| 1 | L1₹24.2 LAccepted-AOC | L1 | Accepted-AOC Lowest | |
| 2 | L2₹30.9 L+₹4.4 L (16.4%)Rejected-Finance | L2 | Rejected-Finance other than lowest | |
| 3 | L3₹54.2 L+₹27.7 L (104.2%)Rejected-Finance 499 A VIDHYUT NAGAR A AJMER ROAD JAIPUR 302021 | JAIPUR | JAIPUR | RAJASTHAN | 302021 | L3 | Rejected-Finance other than lowest |
| Sl No | Description | Qty | Unit | M/s Prakash Enterprises L2 | SHREE BHAGWATI ENTERPRISES L1 | DIVYA ASSOCIATES L3 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan and not exceeding 1.5 metre in depth and getting out in any type of soil complete all as specified and directed. | 135 | Cum | 200 ₹27,000 | 108 ₹14,580 | 100 ₹13,500 Lowest |
| 2.00 | Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50 metre above the starting point complete all as specified and directed. | 30 | Cum | 200 ₹6,000 | 50 ₹1,500 Lowest | 50 ₹1,500 Lowest |
| 3.00 | Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 cm in any type of soil complete all as specified and directed. | 105 | Cum | 200 ₹21,000 | 50 ₹5,250 | 30 ₹3,150 Lowest |
| 4.00 | Supply and laying un-reinforced precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm complete all as specified and directed. | 1,300 | Each | 30 ₹39,000 | 25 ₹32,500 Lowest | 25 ₹32,500 Lowest |
| 5.00 | M&L for Sand cushioning to PVC under ground cable and punning to provide a required cover complete all as specified and directed. | 27 | Cum | 400 ₹10,800 | 125 ₹3,375 Lowest | 500 ₹13,500 |
| 6.00 | M&L for Disc type insulator, Porcelain, vitreous brown, white or green single disc assembly, 145mm high & 255mm dia ball & socket type, for tension clamps for conductors, working pressure 11 KV including taking down old item complete all as specified and directed. | 5 | Each | 500 ₹2,500 | 600 ₹3,000 | 300 ₹1,500 Lowest |
| 7.00 | M&L for Pin type, porcelain, vitreous brown, white or green insulator (HT), 150mm height and 150 mm dia, 11 KV grade including one galvanised MS spindle, two GI washers and one GI nut including taking down old item complete all as specified and directed. | 10 | Each | 500 ₹5,000 | 450 ₹4,500 | 100 ₹1,000 Lowest |
| 8.00 | Supply and fixing Post insulator with GI post for holding fixed/moving contact assemby including fixing arrangement suitable for Air break gang operated switch 200 Amps, 11 KV grade including taking down old item complete all as specified and directed. | 10 | Each | 500 ₹5,000 | 350 ₹3,500 | 150 ₹1,500 Lowest |
| 9.00 | Supply and fixing lightening arrestor expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 11 KV including taking down old item complete all as specified and directed. | 5 | Each Set | 5,000 ₹25,000 | 4,500 ₹22,500 | 2,000 ₹10,000 Lowest |
| 10.00 | Supply and fixing Air break switch 200 amp, for HT 11 KV, 50 Hz AC, Gang Operated, triple pole, outdoor, horizonal / vertical mounting type (ISI marked), mounted on insulators and MS frame work, with fuse carriers & HT fuses, manually operated from ground level with locking arrangement including 65 mm pad lock with two keys, necessary electric connections and taking down old item complete all as specified and directed. | 6 | Each | 8,000 ₹48,000 Lowest | 15,400 ₹92,400 | 14,000 ₹84,000 |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
20 Oct 2025, 6:00 pmClosed
CWE JAIPUR
Military Engineer Services, HQ Commander Works Engineer, KalyanMarg, Banipark, Jaipur-06
REPAIR AND MAINT OF 11 KV NETWORK INCLUDING TRANSFORMER, SWITCHGEAR AND CONNECTED ACCESSORIES AT ZONE-II AREA UNDER GE (S) JAIPUR
2025_MES_731965_1
824501/JPR(S)/E8
Open Tender
Civil Works
Item Rate
180 days
GE SOUTH
AS PER NIT
6 documents required · 6 mandatory
₹500
Yes
GE SOUTH
₹70,000
Yes
JAIPUR
14 Feb 2026
20 Sept 2025
22 Oct 2025
20 Sept 2025
20 Oct 2025
6 Oct 2025
27 Sept 2025
Amount
Excavation in trenches n.exc 1.5 metre wide and n.exc 1.5 metre in depth for foundation etc or for shafts, wells, cess pits, manholes, pier holes, laying cables erection of poles / struts/stays etc not exceeding 10 Sqm on plan and not exceeding 1.5 metre in depth and getting out in any type of soil complete all as specified and directed.
Removing of excavated material (soil) to a distance n.exc 50 metre and depositing where directed at a level n.exc 1.50 metre above the starting point complete all as specified and directed.
Returning, filling in, including spreading, levelling, watering and well ramming in layers n.exc 25 cm in any type of soil complete all as specified and directed.
Supply and laying un-reinforced precast cable covers class HV, type I, flat, size 300mm x 180mm x 40mm complete all as specified and directed.
M&L for Sand cushioning to PVC under ground cable and punning to provide a required cover complete all as specified and directed.
M&L for Disc type insulator, Porcelain, vitreous brown, white or green single disc assembly, 145mm high & 255mm dia ball & socket type, for tension clamps for conductors, working pressure 11 KV including taking down old item complete all as specified and directed.
M&L for Pin type, porcelain, vitreous brown, white or green insulator (HT), 150mm height and 150 mm dia, 11 KV grade including one galvanised MS spindle, two GI washers and one GI nut including taking down old item complete all as specified and directed.
Supply and fixing Post insulator with GI post for holding fixed/moving contact assemby including fixing arrangement suitable for Air break gang operated switch 200 Amps, 11 KV grade including taking down old item complete all as specified and directed.
Supply and fixing lightening arrestor expulsion type complete with all fittings transmission class discharge capacity 65 KA suitable for 11 KV including taking down old item complete all as specified and directed.
Supply and fixing Air break switch 200 amp, for HT 11 KV, 50 Hz AC, Gang Operated, triple pole, outdoor, horizonal / vertical mounting type (ISI marked), mounted on insulators and MS frame work, with fuse carriers & HT fuses, manually operated from ground level with locking arrangement including 65 mm pad lock with two keys, necessary electric connections and taking down old item complete all as specified and directed.
Supply and fixing, fixed contact of Brass Alloy single pole including fasteners suitable for air break gang operated switch of cap 200/400 amp 3 pole 11 KV grade including taking down/dismantling old item complete all as specified and directed.
Supply and fixing moving contact of Brass Alloy single pole including fasteners suitable for air break gang operated switch of cap 200/400 amp 3 pole 11 KV grade including taking down old item complete all as specified and directed.
Supply and fixing flexible Copper strip including fasteners suitable for air break gang operated switch 200/400 amps 11 KV for single phase including taking down old item complete all as specified and directed.
M&L for shifting of transformer of any capacity from any location within the station to location of defective transformer and connecting with HT 11 KV incomer from existing source and LT outgoing cables complete all as specified and directed.
M&L for disconnecting and dismantling including handling and transportation of defective transformer, any type, 63 KVA to 125 KVA, 11 KV/433 V, copper/ Aluminium wound, opening the transformer, safe draining of tranformer oil for reuse, removing all burnt particles i.e tape, paper insulating strings etc gently and carefully, washing of the dust, rust and dirt from all parts including HT/LT coil, core tank and cooling tubes, painting the inner side of tank by zinc chromate paint and preparing the same for re-assembling after carrying out required repairs, re-assembling and re-installation, including connecting up electrically, commissioning at site all as directed by Engineer-in-Charge. Note :- 1. Repair cost is deemed to be included in the quoted rate; and Unsv items required to be replaced shall be measured and paid separately under respective items. 2. The burnt transformer oil will be contractor's property & any new oil will be measured and paid separately under respective item. 3. The coils and the oil shall be inspected for repair/replacement by department rep.
Description all as per Item No 15.00 above but 150 KVA to 250 KVA capacity complete all as specified and directed.
Description all as per Item No 15.00 above but 315 KVA to 400 KVA capacity complete all as specified and directed.
Description all as per Item No 15.00 above but 500 KVA to 630 KVA capacity complete all as specified and directed.
Supply only LT/ HT coil with suitable insulation for copper wound transformer of any type/capacity complete all as specified and directed.
Supply only HT Porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for 63 KVA to 125 KVA capacity transformer complete all as specified and directed.
Description all as per Item No 20.00 above but 150 KVA to 250 KVA capacity complete all as specified and directed.
Description all as per Item No 20.00 above but 315 KVA to 400 KVA capacity complete all as specified and directed.
Description all as per Item No 20.00 above but 500 KVA to 630 KVA capacity complete all as specified and directed.
Supply only LT Porcelain bushing complete with brass/tinned copper rod with nuts and gasket set complete for 63 KVA to 125 KVA capacity transformer complete all as specified and directed.
Description all as per Item No 24.00 above but 150 KVA to 250 KVA capacity complete all as specified and directed.
Description all as per Item No 24.00 above but 315 KVA to 400 KVA capacity complete all as specified and directed.
Description all as per Item No 24.00 above but 500 KVA to 630 KVA capacity complete all as specified and directed.
S&F in replacement of breather of transformer with silica gel complete with end fitting as per existing size and shape complete all as specified and directed.
M&L for Painting of transformer 63 KVA to 125 KVA applying two coats of synthetic enamel paint of grey colour by spraying complete including preparation of old surfaces, removing & cleaning of oil/grease complete all as specified and directed.
Description all as per Item No 29.00 above but 150 KVA to 250 KVA capacity complete all as specified and directed.
Description all as per Item No 29.00 above but 315 KVA to 400 KVA capacity complete all as specified and directed.
Description all as per Item No 29.00 above but 500 KVA to 630 KVA capacity complete all as specified and directed.
M&L for refilling fresh Silica Gel into the breather including removal of old item complete all as specified and directed.
M&L for boring of existing road/path for laying of GI pipe Size 100mm dia protection for UG cable including making good disturbed area/surface complete all as specified and directed.
Supply & fixing or laying galvanised steel tubing light grade (ISI marked) for protection of under ground cable on poles / walls under road crossing etc of size 100 mm bore including dismantling & taking down existing pipe complete all as specified and directed.
M&L for calibration and setting of protection relays of any make or type fitted on 33 KV breakers, transformer Buchholz relay control panel at MRS (details given below) as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including synchronizing of the same with JVVNL/MRS , arrangement shall be made so that fault shall not travel to nearest source feeder including minor repair, replacement of wiring etc, if required complete all as specified and directed. Note:- Calibration should be done twice during the currency of contract as and when directed by Engr-in-Charge.
M&L for calibration and setting of protection relays of any make fitted on 11 KV VCBs (Out going / Incoming 11 KV- 17 Nos) as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including grading with incomer panels at MRS ,synchronizing of the same with MRS setting to ensure that fault shall not travel to nearest source feeder including minor repairs, replacement of wiring etc, complete all as specified and directed. Note:- Calibration should be done twice during the currency of contract as and when directed by Engr-in-Charge.
M&L for calibration and testing of protection relay of any make or type fitted on 11 KV 3 Way RMU as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including grading with incomer panels at MRS. Servicing complete with decarbonizing the contact points, cleaning with CRC solution etc. All indicating lamp of the panel to be replaced if necessary. Breaker control switch, digital Amp meter, Volt meter should be replaced if in case found defective, testing of same after repair complete all as specified and directed. Note:- Servicing will be done twice twice during the currency of contract as and when directed by Engr-in-Charge. This will be considered as one job.
M&L for calibration and testing of protection relay of any make or type fitted on 11 KV 4 Way RMU as per IS and code of practice to ensure NO ERROR including setting for each fault over current with trip time delay in accordance to feeder load and other parameters of site including grading with incomer panels at MRS. Servicing complete with decarbonizing the contact points, cleaning with CRC solution etc. All indicating lamp of the panel to be replaced if necessary. Breaker control switch, digital Amp meter, Volt meter should be replaced if in case found defective, testing of same after repair complete all as specified and directed. Note:- Servicing will be done twice twice during the currency of contract as and when directed by Engr-in-Charge. This will be considered as one job. NOTE FOR ITEM NO 36 to 39 ABOVE (i) The calibration and setting must be completed with in 3 weeks from the date of commencement to avoid major break down. (ii) The calibration and setting shall be carried out by only qualified and experienced engineer. (iii) The relay setting shall be carried out once in three month as per load and site conditions to avoid any fault travel to next adjacent source breaker and shall be monitored regularly. (iv) For payment purpose the payment for calibration of relay and setting of relay twice in 06 months is considered as one job. The cost of monitoring shall deemed to be included in the quoted rate. (v) Calibration Certificate by authorised person should be submitted after calibraction/setting of the VCBs. The record of calibration/setting of relays shall be submitted by the Contractor.
Disconnecting of HT supply from 33 KV VCB with panel capacity of 1250 Amp outdoor/indoor type for overhauling of mechanism of trolly and carrying out repair works, servicing complete with decarbonizing the contact points, cleaning with CRC solution, tightening of springs greasing etc testing after repair complete all as specified and directed.
Disconnecting of HT supply from 11 KV VCB of any capacity of Amps for overhauling of mechanism trolly and carry out repair works, servicing complete with decarborizing the contact points, cleaning with CRC solution tightening springs greasing etc etc testing after repair complete all as specified and directed. Make of Existing VCB - AREVA/ ALSTOM/ CG Note:- Parts replaced in VCB shall be measured and paid separately under respective items.
Supply only Motor Cut off switch suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only Ratchet wheel Assembly with Ratchet pin suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only Shunt Trip Coil, operating voltage 24 Volts DC suitable for 11 KV VCB/ SF6 gas breaker including taking down of existing old unserviceable complete all as specified and directed.
Supply only digital type multifunctional meter with Ammeter/Volt Meter for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only Anti-pumping relay 2NO+2NC, 24V DC, 6 Amp including taking down of existing old unserviceable complete all as specified and directed.
Supply only Closing coil, operating voltage 24 Volt DC suitable for 11KV VCB/SF-6 gas breaker including taking down of existing old unserviceable complete all as specified and directed.
Supply only triping coil assembly suitable for 11KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only small gear assembly with motor shaft suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only Auxillary contactor for contact multiplication 7NO+7NC, 24V, DC, 6 Amp including taking down of existing old unserviceable complete all as specified and directed.
Supply only trip catch assembly suitable for 11KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only hold on catch assembly suitable for 11KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only tripping shaft assembly suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only closing shaft assembly suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only TNC switch suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
Supply only ZZ switch suitable for 11 KV VCB including taking down of existing old unserviceable complete all as specified and directed.
M&L for shutting down and earthing the system to carry out repair to off load rotating type 33KV/200 Amp Air break gang operated switch and alignment of isolators, blades, arcing horns moving mechanism oiling greasing to isolators tightening renewal/ replacement of unserviceable spare/components, nut and bolts complete after carrying out fresh lubrication using Lithium base grease/petroleum jelly, and re-fixing the spare parts/components complete all as specified and directed. Note:- New spare/components shall be measured and paid separately under respective items.
Supply only metallic (brass, alloy) fixed contact set single pole including fixing screw nuts and washers suitable for air break gang operated switch of cap 200 amp 3 pole 33 KV grade including taking down complete all as specified and directed.
Supply only post insulator with GI post for holding fixed/moving contact assembly including fixing arrangement suitable for Air break gang operated switch 200 Amps 33 KV grade including taking down complete all as specified and directed.
Supply only metallic (brass, alloy) GOD conductor/cable connector clamp with nuts, bolts and washers suitable for 33 KV grade panther ACSR conductor including taking down complete all as specified and directed.
Supply & Fixing HT fuse 30 to 200 amps capacity complete all as specified and directed.
Supply, installation & testing of Microprocessor based three phase relay system for over current, earth fault protection type MICOM/CGI 14N Model for 11 KV breaker, setting range with necessary wiring/fitting including dismantling of old IDMTL/Unserviceable relays complete all as specified and directed.
S&F Hooter system operating voltage 24V/220V AC/DC for 4 Nos VCB parallel operating system complete with testing including all accessories such as contactor,re-set switch and cut- out complete wiring etc including taking down old U/S complete all as specified and directed.
S&F HRC fuse (link type) having capacity 2 to 6 amp, 415 V, 80 KA suitable for existing 11 KV Breaker complete all as specified and directed.
S&F PT fuse 3.15 Amp suitable for 11 KV VCB complete all as specified and directed.
S&F stud type terminals of 24V, DC suitable for 11KV VCB including taking down complete all as specified and directed.
S&F Resin based insulator suitable for existing 11 KV Breaker including taking down complete all as specified and directed.
Disconnecting of HT supply from 11 KV VCB of capacity upto 800 Amps including rewiring of VCB control circuit with copper conductor wire size not less than 1.0 Sqmm and after wiring testing complete all as specified and directed. Note- The quoted rate shall deemed to include 20 m Length of 1.00 sqmm copper conductor.
M&L in replacement of spring charge motor assembly with Gear Assembly operating voltage 220 V AC/ DC suitable for 11 KV VCB of Areva/CG as existing on site complete with required material including taking down complete all as specified and directed.
Supply & fixing HT Jumper not more than 2 m long in repair /replacement on existing OH circuit/two Pole /four Pole Structure etc including ACSR Conductor (Weasel) using PG clamp/lugs, fasteners etc as per site requirement including taking down complete all as specified and directed.
S & F epoxy based cast resin CT having ratio 200-150-100/05 for suitable for 11 KV system size as per site including taking down complete all as specified and directed.
Supply and Fixing in replacement LED/Neon indicator Lamps with holder size 22.5mm of different colour (24 V/220 V, AC/DC) complete all as specified and directed.
Supply & Filling of transformer oil in transformer in situ/at site for toping up the level of oil having dielectric strength 60-80 KV during filling after filtration conforming to IS-335 complete all as specified and directed. Make- POWER/INSOLE/UNIVERSAL/SAVITA or Equivalent as per Approved Makes.
M&L for earthing with galvanised steel earth plate electrode 60cm x 60cm x 6 mm thick, buried directly vertically in ground in a pit depth not less than 2.25 metres below ground level with top edge of earth plate at a depth not less than 1.5 metre below normal ground level connected to and including galvanised iron earth strip 32 mm x 6 mm by means of bolts, nuts check nuts and washers of galvanised iron or steel. Earthing strip shall be protected by galvanised iron pipe 40mm bore light grade and connected to continuous earth wire on pole / test point. Watering pipe shall be 20 mm bore GI medium grade. The earthing shall be of inclusive of excavation & earth work in any type of soil, charcoal, salt, funnel PCC pit and RCC cover with handle complete all as specified & tested complete as per electrical plate No. 3 of MES SSR Part-I. NOTE:- (i) The concrete pit shall be made in PCC 1:2:4 type B-O, using 12.00 mm graded crushed stone aggregate 40mm thick precast cover slab of RCC (1:2:4), type B-1, using 20mm graded crushed stone aggregate with suitable MS handle. Reinforcement in cover shall be of 8mm dia TMT bars laid @150mm c/c both ways. (ii) Quoted shall include the cost of 7.5 metre GI pipe 40 mm (Light Grade) for protection of earth wire/strip. (iii) Quoted shall include cost of 7.5 metre earth lead wire/strip. (iv) Earth electrode shall be surrounded by adequate quantity of charcoal dust and salt to a packed thickness of 15 cm on all sides.
Supply & Fixing Polyfloor insulating rubber mat suitable for 11 KV sub station of size 2mtr x 1mtr x 3mm thick ISI mark, IS 15652 complete all as specified and directed.
Dehydration /filtration of transformer oil of existing power transformer installed at site with portable plant to improve the dielectric strength above 60 KV after filtration including testing of dielectric strength after dehydration at site complete all as specified and directed.
Supply, laying and commissioning XLPE insulated screened, PVC bedded galvanised steel strip or wire armoured electric power cables (heavy duty) with aluminium conductor 11000 volts grade IS-7098 marked, suitable for HT 11 KV (E) System laid in trenches/ ducts/ encased in GI pipe/ fixed to poles including jointing & testing complete all as specified and directed of size 95 Sqmm, 3 core cable including taking down/dismantling old item complete all as specified and directed.
Description all as per Item No 77.00 above 185 Sqmm, 3 core cable complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of size 95 Sqmm x 3 core complete all as specified and directed.
Description all as per Item No 79.00 above but 120 to 185 Sqmm x 3 core complete all as specified and directed.
M&L for cable straight through jointing kit, HT 11 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of size 95 Sqmm x 3 core complete all as specified and directed.
Description all as per Item No 81.00 above but 120 to 185 Sqmm x 3 core complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 11 KV grade, heat shrinkable, indoor type complete with jointing material suitable for HT XLPE cable 3 core 11 KV grade complete all as specified and directed of size 95 Sqmm x 3 core complete all as specified and directed.
Description all as per Item No 83.00 above but 120 to 185 Sqmm x 3 core complete all as specified and directed.
M&L for cable end termination, jointing kit, HT 33 KV grade, heat shrinkable, outdoor type complete with jointing material suitable for HT XLPE cable 3 core 33 KV grade, size 185 Sqmm to 240 Sqmm x 3 core complete all as specified and directed.
M&L for cable, jointing kit, HT 33KV grade, heat shrinkable, straight through type complete with jointing material suitable for HT XLPE cable 3 core 33 KV grade , size 185 Sqmm to 240 Sqmm x 3 core complete all as specified and directed.
M&L for fault finding in U/G cable using fault locating machine on requirement for 33/11 KV HT cables of any type/size complete all as specified and directed.
Trimming of trees at HT over head lines, Four pole structures,Two pole structures,Transformers and switchyard vicinity of electric supply pole/street light pole/solar modules & depositing at places n exc 50m complete all as specified and directed.
Painting of HT four pole/two pole structures including GOD complete at various places, applying two coats of synthetic enamel paint of aluminium colour by spraying complete including preparation of old surfaces, removing & cleaning of corrosion complete all as specified and directed.
Painting of HT switchyard 33/11 KV sub-station including GOD complete at various places, applying two coats of synthetic enamel paint of aluminium colour by spraying complete including preparation of old surfaces, removing & cleaning of corrosion complete all as specified and directed.
Labour only for fixing cable end termination, HT jointing kit, 11 KV grade, heat shrinkable, indoor /out door type size 95 Sqmm x 3 core to 240 Sqmm 3 core complete with jointing material making all electrical connections complete all as specified and directed. NOTE :- HT cable Joint is available with the Dept and will be supplied to contractor for fixing during the Execution of work.
Labour only for fixing cable straight through, HT jointing kit, 11 KV grade, heat shrinkable, indoor /out door type size 95 Sqmm x 3 core to 240 Sqmm 3 core complete with jointing material making all electrical connections complete all as specified and directed. NOTE :- HT cable Joint is available with the Dept and will be supplied to contractor for fixing during the Execution of work.
M&L and T&P for tightening of jumpers and busbar and and greasing of GOD at four/two pole structures and tightening of cable at HT and LT at both end of transformers complete all as specified and directed.
Supply & fixing chain link fencing of size 2.1 mtr height and wire mesh size 100mm x 100mm, 4mm dia including line wires, type of mesh as per standard size, rails, straining bolts, etc including provision of binding wire and taking out old fencing complete all as specified and directed.
M&L for Mild Steel work such as angle iron fencing post struts and flat iron fillets etc of grade Fe-310-0, including drilling holes, punching, splitting ends to secure chain link fencing or fixing of barbed wire to posts including all necessary cutting, welding drilling, bolting or riveting etc and including bands strap support for chain link, steel screw as required,10mm dia MS bar as in tie bars/horizontal bars fixed to secure the fencing on posts complete and rolled mild steel Framed work as in Gates of angle or other section with gusset plates, rails, braces, etc., complete, drilled for fixing of steel sheeting or other covering, Doors etc. to be prepared for hanging or sliding with & including either hooks & hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails & guides) & hanging; also fastening & fixing complete GDE Fe 410-0 or Fe 310-0 including taking down old Mild Steel work complete all as specified and directed.
M&L for Surface Dressing/Cleaning of various 11/33 KV sub-stations free from vegetation of any type including trimming of tree branches, bushes, creepers, etc. also on fencing complete, Cleaning of sourrounding area of transformer/GOD on HT two pole and four pole structures complete entire area of fencing at various places complete all as specified and directed.
Supply and laying at 11 KV Switchyard/substation , stone aggregate of size 40-80 mm upto height of 30 cm after the height of sand cushioning (river sand) which will be laid upto height of 15 cm before laying stone aggregate in sub-stations/electric yards including levelling and at cable ducts of switchyard/installation complete all as specified and directed Note:- It should be ensured that before laying stone aggregate and sand the grass or unwanted bushes shall be treated checmically to remove the unwanted vegetation and surface of the switchyard/installation should be made totally free from the existing unused aggregates without destroying the cable, earthpit etc at the installation including waterproof tarpaulin, all area covered by waterproof tarpaulin before laying of sand complete all as specified and directed.
Supply and laying at 33 KV switchyard/substation stone aggregate of size 40-80 mm upto height of 30 cm after the height of sand cushioning (river sand) which will be laid upto height of cm before laying stone aggregate in sub stations/electric yards including levelling and at cable ducts of switchyard/installation complete all as specified and directed Note:- It should be ensured that before laying stone aggregate and sand the grass or unwanted bushes shall be treated checmically to remove the unwanted vegetation and surface of the switchyard/installation should be made totally free from the existing unused aggregates without destroying the cable, earthpit etc at the installation including waterproof tarpaulin, all area covered by waterproof tarpaulin before laying of sand complete all as specified and directed.
Supply and laying of kerb stone at 11 KV Switchyard/substation , size of kerb stoe 300 mm X 300 mm X 150 mm. The aggregate and sand should be supported by kerb stone of standard size along with the edge of the perimeter. Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand), including making joints with or without grooves (thickness of joints except at sharp curve shall not to more than 5 mm), including making drainage opening wherever required complete all as specified and directed.
M&L for rectification, detection of gas leakage & refilling of the same in compatible to the pressure marked by the OEM for existing 11 KV VCB Interrupter complete all as specified and directed.
M/s Prakash Enterprises (BID ID -3449067)
DIVYA ASSOCIATES (BID ID -3455622)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.39 MB
TENDERDOCUS82501.pdf
Tender Documents • 0.70 MB
BOQ_819505.xls
BOQ • 0.35 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .