| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹58.8 LAccepted-AOC R 233 6 SIR SYED ROAD 3 JOGABAI EXT OKHLA NEW DELHI DELHI 110025 | SOUTH EAST DELHI | DELHI | 110025 | L-1 | Accepted-AOC Lowest bidder for the work. | |
| 2 | L-2₹74.0 L+₹15.2 L (25.9%)Rejected-Finance | L-2 | Rejected-Finance other than the lowest bidder | |
| 3 | Rejected-Technical | - | Rejected-Technical CONDITIONS NOT COMPILED WITH | |
| 4 | Rejected-Technical | - | Rejected-Technical CONDITIONS NOT COMPILED WITH | |
| 5 | Rejected-Technical | - | Rejected-Technical CONDITIONS NOT COMPILED WITH |
Tender Value
₹77.3 L
EMD Value
₹1.4 L
Closing Date
18 Jul 2024, 6:00 pmClosed
Col Pawan Kumar CWE Bhopal
Headquarters, Commander Works Engineer, Bhopal, Military Engineer Services, SI Line, Bhopal, Pin Code - 462001 (Madhya Pradesh)
PROVN OF PRECISION AIR CONDITIONER FOR MSN LAN AT DSCC AYODHYA NAGAR UNDER GE DRONACHAL
2024_MES_658598_1
83914/E8
Open Tender
Civil Works
Item Rate
180 days
DRONACHAL
AS PER NIT CONDITION
7 documents required · 7 mandatory
₹1,000
Yes
GE Dronachal
₹1.4 L
Yes
14 Sept 2024
8 Jun 2024
20 Jul 2024
8 Jun 2024
18 Jul 2024
6 Jul 2024
8 Jun 2024 - 6 Jul 2024
Amount
Supply,commissioning ,testing of DX based MICROPROCESSOR BASED PRECISION A/C UNITS as per the specifications complete with double skin side panels sandwich panels with internal isulation ,Direct Expansion Evaporator Coil with hydrophilic coating, air cooled condenser with stepless variable speed fans for winter operation, Double circuit with One Variable scroll compressor and one fixed type, with internal thermal overload protection, crankcase heater, Electronically commutated brushless motor Backward curved Plug fan evaporator coil with hydrophilic coating. The refrigerant circuit shall comprise of liquid receiver, Thermostatic/Electronic Expansion Valve, copper refrigerant pipe with anti-condensation insulation on suction line. The unit shall have environment friendly refrigerant (R410A), single/ double stage electric heater, variable capacity auto-modulating humidifier (efficiency minimum 0.75kW/Kg/hr),stainless steel drain pan. Liquid Receiver, Pressure Relief Safety Valve, Liquid Line Solenoid Valve and vibration isolator. Motor shall be suitable for 415 + 10% volts, 50 cycles, 3 phase AC supply and external static pressure shall be 25 Pa. Outdoor unit motor protection should be with IP-54 protection and should be weather proof which shall be designed for high ambient operating condition, it should have Fan Speed Controller to modulate the Fan Speed by sensing the Condensing Pressure for Low Ambient Operation. Auto sequencing of the unit for equal run time should be integral part of the micro-processor. Note: Each unit shall have inbuilt sequential controller for operating unit in N+1 confguration. Microprocessor should have inbuilt features of Team Mode and cascade mode incase required including Minor Civil Works as per the site requirment all as specified and directed by Engr-in-charge. (a) Airflow Configuration: Bottom Discharge and top Suction (b) 15TR Actual Cooling capacity (Actual capacity at 22°C ± 1°C, 50% RH Return Air Condition & 43.3°C Outside Ambient Conditions). Unit shall be capable of operation upto 50°C. (c) LOWER SIDE INSTALLATION: Installation, Commisioning and testing of 15 TR Precision AC including lifting shifting positioing, Pressure testing, Vaccuming Refrigerant Charging (R 410A ) Complete as required including Indoor Stand for mounting of Indoor Units-02 nos & Outdoor Stand for mounting of Outdoor Units-04 nos all as specified and directed by Engr-in-charge-02 nos
Supply & installation of Hard Drawn refrigerant Copper piping of size 7/8" and 11/8" ( 19 G) with 13mm Nitrile Rubber insulation to interconnect indoor and outdoor units. Considering 40 RMT / Machine. Charged As per actual all as specified and directed by Engr-in-charge
Supply & Laying, termination, connection of interconnecting electrical armoured cabling for Indoor Units & Outdoor Units of size 2.5 Sq.MM X 3 Core. Considering 20 RMT / Machine. Charged As per actual all as specified and directed by Engr-in-charge
Supply & Installation of PVC insulated 40 mm dia drain piping. Considering 10 RMT / Machine. Charged As per actual all as specified and directed by Engr-in-charge
Supply & Installation of PVC insulated 25 mm dia Humidifier piping. Considering 10 RMT / Machine. Charged As per actual all as specified and directed by Engr-in-charge
Supply & Laying, termination, connection of interconnecting electrical armoured cabling for Indoor Units & Outdoor Units of size 25Sq.MM X 3 Core. Considering 10 RMT / Machine. Charged As per actual all as specified and directed by Engr-in-charge
Supply of Floor Grill with Automodulation Dampers and sensors to control the dampers
Auto Traders (BID ID -3066460)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .