Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1₹92.0 LAccepted-AOC | 1 | Accepted-AOC Acceptance Of Tender | |
| 2 | 2₹1.0 Cr+₹6.8 L (7.08%)Rejected-Finance MD 1 236 SECTOR D1 LDA COLONY KANPUR ROAD LUCKNOW U P PIN 226012 | LUCKNOW | UTTAR PRADESH | 226012 | 2 | Rejected-Finance Not L1 | |
| 3 | 3₹1.1 Cr+₹10.6 L (11.0%)Rejected-Finance 118 442 E 2 KAUSHALPURI KANPUR 208012 | KANPUR | KANPUR NAGAR | UTTAR PRADESH | 208012 | 3 | Rejected-Finance Not L1 |
| Sl No | Description | Qty | Unit | rajan construction L1 | Supreme Builders L3 | R K CONTRACTOR AND SUPPLIERS L2 |
|---|---|---|---|---|---|---|
| 1.00 | Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets calling bell, bell push, etc for taking credit including making good the disturbed surfaces to match with the existing complete all as specified and directed.
Note : Old / unsv switches, sockets ceiling roses, pendants, regulators, calling bell, bell push etc obtained from dismantling shall be measrued under respective item of Sch of credit. | 5,398 | Per point | 12 ₹64,776 | 15 ₹80,970 | 10 ₹53,980 Lowest |
| 2.00 | Material and labour for one light / fan point controlled by one, one way switch 06 Amp wiring with 1.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable with and including continuous earth wire of size 1.5 Sq mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 20 mm dia or higher, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall etc and making good to the disturbed surfaces to match the existing complete all as specified and directed.
(Note : Modular cover plate and flush box of requisite size shall be measured and paid seprately under respective items) | 1,070 | Per point | 300 ₹3,21,000 Lowest | 429 ₹4,59,030 | 400 ₹4,28,000 |
| 3.00 | All as per serial item No 02 here-in-before but one bell point controlled by one bell push, 06 Amp. | 48 | Per point | 300 ₹14,400 Lowest | 429 ₹20,592 | 400 ₹19,200 |
| 4.00 | All as per serial item No 02 here-in-before but one, two way light point controlled by two, two way switches, 06 Amp. | 12 | Per point | 320 ₹3,840 Lowest | 429 ₹5,148 | 400 ₹4,800 |
| 5.00 | All as per serial item No 02 here-in-before but one 3 pin, 06 Amp socket outlet point on independent board controlled by one, one way switch 06 Amp. | 343 | Per point | 300 ₹1,02,900 Lowest | 429 ₹1,47,147 | 400 ₹1,37,200 |
| 6.00 | All as per serial item No 02 here-in-before but one 3 pin, 06 Amp socket outlet point on same board controlled by one, one way switch 06 Amp. | 179 | Per Point | 60 ₹10,740 Lowest | 116 ₹20,764 | 100 ₹17,900 |
| 7.00 | All as per Serial Item No 02 here-in-before but point wiring with 2.5 Sq mm single core FRLS cables and earth continuity wire of 2.5 Sq mm single core FRLS cable for one 3 pin 16 Amp socket out let point controlled by one, one way switch on independent board complete all as specified and directed. | 272 | Per point | 350 ₹95,200 Lowest | 550 ₹1,49,600 | 530 ₹1,44,160 |
| 8.00 | S & F Switch Modular 6A single pole, one way, 1 module complete all as specified and as directed | 1,587 | Each | 24 ₹38,088 Lowest | 65 ₹1,03,155 | 60 ₹95,220 |
| 9.00 | S & F Switch Modular 16A single pole, one way, 1 module complete all as specified and as directed | 272 | Each | 66 ₹17,952 Lowest | 110 ₹29,920 | 100 ₹27,200 |
| 10.00 | S & F modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and as directed | 517 | Each | 52 ₹26,884 Lowest | 120 ₹62,040 | 100 ₹51,700 |
Tender Value
₹1.2 Cr
EMD Value
₹2.3 L
Closing Date
24 Nov 2025, 6:00 pmClosed
CWE Lucknow
HQ CWE Lucknow, 229 MG Road, Lucknow Cantt, Lucknow-226002
SPL REPAIR TO INTERNAL ELECTRIFICATION IN CERTAIN BLDGS OF 7 KUMAON REPAIR/ REPLACEMENT OF ALUMINIUM WIRING TO COPPER WIRING IN CERTAIN BLDGS AT SHEA LINE SPECIAL REPAIRS/ REPLACEMENT OF OLD UNSERVICABLE VTPN DBS SPN DBS MCB/MCCBS SUB MAIN WIRING XL
2025_MES_730478_2
CWE/LKO/E/T-67 OF 2025-26
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Lucknow
Please refer Tender documents.
8 documents required · 8 mandatory
₹1,000
GE East lukcnow
₹2.3 L
Yes
10 Jan 2026
10 Nov 2025
26 Nov 2025
10 Nov 2025
24 Nov 2025
17 Nov 2025
10 Nov 2025 - 17 Nov 2025
Amount
Taking down carefully copper / aluminium point wiring (light, fan, socket or power) complete including fixture and fittings such as switches, ceiling roses, pendants, regulators, sockets calling bell, bell push, etc for taking credit including making good the disturbed surfaces to match with the existing complete all as specified and directed. Note : Old / unsv switches, sockets ceiling roses, pendants, regulators, calling bell, bell push etc obtained from dismantling shall be measrued under respective item of Sch of credit.
Material and labour for one light / fan point controlled by one, one way switch 06 Amp wiring with 1.5 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed FRLS copper conductor cable with and including continuous earth wire of size 1.5 Sq mm nominal cross sectional area, single core, 1100 Volts grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 20 mm dia or higher, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall etc and making good to the disturbed surfaces to match the existing complete all as specified and directed. (Note : Modular cover plate and flush box of requisite size shall be measured and paid seprately under respective items)
All as per serial item No 02 here-in-before but one bell point controlled by one bell push, 06 Amp.
All as per serial item No 02 here-in-before but one, two way light point controlled by two, two way switches, 06 Amp.
All as per serial item No 02 here-in-before but one 3 pin, 06 Amp socket outlet point on independent board controlled by one, one way switch 06 Amp.
All as per serial item No 02 here-in-before but one 3 pin, 06 Amp socket outlet point on same board controlled by one, one way switch 06 Amp.
All as per Serial Item No 02 here-in-before but point wiring with 2.5 Sq mm single core FRLS cables and earth continuity wire of 2.5 Sq mm single core FRLS cable for one 3 pin 16 Amp socket out let point controlled by one, one way switch on independent board complete all as specified and directed.
S & F Switch Modular 6A single pole, one way, 1 module complete all as specified and as directed
S & F Switch Modular 16A single pole, one way, 1 module complete all as specified and as directed
S & F modular Socket, 6A - 2/3 pin combined 2 module complete all as specified and as directed
S & F modular Socket 6A/16A - 2/3 pin combined 2 module complete all as specified and as directed
S & F Modular White cover plate with frame 12 module complete all as specified and as directed
S & F Modular White cover plate with frame 8 module complete all as specified and as directed
S & F Modular White cover plate with frame 4 module complete all as specified and as directed
S & F Modular White cover plate with frame 3 module complete all as specified and as directed
S & F Modular White cover plate with frame 2 module complete all as specified and as directed
S & F Modular Metal flush box 12 module complete all as specified and as directed
S & F Modular Metal flush box 8 module complete all as specified and as directed
S & F Modular Metal flush box 4 module complete all as specified and as directed
S & F Modular Metal flush box 3 module complete all as specified and as directed
S & F Modular Metal flush box 2 module complete all as specified and as directed
S & F Calling bell, AC 230 Volts, single phase complete all as specified and as directed
S & F bell push AC 230 Volts, 1 module complete all as specified and as directed
Supply and fix fan step regulator, 120W 2 module suitable for BLDC Fans complete all as specified and as directed
Supply and fix lamp holder, PVC / Polycarbonate type with back plate suitable for batten fitting complete all as specified & directed.
M&L for point with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 1.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 1.5 sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings / fixing accessories and unwelded sunken galvanized pressed steel terminal boxes of thickness not less than 1.0 mm covered with 3 mm thick phenolic laminated white sheet cover for mounting switches, sockets, fan regulators as required for the following :- One light point or fan point controlled by one switch.
All as per Item No 26 but One socket outlet 6 amp controlled by one switch on indepdendent board.
All as per Item No 26 One socket outlet 6 amp controlled by one switch on the same board with other switches.
M&L for point with 1100 volts grade PVC insulated FRLS multistranded copper conductor cable 2.5 sqmm (Phase - Red, Neutral - Black) and earth continuity conductor 2.5 sqmm (Green) drawn into and including concealed rigid non metallic PVC conduit medium grade not less than 20 mm dia ISI marked ivory colour with all conduit fittings / fixing accessories and sunken galvanized pressed steel terminal box of thickness not less than 1.0 mm covered with 3 mm thick phenolic laminated white sheet cover for mounting switches, sockets as required for one 16 amp socket outlet point controlled by one switch on independent board.
S & F switch piano flush button single pole one way 6 amp polycarbonate body complete.
S & F socket outlet 2 in 1, 2 & 3 pin, 6 amp, flush type polycarbonate body complete.
S&F switch socket combination 2 in 1, 3 pin 6 & 16 amp flush type polycarbonate body complete.
S & F electronic step fan regulator 120 - 280 volts of 100 watt capacity (socket type) polycarbonate body including connecting up complete.
Supply and fix in replacement of decorative wall mounting type LED light fitting, 1 x 15 Watt, 230 Volt made up of Polycarbonate including shade, lamp holder including 9/10 Watts LED lamp B22 CDL etc and all accessories pre-wired including connecting up complete all as specified and directed.
Supply and fix in replacement of integrated LED bulk head fitting 10 Watt, 6500K with IP 65 protection comprises of high pressure die cast aluminium housing, polycarbonate cover, etc complete all as specified and directed.
S & F in replacement LED surface mounted Batten 20-22 watt, powder coated die cast / extruded pvc polycorbonated body (Thickness ≥ 1.20 mm) and construction as per IS : 10322 with driver (Replaceable) as per the requirement with Driver efficiency >85%, Operating voltage AC 140-270 Volt, freq 50 Hz, Operating temp range -15 deg to 40 deg centigrade, internal surge protection of 2.5 KV with Short & Open circuit protection, THD < 10% , P. F.≥0.95, IP20, CRI >80, Flicker free, (flicker should be below 5%), life time (LED & electrical circuitary), of minimum 50000 burning hours with 70% of initial Lumen maintained till life ends, CCT 5700°K /6000°K/6500°K (As per ANSI Bin), SDCM (Standard Deviation Color Matching) <3, Maximum power consumption should not more than the specified rating and fixture shall be of relevant BIS standard and trade mark certificate (T.C.). Manufactures Word Mark/ Name Engraved/ Embossing/ Screen printing on housing. complete in all respect including connections with suitable size FRLS, PVC insulated copper conductor cable and earthing etc as required with Minimum 5 year OEM warranty. System lumen efficacy 100-110 lm/Watt output. LM79 & LM80 Test report from NABL lab for all testing required for LED fixtures as BIS shall be submitted. Shape size and CCT shall be as approved by Engineer-in-Charge as per requirement. (Thermal management: heat sink of aluminum housing such that LED junction temperature shall not rise above 90°C).
Ditto all as per item No 36 above but 10-12 Watt capacity
Supply & fix in replacemnet recessed mounted 12 watt round LED ceiling lights SMD type with diffuser spring loaded having lumen output not less then 120 luman watt suitable for fixing in 3" juction boxex incl connection complete all as specified & directed.
Supply and fix ceiling rose, 6 Amp, 250 volt, AC, ISI marked with three equal size terminals and PVC / Polycarbonate insulated body of 50 x 25 mm size complete all as specified & directed.
Taking down carefully ceiling fan / exhaust fan of any sweep complete with all accessories, dismantling blades and deposit in safe custody of AGE E/M Yard-II for BER procedure complete all as specified & directed.
Material and labour for sub main wiring with two single core, 10 Sq mm nominal cross sectional area, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 10 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to match the existing including taking out the unserviceable sub main wiring complete all as specified & directed. Note : 1. PVC Conduit and accessories shall be deemed to be included in the quoted rate 2. Three runs of 10 sqmm copper conductor and one run of PVC conduit shall be measured as one unit.
Material and labour for sub main wiring with two single core 06 Sq mm nominal cross sectional area, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 06 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to match the existing including taking out the unserviceable sub main wiring complete all as specified & directed. Note : 1. PVC Conduit and accessories shall be deemed to be included in the quoted rate 2. Three runs of 6 sqmm copper conductor and one run of PVC conduit shall be measured as one unit.
Material and labour for sub main wiring with two single core, 04 Sq mm nominal cross sectional area, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable with and including continuous earth wire of size 04 Sq mm nominal cross sectional area, single core, 1100 Volt grade, multi-stranded, PVC insulated, unsheathed, FRLS copper conductor cable and connected to common earth and earth dolly with suitable copper lugs and drawing into and including rigid non-metallic PVC conduit of 25 mm dia, medium grade complete with and including all PVC conduit accessories concealed into wall by cutting of chases in wall and making good to the disturbed surfaces to match the existing including taking out the unserviceable sub main wiring complete all as specified & directed. Note : 1. PVC Conduit and accessories shall be deemed to be included in the quoted rate 2. Three runs of 4 sqmm copper conductor and one run of PVC conduit shall be measured as one unit.
Supply and fix in replacement of AC modular box SPN plug and socket complete with and including MCB, SP, AC, 240 volt of 20 Amp, 'C' curve 10 KA breaking capacity and flush to wall including all cuttings & chases etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed.
Supply and fix in replacement of sheet metal enclosure distribution board, double door, single pole and neutral, AC, 240 volt, 08 way, with 200 Amp rated copper bus bar and metal door with IP - 43 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed. Note : MCBs and DB shall be of same make.
S & F in replacement of MCB distribution board, ETPN, 415 volts, 8 ways, powder coated, CRCA steel sheet, degree of protection IP 43 - IK 09 with reversible double door, recess mounted, having insulated 100 amp tinned copper bus bar, neutral busbar, earth bar, din bar, detachable gland plate, interconnection, earthing connection, blanking plates in unused spaces as required. Note : MCBs and DB shall be of same make.
Supply and fix in replacement of sheet metal enclosure distribution board triple pole and neutral (VTPN),double door, AC, 440 volt, 04 way with 200 Amp rated copper bus bar and metal door with IP 54 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed and comprising of the following:- (a) Incoming : MCCB, 125 Amp, 04 pole, AC, 415 Volt of 16 KA (Icu=Ics, thermally adjustable between 70% to 100%) - 01 Nos. (b) Out going : MCB, SP, AC, 240 volt of 06 to 32 Amp, "C" curve, 10 KA breaking capacity - 12 Nos. Note : 1. MCCB, MCB and DB shall be of same make. 2. Cost of MCCB and MCBs shall be deemed inclusive in quoted unit rate.
Supply and fix in replacement of sheet metal enclosure distribution board triple pole and neutral (VTPN),double door, AC, 440 volt, 04 way with 200 Amp rated copper bus bar and metal door with IP 54 & IK 09 protection along with cable end box for above DB and flush to wall including all cutting etc in wall and making good to the disturbed surfaces to match the existing complete all as specified & directed and comprising of the following:- (a) Incoming : MCCB, 125 Amp, 04 pole, AC, 415 Volt of 16 KA (Icu=Ics, thermally adjustable between 70% to 100%) - 01 Nos. (b) Out going : MCB, SP, AC, 240 volt of 06 to 32 Amp, "C" curve, 10 KA breaking capacity - 08 Nos. Note : 1. MCCB, MCB and DB shall be of same make. 2. Cost of MCCB and MCBs shall be deemed inclusive in quoted unit rate.
S & F in replacement of MCB TPN three pole 415 volts 40 to 63 Amps repturing capacity 10KA SI marked including making connections by using suitable copper lugs as required.
Supply and fix in replacement of MCB, SP, AC, 240 volt of 06 to 40 Amp capacity "C" curve, 10 KA breaking capacity and making connections by using suitable copper lugs complete all as specified & directed.
Supply and fix in replacement of MCB, SPN AC, 240 volt of 32 Amp capacity "C" curve, 10 KA breaking capacity and making connections by using suitable copper lugs complete all as specified & directed.
Supply and fix in replacement of MCB, DP, AC, 240 volt of 32 Amp capacity "C" curve, 10 KA breaking capacity and making connections by using suitable copper lugs complete all as specified & directed.
Material and labour for earthing complete with galvanised mild steel earth plate electrode 60 cm x 60 cm x 6 mm with elect plate No 3 thick buried vertically in ground (earth pit not less than 2.25 metre deep below ground level) with top edge of the plate not less than 1.5 metre below normal ground level steel earth plate connected with GI wire 04 mm dia by means of lug, bolts, nuts, check nuts, washers of galvanised iron or steel GI protection pipe 15 mm bore light grade and connecting to main switch board / Main DB’s including excavation, earth work, salt and charcoal dust mixed and packed 150 mm thick around GI earth plate, GI pipe medium grade 20 mm nominal bore watering pipe GI sheet funnel wire mesh, concrete pit, RCC cover 40 mm thick in PCC 1:2:4 type B1 duly reinforced with MS Bars 6 mm dia at the rate of 75 mm centre to centre both way with 12 mm dia lifting handle and pit / chamber in PCC 1:3:6 type C1, Angle iron 40 mm x 40 mm x 3 mm frame for pit cover including testing on completion all as shown on serial page No 497 of SSR part I - 2009 complete all as specified and directed.
Supply and fixing ceiling fans 1200 mm sweep, BEE star rated 5 with brush less direct current (BLDC) motor, class of insulation B, 3 Nos blades, up to 90 cm long down rod, canopies, shackels, kit, safty rope, copper winding, power factor not less then 0.9 service value ( CM/M/W) min 6.00, air delivery min 210 cum/min, 350 RPM ( tolerance as per IS: 374- 2019) THD less then 10 % remote unit for speed control and all remaining accessories incl safty pin, nut bolts, washers , tempr rise 75 degree C (max) , insulation resistance more then 2 mega ohm, suitable for 230 V, 50 Hz complete.
S & F of exhaust fan single phase, 230/240 Volt heavy duty of size 300 mm sweep 1400 RPM including suitable louvers and making connection with twisted copper flexible wire 23/0.076mm all as specified and directed.
S & F exhaust fans, plastic body, ac, single phase, 230/240 v of size 200 mm sweep with louver and making connection with twisted copper flexible wire 23/0.076mm all as specified and directed
Supply and fix in replacement 45W Pressure die cast aluminium housing street light with system lumen of min 4500 lm and system efficacy of min 100-110 lm/w, IP-66,IK-10 single piece die cast incl spigot, dia 48-76mm,LED lifetime (L70B50) 75000 buring Hrs with integrated optical cover. Street light should have standalone lighting control system with AUTO ON/OFF based on DUSK/DAWN timings,preset time settings with monthly variations (Jan to Dec), inbuilt real time clock for switching, incleds dimming profile for energy savings,drift not exceedind max 2mins/year, clock retention upto five yeras, auto switching off secondary power for module,dimmable driver based on PWM control, dim to off with high/low voltage cut off with 440V protection for 8 hrs for complete luminiarie incl driver and astro module,surge protection as perIEC 61000-4-5 all as specified and directed by engineer in charge.
Supply and fix in replacement recessed mounted 2X2 LED panel, made of CRCA housing with high efficiency Polystyrene diffuser Luminaire should have minimum efficacy at System level >=120Lm/W with minimum system Lumens 4200 & Max System wattage of 35-36W, Life of fixture : 50000 burning Hrs.@L7OB50 Lumen maintenance, CCT-6500K (SDCM<=5), CRI Ra >=80, THD<10%, PF >0.95, an operating Voltage Range of 160-270 VAC. Minimum internal Surge Protection 4.0KV & IP20/IK02 protection.Fixture should comply with to IEC61000-3-2 ed.3.2, 2009 for Harmonics, IEC61347 -2 -13, 2006 in Conjunction with IEC61347-1 ed.2.0, 2007 for Electrical Safety, IEC62384 ed.1.1, 2011 for performance and IEC61547 ed.2.0, 2009, IEC 60598-2-2, CISPR 15 for EMC / EMI compliance with flicker free operations ripple <5%.both the fixture and Driver should have seperate BIs approval. complete.
Cutting walls any type, making holes for fixing of exhaust fan of any size or sweep and making good surface with fine plastering, finishing and colouring with existing colour matching complete all as specified and directed
Taking down electric meter and refixing on same board after rewiring all as specified and directed.
Supply and fixing of 15 watt rechargeable bulb with min 2 hrs backup , 230v, 50 Hz complete.
M & L for applying two coats of oil bound distemper over a coat of primer on walls with 1 mm thick putty after complete removal of existing treatment all as specified and directed by Engr-in-Charge.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 35 sqmm 3.5 core including taking out old unsv cable complete all as specified and directed. Note : Earth work other relevent items (if any) shall be measured and paid seprately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core including taking out old unsv cable complete all as specified and directed. Note : Earth work other relevent items (if any) shall be measured and paid seprately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 10 sqmm 2 core including taking out old unsv cable complete all as specified and directed. Note : Earth work other relevent items (if any) shall be measured and paid seprately.
Supply, laying and testing cable XLPE insulated, screened PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of size 16 sqmm 4 core including taking out old unsv cable complete all as specified and directed. Note : Earth work other relevent items (if any) shall be measured and paid seprately.
Excavation in trenches soft/loose soil not exceeding 1.5 m wide and not exceeding 1.5 m deep for laying of pipes/cables etc getting out and bottom surface to required gradient complete all as directed & specified
Returning filling in including spreading leveling watering and well ramming in layers each not exceeding 25 cm thickness complete all as specified and as directed
Removal of surplus spoil to a distance not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed
Supplying, filling in trenches, spreading, leveling sand cushioning 8 cm below cable and 15 cm above the cable for under ground cable complete all as specified & directed. i.e 18 cm punned down thick shall be considerd for mesurement)
M & L Old size sub class 'B' bricks,laid flat in trenches over the cable with length of brick perpendicular to the direction of the cable , adjacent/abutting each other complete all as specified
S & F in replacement of factory made powder coated distribution board SP & N 12 way fabricated of CRCA sheet with metal door & IK -09 protectionbar, Neutral bar, standard DIN rail, earth bar and cable ties for cable management, top and bottom removable gland plates complete.
S & F in replacement of factory made powder coated distribution board 4 way TPN DB Double door with metal double door IP-43 & IK -09 fabricated from CRCA sheet and concealed on wall and including 100 Amps bus bar, Neutral bar, Standard din rail,earth bar and cable ties complete .
Supply and fix cast aluminium heavy pole designer leg and border designer base finished with polyurethane paint (with prior treatments) diamtr of one leg is approx 76mm outer dia for spiogot entry 60mm 03 Nos "T" shaped bolts with nuts and washers provided for concrete foundation , total length of the pole incl base and legs (base x 03 Nos legs) is 2463 MM (Appx 8 fit 1 inch ) with fully cast aluminium finish polurethane paint( with prior tretments) suare junction with max projection breadth of 625 mm suitable for two number post top lantren with polyurethane ( with prior treatments ) Paint with arylic window cover total length 533 mm and breadth 228 mm.B-22 brass provided with qaluminium cover incl PCC 1:2:4 (size 600 x 600 x 600 mm ) foundation, , nut bolts, connecting up complete.
Supply and fix in replacement LED Flood light 140 W IP 65 made up of pressure die cast aluminium housing with potted Isolated driver and high power LED and individual lenses complete.
Supply and fix in replacement LED street light fitting 90 watt , IP 66, made up of pressure die cast aluminium housing with potted Isolated driver and high power LED and individual lenses, complete.
M & L steel tubelar swaged poles complete with cast iron base plate, finial tapper plug, bolts, nuts & screws as specified type 410 SP-22 ( 8.50 meters long) complete.
S & F in replacement street light GI bracket of 1.2 mtr long made out of 40mm dia light grade GI pipe bend to shape of 120 degree end welded at required including 02 Nos MS clamp of flat iron 40 x 6mm with nuts bolts & washers for fixing on wall complete.
Supply, install, test and commissioning in replacement factory made THERMOPLASTIC/HDPE CABLE JUNCTION BOXES IP 66/67 “weather proof”, with terminals for outdoor installation (with knockouts for cable entry) of min size 205 x 255 x 112 mm depth with cable entry size of 10-25 sqmm with terminal incl Aluminium bus bar and MCB SP 6amp-----01 No. complete.
Supply and fixing GI pipe light grade 40 mm bore for cable protection fixed to poles/along wall/floor/under road/across the drain or nallah including taking down old unserviceable GI pipe complete.
M & L for PCC (1:4:8) type D-2 using 40 mm graded stone aggregate in foundation of electric poles, struts PCC blocks including necessary form work and fair finish to exposed surfaces without using extra cement etc, complete.
M & L for PCC (1:3:6) type C-2 using 40 mm graded stone aggregate in the foundation of electric poles,stay assembly and struts PCC blocks including necessary form work and fair finish to exposed surfaces without using extra cement etc, complete.
All as per srl No Item No- 82 here-in-before but PCC (1:2:4) type B-1 using 20mm graded stone aggregate for coping of poles complete.
R K CONTRACTOR AND SUPPLIERS (BID ID -3481562)
Supreme Builders (BID ID -3486964)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.10 MB
2ndCallTenderet67.pdf
Tender Documents • 0.60 MB
BOQ_827586.xls
BOQ • 0.33 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .