| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹40.1 LAdmitted-Finance | ₹40.1 L | L1 | Admitted-Finance |
| 2 | L2₹42.2 LAdmitted-Finance | ₹42.2 L | L2 | Admitted-Finance |
| 3 | Rejected-Technical | - | - | Rejected-Technical Not Qualified |
| Sl No | Description | Qty | Unit | RATHER ELECTRICALS AND CONTRACTOR L2 | JAI CHANDI MAA ENTERPRISES L1 |
|---|---|---|---|---|---|
| 1.00Creation of 25KVA Xmer at Chol Changa Barote Balet in Village Dhundhrath | |||||
| 1.01 | 25 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound
Distribution Transformer of latest Energy Efficiency
Level-2 (New), IS1180 Part-I; 2014 as per latest upto date
amendment | 1 | No | 1,15,000 ₹1.1 L | 1,20,000 ₹1.2 L |
| 1.02 | Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer
housing, Stn. Type | 1 | Set | 3,500 ₹3,500 | 4,500 ₹4,500 |
| 1.03 | 11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical | 1 | Set | 7,000 ₹7,000 | 9,500 ₹9,500 |
| 1.04 | 11 kV Horn Gap Fuse Set 3 Phase 200A | 1 | Set | 3,500 ₹3,500 | 4,500 ₹4,500 |
| 1.05 | 95 mm² Single-Core Cable,1.1kV Grade, PVC Insulated
Stranded Conductor FRLS type | 44 | mtr | 95 ₹4,180 | 260 ₹11,440 |
| 1.06 | 9 Mtr. Long Pole( ST-410 SP33) | 2 | No | 20,500 ₹41,000 | 20,500 ₹41,000 |
| 1.07 | 11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and
80kV Negative, creepage distance 320mm | 3 | No | 250 ₹750 | 300 ₹900 |
| 1.08 | GI Channel/Angle/Flat of sizes including clamps | 250 | Kg | 150 ₹37,500 | 110 ₹27,500 |
| 1.09 | Galvinized Nuts and Bolts. | 8 | Kg | 120 ₹960 | 110 ₹880 |
Tender Value
Refer Docs
EMD Value
₹99,500
Closing Date
29 Dec 2025, 2:00 pmClosed
Executive Engineer JPDCL Batote
Oo Executive Engineer JPDCL Batote
Supply, Survey, Erection, Testing and Commissioning including laying of LT and HT after creation of 3 No 25 KVA substation at Chol Changa, Barote balet at Dhundrath , Dadla in village Ganote, and Bhagyan for electrification Of Unelectrified
2025_PDD_298792_1
eNIT 39 of 2025-26
Open Tender
Electrical and Maintenance Works
45 days
Ramban
Please refer Tender documents.
5 documents required · 5 mandatory
₹2,000
Yes
Executive Engineer JPDCL Batote
₹99,500
Yes
7 Mar 2026
22 Dec 2025
30 Dec 2025
22 Dec 2025
29 Dec 2025
22 Dec 2025
Creation of 25KVA Xmer at Chol Changa Barote Balet in Village Dhundhrath
25 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-I; 2014 as per latest upto date amendment
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution Box for 25 kVA DTR with MCCB for incomer & Switch Fuse Units for Outgoing Circuits
Cement bottoming 1:2:4 mix as per REC standards .5cum /pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
LT Distribution Box for 25 KVA DTR with MCCB for incomer and SFU's for outgoing Circuits.
Laying of HT Line with ACSR Weasel Conductor on ST Poles 9 mtr long at Chol Changa Barote Balet in Village Dhundhrath (some poles are already erected)
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
30 mm² ACSR Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Laying of LT Line on ST Poles 8 mtr long with ACSR Weasel Conductor at Chol Changa Barote Balet in Village Dhundhrath (some poles are already erected)
8 Mtr. Long Pole(ST-410 SP15)
ACSR Weasel
Shackle Insulator
M Clamp
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Creation of 25KVA Xmer at Dadla in Village Ganote
25 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-I; 2014 as per latest upto date amendment
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution Box for 25 kVA DTR with MCCB for incomer & Switch Fuse Units for Outgoing Circuits
Cement bottoming 1:2:4 mix as per REC standards .5cum /pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
LT Distribution Box for 25 KVA DTR with MCCB for incomer and SFU's for outgoing Circuits.
Laying of HT Line with ACSR Weasel Conductor on ST Poles 9 mtr long at Dadla in Village Ganote
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
30 mm² ACSR Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Laying of LT Line on ST Poles 8 mtr long with ACSR Weasel Conductor at Dadla in Village Ganote
8 Mtr. Long Pole(ST-410 SP15)
ACSR Weasel
Shackle Insulator
M Clamp
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Creation of 25KVA Xmer at Baghyan in Village Baghyan
25 kVA (11/0.433-0.250KV;50Hz), Aluminium Wound Distribution Transformer of latest Energy Efficiency Level-2 (New), IS1180 Part-I; 2014 as per latest upto date amendment
Gapless Surge Arrestor,9 kV ,10 kA ,LA with polymer housing, Stn. Type
11kV GO, AB Switch 3-Phase, 3-Pole, 200 Amp, Vertical
11 kV Horn Gap Fuse Set 3 Phase 200A
95 mm² Single-Core Cable,1.1kV Grade, PVC Insulated Stranded Conductor FRLS type
9 Mtr. Long Pole( ST-410 SP33)
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lightening Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
GI Channel/Angle/Flat of sizes including clamps
Galvinized Nuts and Bolts.
LT Distribution Box for 25 kVA DTR with MCCB for incomer & Switch Fuse Units for Outgoing Circuits
Cement bottoming 1:2:4 mix as per REC standards .5cum /pole
Earthing of substation --Excavation of earth pit of dia 650 mm & depth 3000 mm, installation of Earthing pipe of 40 mm Nominal bore & 4mm wall thickness & length 2.5 mtr long as Per IS 1239.GI Strip for neutral earthing of size 25 mm x 3 mm for connection of transformer body,G.O Set & lightening arrestor as per IS 2629/85, GI nuts & bolts,refilled with earth enhancement materials and earth Chamber made of brick masonary with RCC slab cover.
LT Distribution Box for 25 KVA DTR with MCCB for incomer and SFU's for outgoing Circuits.
Laying of HT Line with ACSR Weasel Conductor on ST Poles 9 mtr long Baghyan in Village Baghyan
9 Mtr. Long Pole( ST-410 SP33)
GI V cross-arm with top Bracket including clamp
GI Channel X-arm including clamps and braces
30 mm² ACSR Conductor
11kV Polymeric composite Pin Insulator 12kV, 5kN, Lighting Impulse 75kV Positive and 80kV Negative,creepage distance 320mm
11kV Polymeric composite Disc Insulator 12kV,min failing load 45kN, Lighting Impulse 75kV Positive and 80kV Negative, creepage distance 320mm
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Laying of LT Line on ST Poles 8 mtr long with ACSR Weasel Conductor Baghyan in Village Baghyan
8 Mtr. Long Pole(ST-410 SP15)
ACSR Weasel
Shackle Insulator
M Clamp
Galvanized Nuts and Bolts
Earthing Complete by GI Pipe 40 mm or GI Rod 20mm 2.5 mtr long through GI Strip.
Aluminium Paint
Please Enable Macros to View BoQ information
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.21 MB
BOQ_968803.xls
BOQ • 0.41 MB
SBDeNIT39.pdf
Tender Documents • 0.72 MB
Download all tender documents and submit your bid