deputy General Manager Proc.
HLL BIOTECH LIMITED, Integrated vaccine complex, Survey no 192 195, Meleripakkam village, Chengalpattu PIN 603003
Supply, Service, Repair, Testing Validation Of Cleanroom Equipment such as Laminar Air Flow Units (LAF) Mobile Laminar Air Flow Units Mobile (LAFU), Ceiling Laminar Air Flow Units Ceiling (CLAFU) And Associated Components) for VVF, BCG Blocks at I
2026_HBL_279995_1
HBL/CRPEQP/IVC/CPT/26-27 dtd 06.06.2026
Open Tender
Miscellaneous Works
Item Rate
60 days
Chengalapattu
Please refer Tender documents.
17 documents required · 17 mandatory
₹1,770
Yes
HLL Biotech Limited
₹2.0 L
Yes
29 Jul 2026
6 Jun 2026
20 Jun 2026
6 Jun 2026
19 Jun 2026
7 Jun 2026
| Sl No | Description | Qty | Unit | Est. Rate | Est. Amount |
|---|---|---|---|---|---|
| 0 | CRE - SUPPLY, INSTALLATION , TESTING , COMMISSIONING & VALIDATION | - | - | - | - |
| 1 | CEILING SUSPENDED LAMINAR AIR FLOW UNIT (CLAF) - S. I.T.C & V | - | - | - | - |
| 2 | Supply,installation, testing, commissioning and validation of Ceiling Suspended Laminar Air Flow Unit (CLAF) conforming to ISO 14644-1 Class 5 (Grade A) . The unit shall be of the recirculating, vertical unidirectional airflow type, designed for ceiling suspension with a heavy-duty SS 304 Grade (minimum 1.2 mm) structural hanging framework with mirror-polished finish as per site requirement.
The scope of work and per-unit costing shall include the SITC of the accessories listed below; quantities of accessories per unit shall be determined in accordance with standard design requirement: Double-width double-inlet (DIDW) forward-curved centrifugal blower. The pre-filtration stage shall consist of a 5-micron EU5-grade pre-filter. The terminal HEPA filter shall be H14 Grade as per EN 1822. LED lamp shall be provided with minimum ≥500 LUX at work surface, The control panel enclosure shall be fabricated from SS 304 Grade, minimum 1.5 mm thick sheet, 240 grit electropolished finish with a satin matt surface, IP54 rated or better, with all edges and corners radiused for cleanability. The panel shall house and integrate the following functional elements: The unit shall be fitted with magnehelic differential pressure gauges for HEPA filter range 0–500 Pa—with high and low pressure alarm indication and visual/audio alert for filter choke, all inclusive of pnenumatic tubing. A Feather-touch ON/OFF switch panel with HMI-type controls for blower, . A Poly Alpha Olefin (PAO) upstream test port shall be provided for HEPA filter integrity testing. Atmospheric pressure port shall also be provided. Air velocity sensing device shall be provided with display on control panel, Speed controller for blower motor shall be of solid-state type. Blower failure visual and audio alarm indication shall be provided. An emergency stop switch (mushroom-head, lockable, IP55) shall be incorporated. The interconnecting pipe between CLAF and control panel shall be of SS304, Electrical supply shall be 230V, 1 Phase, 50 Hz with MCB protection. Hanging arrangement shall be designed for safe working load with minimum 4 suspension points and shall be approved structurally. All works shall include mechanical fixing, electrical connections to existing DB, pneumatic tube connections for gauges, levelling and alignment. Testing and commissioning shall include installed HEPA filter integrity test, non-viable particle count, airflow velocity uniformity and pattern test, pressure drop verification across each filter stage, lux level measurement, sound level measurement. Validation documentation (DQ, IQ, OQ) shall be submitted as per HBL approved format. | - | - | - | - |
| 3 | BCG Block | - | - | - | - |
| 4 | Size (Overall) in mm: 2260 x 3065 x 650 - SITC | 1 | Nos | - | - |
| 5 | Size (Overall) in mm: 2260 x 965 x 650 - SITC | 1 | Nos | - | - |
| 6 | Size (Overall) in mm: 1100 x 1400 x 650 - SITC | 1 | Nos | - | - |
| 7 | VVF Block | - | - | - | - |
| 8 | Size (Overall) in mm: 2590 x 1250 x 650 - SITC | 1 | Nos | - | - |
| 9 | Size (Overall) in mm: 2590 x 1350 x 650 - SITC | 1 | Nos | - | - |
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Tendernotice_1.pdf
PDF • 0.59 MB
TEDOCRPEQP.pdf
Tender Documents • 0.57 MB
BOQ_326761.xls
BOQ • 0.42 MB
DATEEXTNCREII.pdf
PDF • 0.11 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .