| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹28.9 LAccepted-AOC | L1 | Accepted-AOC L1 bidder | |
| 2 | L2₹33.3 L+₹4.4 L (15.2%)Rejected-Finance 19 LAKE TEMPLE ROAD KOLKATA 700029 | KOLKATA | WEST BENGAL | 700029 | L2 | Rejected-Finance 2nd lowest bidder | |
| 3 | L3₹35.4 L+₹6.4 L (22.3%)Rejected-Finance 4TH FLOOR VOLTAS HOUSE A BLOCK DR BABASAHEB AMBEDKAR ROAD CHINCHPOKLI MUMBAI MAHARASHTRA 400033 | MUMBAI | MAHARASHTRA | 400033 | L3 | Rejected-Finance 3rd lowest bidder |
| Sl No | Description | Qty | Unit | VOLTAS LIMITED L3 | TRANSTECH L1 | Shinryo Suvidha Engineers India Pvt. Ltd. L2 |
|---|---|---|---|---|---|---|
| 1.00SITC of Following Ceiling Suspended Double Skinned Mini Air Handling Units (30 mm TSP) each consisting of the following and having 23+2 mm thick PUF insulated extruded Aluminium section frame construction: a) Fan Section DIDW forward curve imported fan (MK.Krugar/Nikotra).The AHU shall consist of 1 no. Centrifugal Blower with 1 no 3phase TEFC Squirell cage induction motor. b) Coil Section with 4 Row deep (0.41 mm thick) with 12 FPI Chilled Water Cooling Coils with washable Pre-filters with efficiency 80% down to 20 microns c) 3 phase TEFC Sqirrel Cage Induction Motor. d) Sandwiched SS Drain Pan with bottom surface of the pan thermally insulated. e) with UVC emitter. f) including suitable control panel housed in sheet steel enclosure comprises with 4-pole 16A MCCB with rotary handle, DOL starter, start/stop push buttons, Auto/manual selector switch incl single phase priventer etc and having suitable provision for interlocking with FDA system. AHU MAKE - EDGETECH/ VOLTAS/ZECO/CLIMCONE | ||||||
| 1.01 | 1200 CFM Nominal Capacity, 30 MM TSP | 7 | Item | 1,33,026 ₹9,31,182 | 1,26,504 ₹8,85,528 | 92,577 ₹6,48,039 Lowest |
| 2.00FAN COIL UNIT :- SITC of Fan coil unit with controller package includes 2 way on/off type valve, Ball Valve with and without strainer for connections and temperature controller with linkages. (Make:Edgetech/Voltas/Zeco). | ||||||
| 2.01 | 1TR/ 400 CFM | 2 | Nos | 38,324 ₹76,648 | 27,837 ₹55,674 Lowest | 30,272 ₹60,544 |
| 2.02 | 2 TR/ 800 CFM | 4 | Nos | 49,120 ₹1,96,480 | 36,644 ₹1,46,576 | 35,332 ₹1,41,328 Lowest |
| 3.00CHILLED WATER PIPING (MS HVY CLASS) Supply, Design, fabrication and erection of MS heavy class ERW pipe for CHILLED WATER CIRCUIT in accordance to IS-1239 standards including providing necessary qunatities of flanges, fittings, bends, elbows, gasket, nut-bolts etc. as follows: Make - TATA / Jindal. | ||||||
| 3.01 | 80 MM NB | 100 | Mtrs. | 1,265 ₹1,26,500 | 953 ₹95,300 | 852 ₹85,200 Lowest |
| 3.02 | 65 MM NB | 40 | Mtrs. | 1,025 ₹41,000 | 773 ₹30,920 Lowest | 934 ₹37,360 |
| 3.03 | 50 MM NB | 48 | Mtrs. | 806 ₹38,688 | 607 ₹29,136 Lowest | 741 ₹35,568 |
| 3.04 | 40 MM NB | 60 | Mtrs. | 582 ₹34,920 | 435 ₹26,100 Lowest | 709 ₹42,540 |
Tender Value
₹32.3 L
EMD Value
₹64,500
Closing Date
23 May 2025, 12:00 pmClosed
Exe.Engr.-I, Kol. South Health El. Divn. P.W.Dte
75 D H Road Kidderpore Kol_23
Air Conditioning Work for Renovation of Paediatric Surgery Wards and allied Doctors rooms, Sister rooms, Teaching rooms at central portion of 2nd and 3rd floors of Main Building within the campus of IPGMER - SSKM Hospital, Kolkata.
2025_WBPWD_839146_1
WBPWD/EE-I/KSHED/Q07/25-26
Open Tender
A/C ORG
Item Rate
45 days
Kolkata
Please refer Tender documents.
4 documents required · 4 mandatory
₹64,500
O/o Exe.Engr., Kol. South Health El. Divn. P.W.Dte
9 Sept 2026
25 Apr 2025
26 May 2025
25 Apr 2025
23 May 2025
3 May 2025
2 May 2025
Amount
1200 CFM Nominal Capacity, 30 MM TSP
FAN COIL UNIT :- SITC of Fan coil unit with controller package includes 2 way on/off type valve, Ball Valve with and without strainer for connections and temperature controller with linkages. (Make:Edgetech/Voltas/Zeco).
1TR/ 400 CFM
2 TR/ 800 CFM
CHILLED WATER PIPING (MS HVY CLASS) Supply, Design, fabrication and erection of MS heavy class ERW pipe for CHILLED WATER CIRCUIT in accordance to IS-1239 standards including providing necessary qunatities of flanges, fittings, bends, elbows, gasket, nut-bolts etc. as follows: Make - TATA / Jindal.
THERMAL INSULATION OF CHILLED WATER PIPE Supply and fixing of 50 MM THICK "TF" qulaity (16 Kg/CuM density) Expanded Polystrene pipe section, Vapour barrier and covered with sand, cement and plaster with GI chicken wire mesh including painting by one coat of primer and two coats of synthetic enamel paint ( Asian/ ICI).
DRAIN PIPE FOR CHILLED WATER SYSTEM SITC of Drain piping with PVC (Sch-40) pipes with fittings duly insulated with 19MM thick Nitrile rubber section, Vapour barrier with necessary quantities of supports, flanges, bends, elbows, fittings, nut-bolts, gaskets etc: MAKE - Finolex/ Supreme/ oriplast
WATER LINE VALVES, STRAINERS & ACCESSORIES SITC of the following Water line Valves, Strainers and accessories as per following categories, sizes and qunatities complete with providing flanges, nut-bolts, gasket and welding arrangements:
BUTTERFLY VALVE S&F Following Water line Butterfly-Valve as per following categories, sizes and qunatities complete with providing flanges, nut-bolts, gasket and welding arrangements: Butterfly valve shall be of PN 16 rating as per standard. Valves of sizes 32 mm and above shall be made out of Cast Iron body, SG iron disc with Nylon coated, SS-431 Stem, EPDM integrally moulded liner with hand lever/Gear Box. Valves up to 150 mm NB shall be with detachable hand lever operation whereas valves above 150 mm NB shall have warm gear operation. Make - Advance / C & R / Audco /Honeywell
BALANCING VALVE S&F Following Water line Balancing - Valve as per following categories, sizes and natities complete with providing flanges, nut-bolts, gasket and welding arrangements: The valves shall be designed for PN 16 rating as per standard. The valves of sizes 32 mm to 65mm dia. shall be of gun metal / cast iron construction with screwed ends angular design hand wheel with locking facility. Whereas valves of sizes 80mm and above shall be of cast iron construction with internal parts of SS 410 and EPDM / nitrile seat with flanged ends. The test cocks should be long enough to protrude out of valve insulation Make - Advance / C & R / Audco /Honeywell
3-WAY MIXING VALVE WITH ACTUATOR, LINKAGE & THERMOSTAT The three way modulating valves shall be provided in chilled water line to the cooling coil of Air- handlers which is actuated by a proportionate thermostat. These valves shall consist of bronze metal valve body with stainless steel trim with linear flow characteristics. Modulating motor shall be suitable for operation with a signal of 0-24 volt DC. The pressure drop across valve for air-handler unit shall not exceed 5.0 PSI. The valve linkages shall be of the same make as of valves & modulating motor. Mak e- Honeywell / Belimo / Danfoss
PRESSURE GAUGE SITC of the following Water line PRESSURE GAUGE as per following categories, sizes and qunatities complete with providing flanges, nut-bolts, gasket and welding arrangements: Bourdon type pressure gauges of 100mm dia of suitable range shall be provided.The water pressure gauge shall be made of stainless steel grade SS304. The dial plate shall be powder coated with white colour base & the calibration shall be done in black colour. All the pressure gauges shall be complete with ball valves & SS Siphon and confirming to IS:3624. Make - H Guru.
THERMOMETER SITC of the following Water line V form thermometer shall be made of aluminium die casting with golden colour anodizing. The thermometer shall have a V groove in the body to protect the refill from the damages during the installation. The refill shall be filled with blue colour mercury. The thermometer shall be complete with brass well & the calibration of temperature shall be in Celsius & Fahrenheit. Make - H Guru./ approved by EIC
AUTO AIR VENT S&F of Auto air vent including necesary piping connection as required. Make - Honeywell
G.I. DUCT WORK Supply & fixing of Class - VIII grade (120 GSM) supply/return air duct along with pre fabricated plenum for supply and return air with necessary supports, flanges etc. as required and as per IS 655 and IS-277 standards of following gauges. Make - SAIL/ TATA.
22 SWG thick
24 SWG thick
DUCT THERMAL INSULATION Supplying and fixing of 19 mm thick duly laminated aluminum foil of mat finish closed cell Nitrile rubber (Class “O”) insulation on existing duct after applying suitable adhesive for Nitrile rubber. The joints shall be sealed with 50 mm wide and 3 mm thick self adhesive nitrile rubber tape insulation complete Make - A-Flex/K flex/ Armacell
DUCT ACOUSTIC INSULATION Supplying & fixing of acoustic insulation inside ducting with 10mm thick open cell nitrile rubber(class O) of density 140Kg/cu.m-160 Kg/Cum insulation with bolts nuts GI washers etc as required. Make - A-Flex/K flex/ Armacell
ACP Box/Drop Ceiling work: Supply, fabrication & fixing of box type drop ceiling to cover the indoor units/CS AHUs & supply air ducts including the cost of hinged type trap door arrangement with 3mm thick ACP sheet as per manufacturer's specification on the frame work fabricated from Aluminium hollow rectangular section of size 50mm x 25mm (2mm thick) & duly suspended by Aluminium hollow rectangular section of size 50mm x 38mm (3mm thick) and silicon sealent complete in all respect as per direction of EIC. (Make:Aludecor/ Pratapbond/ Timex Bond)
AIR TERMINATION ACCESSORIES
Supply & Fixing of Aluminium powder coated supply air grills with volume control damper.Make - Systemair / Air Enterprise / Premire / Caryaire / Airmaster.
Supply & Fixing of Aluminium powder coated return air grilles without volume control damper.Make - Systemair / Air Enterprise / Premire / Caryaire / Airmaster.
Supply & Fixing of motorised Fire damper made out of 18 SWG GI sheet and frame with actuator, control circuit compatible with fire detection system (3 rd Party).
Supply & Fixing of Fresh air package with cowl, bird net arragements.Make - Systemair / Air Enterprise / Premire / Caryaire / Airmaster.
Defect Liability Period - 1 (One) year
The Agency must procure the materials from the Manufacturer / OEM or from their authorised sales channel so that the standard warranty / support of the Manufacturer / OEM becomes applicable to the products to be delivered and installed by them. Documents that authenticates such procurement from the Manufacturer / OEM or from their authorized sales channel and standard warranty / support should be sent from the e-mail of the Manufacturer / OEM / authorized sales channel to the e-mail of Engineer-in-Charge and hard copy of it to be submitted during execution, of work/ submission of bill. If any refurbished material is supplied and installed, penal action will be taken as per existing rules
Make & model of each and every material to be approved by EIC
Shinryo Suvidha Engineers India Pvt. Ltd. (BID ID -6386963)
VOLTAS LIMITED (BID ID -6432524)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .