EEE EWD Dumka
Dumka
S/R to E.I. in Arts Building and Provision of Main Cubical Panel of Sahibganj College, Sahibganj.
2026_ENRGY_109404_4
Energy/EWD/Dumka/27/2025-26
Open Tender
Electrical Works
Percentage
45 days
Dumka
Please refer Tender documents.
8 documents required · 8 mandatory
₹5,000
₹99,500
31 Jan 2026
21 Jan 2026
28 Jan 2026
21 Jan 2026
27 Jan 2026
22 Jan 2026
Part - "A"
S/R to E.I. in Arts Building of Sahibganj College Sahibganj.
Wiring for light point/fan point/exhaust fan point/call bell point with 1.5 sq.mm FR PVC insulated copper conductor single core in surface/recessed PVC conduit, with modular switch, modular plate suitable GI box etc as required a) Group - C
Wiring for circuit/ submain wiring along with earh wire with the following sizes of FR PVC insulated copper conductor single core cable in surface / recessed PVC conduit as required
a) 2 x 2.5 sq.mm + 1 x 2.5 sq.mm earth wire (For Circuit - 700m + computer board - 700 from DB)
b) 2 x 1.5 sq.mm + 1 x 1.5 sq mm earth wire (12 Nos street light wiring on building)
c) 2 x 1.5 sq.mm + 1 x 1.5 sq mm earth wire (21 Nos highbay light )
d) 2 x 6.0 sq.mm + 1 x 6.0 sq.mm earth wire (combined Power Submain)
e) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (10 nos subamain for light, computer, highbay light, heavy duty wall fan)
f) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (3 nos power)
g) 2 x 4.0 sq.mm + 1 x 4.0 sq.mm earth wire (50 Nos A.C wiring direct from sub panel Busbar @ 25 mtr)
Supplying and drawing following sizes of FR PVC insulated copper conductor single core cable in existing surface / recessed steel / PVC conduit including dismantling as required a) 1 x 1.5 sq.mm (For inverter wiring)
Supplying and fixing suitable GI box with modular plac and cover in front on surface of in recess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 amps modular switch. connection, painting etc. as required
Supplying and fixing suitable GI box with modular plac and cover in front on surface of in recess, including providing and fixing 6 pin 15/16 amps modular socket outlet and 5/6 amps modular switch. connection, painting etc. as required
S/F A following Compact unit made Modular Computer board. a) 9 Module - 1 Nos b) 5 amp switches - 2 Nos c) 5 amp socket - 2 Nos d) 15 amp socket - 1 Nos e) 15 amp switches - 1 Nos
S/F A following Compact unit made Modular Computer board. a) 6 Module - 1 Nos b) 5 amp switches - 2 Nos c) 5 amp socket - 2 Nos
S/F following way single pole neutral, sheet MCB distribution board, 240 volts on surface/ recess, complete with tinned copper busbar, neutral busbar, earth bar, din bar, detachable gtand plate, interconnections, Phosphatized and powder painted including earthing etc as reqd. (But without MCB/RCCB/Isolator)
a) 8 way double door
b) 6 way double door
c) 4 way double door
d) 2 way double door
S/F following 240 volts, 'C' series/"B" series miniature circuit breaker suritable for lighting and other loads of following poles in the existing MCB DB complete with connection, testing and commissioning etc. as reqd.
a) 6/32 amps, MCB
b) 63 amps, DP MCB
c) 40 amps, DP MCB
S/F 20 amps, 240 volts, SPN industrial type, socket outlet, with 2 pole and earth, metal enclosed plug top'along with 20 Amps'C' series, SP MCCB, in sheet steel enclosure, on surface or in recess with chained metal cover for the socket outlet and complete with connections, testing and commissioning etc as reqd..
S/F LED tube light fitting 20/22 watt including connection etc as reqd.
S/F Double LED tubelight fitting made of Die cast aluminium housing 2 x 20 watt bettal tubelight suitable for surface mounted.
Supplying and fixing batten/ angle holder including connection etc as reqd.
S/F 2 pin 5 Amp ceiling rose on the existing junction box/woden block ineluding connection etc as reqd.
S/F 9/10 watt L.E.D lamp etc as reqd. (Bajaj/ Phillips/ or equi)
S/F steped type electronic fan regulator deluxe on the exisang switch Box/ cover including connection etc as reqd. (a) Electronic step fan regulator deluxe modular.
S/F PVC/ G.I box of follwing sizes on surface or in recess with sutiable sizes of Phenolic laminated sheet cover infront including painting etc as reqd. (a) 75 mmx75 mmx50mm deep/ (4"x4")
S/F 9" exhaust fan complete including connection etc as reqd.
S/F 100W suspended highbay light
S/F 16" (400mm) Wall mounted fan"
Supplying and laying of XLPE insulated PVC sheathed aluminium armoured cable working voltage upto 1100 volts as per IS: 7098 (Part I) of following sizes (Make, Havelis,polycab, finolax, capital or equivelant) a) 3.5 core 185 sq mm (from Generator room to Main panel)
b) 3.5x 95 sq mm (Generator Panel to Arts block)
c) 3.5 x 70 sq sq mm (Ground floor to 1st floor)
d) 3.5 x 95 sq mm (From ground floor to 1st floor)
e) 3.5 x 25 sq mm ( For light and power subpanel)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required. Upto 35 sq. mm (clamped with 1mm thick saddle)
Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 35 sq mm but not exceeding 95 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 95 sq mm but not exceeding 185 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
80mm dia Earthing Electrode 2mtr. Length / 80mm dia Earthing Electrode 3mtr. Length / 50mm dia Earthing Electrode 2mtr. Length/50mm dia Earthing Electrode 3mtr. Length & Backfill Compound chemical 4 Bag(per bag 25 KG)
Supply and laying 8 SWG copper wire at 0.50 metre below ground level for conductor earth electrode, including solding etc. as required.
S/F 90W LED Street light Make - havells/bajaj/halonix/jaguar/benlo
S/F 65 mm dia , G.I. bend medium class (For LED street light strengthening)
S/F of 48" Ceiling Fan with all accessories. Make - Bajaj/Usha/Vguard/polar
Providing and fixing following DP/TP&N sheet metal switch disconnector fuse unit in the existing metal board with rewireable type fuses, including drilling holes in metal board . making connections. etc. as required.
32 amps, double pole (for street light on Buildings)
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. ( Main panel Ground Floor)
a) 315 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 250 amps, 35 KA fixed thermal setting MCCB (Solar Incomer & generator incomer) = 2 Nos
c) 160 amps, 35 KA fixed thermal setting MCCB (for 1st floor outgoing) = 1 Nos
d) 200 amps, 35 KA adjustable thermal setting MCCB (for 1st floor outgoing) = 1 Nos
e) 250 amps 4 pole Changeover = 2 nos
f) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing)= 7 Nos
g) 63 amps DP MCB = 4 Nos
h) 63 amps TPN MCB = 2 Nos
i) Voltmeter = 1 Nos (digital)
j) Ammeter = 1 Nos (digital)
k) Indecator = 6 Nos
l) C.T. Coil = 3 Nos
m) 50mm x 5mm copper tape (For double busbar and connection) = 50 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Power Main panel 1st floor)
a) 200 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 4 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 12 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Solar/Light Main Panel 1st Floor)
a) 160 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 63/100 amps 16 KA fixed thermal setting MCCB (Outgoing) = 4 Nos
c) 63 amps DP MCB = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 3 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 12 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (Power and Light distribution Panel)
a) 63/100 amps 10 KA fixed thermal setting MCCB = 1 Nos
b) Indecator = 3 Nos
c) 25mm x 5mm copper tape = 8 Kg
ceiling fan down rod 1'
ceiling fan down rod clamp
Part - "B"
Provision of Main Cubical Panel at Sahibganj College Sahibganj.
Supplying and laying of XLPE indulated PVC sheathed, heavy duty, armoured elecrical cable with aluminium conductor for working voltage upto and including 1100 volts as per IS:7098 (Part I) of following sizes (Make - Havells, polycab, finolax, capital or equivalent) a) 3.5 core 240 sqmm (From Transformer to Main Panel)
b) 4x16 sq mm (For generator supply to principal office & Nandini Building)
c) 3.5x25 sq mm (For Main Supply to principal office & Nandini Building)
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. ( Main panel)
a) 500 amps, 35 KA adjustable thermal setting MCCB (for main incomer) = 1 Nos
b) 315 amps, 35 KA fixed thermal setting MCCB (generator incomer) = 2 Nos
c) 300 amps, 4 pole changeover = 2 Nos
d) 250 amps, 35 KA adjustable thermal setting MCCB (outgoing) = 3 Nos
e) 315 amps, 35 KA adjustable thermal setting MCCB (outgoing) = 1 Nos
f) 100 amps, 16 KA fixed thermal setting MCCB (Outgoing) = 10 Nos
g) 63 Amps, TPN MCB = 5 Nos
h) Voltmeter = 2 Nos (digital)
i) Ammeter = 2 Nos (digital)
j) Indecator = 9 Nos
k) C.T. Coil = 6 Nos
l) 200 Amps, 35 KA MCCB = 4 Nos
l) 50mm x 5mm copper tape (For double busbar and connection) = 70 Kg
fabricaton and installation of cubical panel with following accessories made of 16 SWG MS sheet painted with one coat steel primer and two coat power spray painting with approved shade makin PCC Plinth and foundation including fitting/ fixing / connection & transportation up to work site, labour charge etc all complete. (For Principal office and Nandini Building)
a) 63/100 amps, 10 KA fixed thermal setting MCCB (for main, generator and solar) = 3 Nos
b) 63 amps DP MCB = 6 Nos
c) 63 amps 4 pole changeover = 2 Nos
d) Voltmeter = 1 Nos (digital)
e) Ammeter = 1 Nos (digital)
f) Indecator = 6 Nos
g) C.T. Coil = 3 Nos
h) 50mm x 5mm copper tape = 14 Kg (For double busbar)
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size not exceeding 35 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
Laying of one number PVC insulated and PVC sheathed/ XLPE power cable of 1.1 KV grade of size exceeding 185 sq mm but not exceeding 400 sq mm direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.
CGST@9%(mailto:CGST@9%塹ᴻ䡿ⲯ嶂藄挧ꮥ)
SGST@9%(mailto:SGST@9%塹ᴻ䡿ⲯ嶂藄挧ꮥ)
Labour Cess @ 1%
stage.html
html • 0.02 MB
cancelled_1.pdf
pdf • 0.42 MB
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.09 MB
F2.pdf
Tender Documents • 0.27 MB
BOQ_147781.xls
BOQ • 0.32 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .