Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹12.8 LAccepted-Finance UC I USHA PARK HARI NAGAR NEW DELHI 64 | NEW DELHI | DELHI | 110001 | 1 | Accepted-Finance 1 | |
| 2 | 2₹13.3 L+₹50,346 (3.94%)Rejected-Finance A 111 JHILMIL COLONY EAST DELHI 110095 | SHAHDARA | DELHI | 110095 | 2 | Rejected-Finance 2 |
Tender Value
₹13.0 L
EMD Value
₹25,968
Closing Date
4 Jan 2024, 10:00 amClosed
Executive Engineer-NZ
Office of the Executive Engineer,EE(Elec-I) Division, NZ
Provision of E. I. and other allied works in Malaria Offices near (1) Ayurvedic Dispensary Bhaktawarpur, (2) Old MCD Dispensary Main Chowk Nangloi, (3) Primary Urban Health Centre Lampur Road Narela (02 Nos for Ward 1, 2), (4) Old MCD Building
2023_MCD_179369_1
MCD/TR/9449/2023_6_1_1/1
Open Tender
Electrical Works
Item Rate
120 days
Narela
2 documents required · 2 mandatory
₹590
₹25,968
4 Jan 2024
27 Dec 2023
4 Jan 2024
27 Dec 2023
4 Jan 2024
28 Dec 2023
Amount
PART A - DSR Items
OD19464/2023-2024:DSR22 1.8.3 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with piano type switch, phenolic laminated sheet, suitable size M.S. box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group C
OD20848/2023-2024:DSR22 1.14.2 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
OD20847/2023-2024:DSR22 1.14.3 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required. 2 X 4 sq. mm + 1 X 4 sq. mm earth wire
OD20846/2023-2024:DSR22 1.14.4 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required 2 X 6 Sq.mm + 1 x 6 sq.mm earth wire
OD19470/2023-2024:DSR22 1.23.1 Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required. 5/6 amps switch
OD19471/2023-2024:DSR22 1.23.4 Supplying and fixing following piano type switch / socket on the existing switch box/ cover including connections etc. as required.3 pin 5/6 amp socket outlet
OD19472/2023-2024:DSR22 1.30 Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including providing and fixing 6 pin 5/6 & 15/16 amps socket outlet and 15/16 amps piano type switch, connection, painting etc. as required.
OD19485/2023-2024:DSR22 2.3.1 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator. 6 way, Double door
OD21087/2023-2024:DSR22 2.3.3 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator 12 way, Double door
OD19473/2023-2024:DSR22 2.12.2 Supplying and fixing following rating, double pole, 240 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
OD19474/2023-2024:DSR22 2.10.1 Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single pole
OD19475/2023-2024:DSR22 1.50.1 Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required. Upto 450 mm sweep
OD19476/2023-2024:DSR22 5.1 Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. (but without charcoal/ coke and salt ) as required.
OD19477/2023-2024:DSR22 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.
OD19478/2023-2024:DSR22 5.18 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as required.
OD21086/2023-2024:DSR22 2.14.3 Supplying and fixing following rating, double pole, (single phase and neutral), 240 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 300 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps
OD19480/2023-2024:DSR22 7.6.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required. Upto 35 sq. mm
OD19481/2023-2024:DSR22 7.7.1 Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
OD19592/2023-2024:DSR22 7.5.1 Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Upto 35 sq. mm
OD19593/2023-2024:DSR22 14.16.1 Supplying and laying of following size DWC HDPE pipe ISI marked along with all accessories like socket, bend, couplers etc. conforming to IS 14930, Part II complete with fitting and cutting, jointing etc.direct in ground (75 cm below ground level) including excavation and refilling the trench but excluding sand cushioning and protective covering etc., complete as required. 63 mm dia (OD-63 mm & ID-51 mm nominal)
OD19463/2023-2024:DSR22 21.1 Supply, Installation, Testing and Commissioning of 1200 mm sweep, BEE 5 star rated, ceiling fan with Brush Less Direct Current (BLDC) Motor, class of insulation: B, 3 nos. blades, 30 cm long down rod, 2 nos. canopies, shackle kit, safety rope, copper winding, Power Factor not less than 0.9, Service Value (CMM/W) minimum 6.85, Air delivery minimum 215 CMM, 350 RPM (tolerance as per IS : 374- 2019), THD less than 10%, remote or electronic regulator unit for speed control and all remaining accessories including safety pin, nut bolts, washers, temperature rise=75 degree C (max.), insulation resistance more than 2 mega ohm, suitable for 230 V, 50 Hz, single phase AC Supply, earthing etc. complete as required.
OD19595/2023-2024:DSR22 12.37 Supplying and fixing of light class G.I. pipe of 50 mm dia. (nominal) 3 metres length along the pole for protection of under ground cable as required.
PART B - Approved Items
122.1.2:Supply of XLPE insulated PVC sheathed Al. Conductor Armoured Cable 1.1KV grade conforming to IS-7098 of following size:-2C*6 sqmm
122.1.44:Supply of LED Tube type luminaire 20 Watt rating complete with polycarbonate housing batten integrated electronic driver prewired with high efficient LEDs with the following:(a) Total system wattage 20 watt +/- 5%(b )Luminous efficacy lumens/watt >=95 (c)Power Factor >=0.95
122.1.47:Supply of 250 mm (10 inch) sweep 1250 rpm exhaust fan Fresh Air Type complete with shutter blades etc. as required.
122.2.2: P/F Hot press sheet moulded compound (SMC) fire retardant (Temp. resistance up to 200 C), IP 55 weather proof pole box of inner dimension 200x160x98mm (NS) complete with suitable arrangement for fixing of 2 nos of 6 to 32 amp single pole MCB & 63 Amp. Double pole isolator (MCB/Isolator excluded) with neutral link duly shorting on DIN Channel with2 Nos of MS clamps with SS back plate of suitable size with danger monogram property printed on the cover etc as reqd. as reqd.
122.2.28:SITC of 60W LED Flood Light luminiare fitted with lens, made of pressure die cast aluminium housing & toughened glass cover complete with the following specification as reqd with IP 66 protection (a) Total system wattage =60 watt +/- 5% (b) Luminaire Efficacy>=100 Lm/w (c) Power Factor>=0.95 (d) Protection Class- IP-66
122.2.111:supply and fixing of 4.5 KG DCP with CO2 gas cartridge fire extinguisher (conforming to IS:2171 with cylinder fully charged)
PART C - Civil Items
10.18:Providing and fixing circular / hexagonal cast iron or M.S. sheet box for ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm thick M.S. sheet with its top surface hacked for proper bonding, top lid shall be screwed into the cast iron/M.S. sheet box by means of 3.3 mm dia round headed screws, one lock at the corners. Clamp shall be made of 12 mm dia M.S. bar bent to shape as per standard drawing .
M/S. A.K. Electricals
Bidder Name
M/S. A.K. Electricals
SRI BALAJI ELECTRICALS
stage.html
html • 0.03 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .