Executive Engineer
Electrical Division No.II, HPPWD, U.S. Club, Shimla-01.
Providing repair and replacement to E.I. in Indira Gandhi Sports Complex at The Mall Shimla
2026_PWD_137038_4
ED.II.TA.NIT.26-27.1185 dt. 18-06-2026
Open Tender
Electrical Works
90 days
Shimla
Please refer to tender documents. Eligibility criteria is mentioned at page No. 6-7, 9-10 of GCC. Documents mentioned in eligibility criteria must be uploaded to qualify the bid.
7 documents required · 7 mandatory
₹500
₹23,000
23 Jun 2026
23 Jun 2026
2 Jul 2026
23 Jun 2026
1 Jul 2026
23 Jun 2026
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
Group C
Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed steel conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper conductor single core cable for loop earthing as required.
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FARLS PVC insulated copper conductor, single core cable in surface/ recessed steel conduit as required.
2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire
2 X 4 sq. mm + 1 X 4 sq. mm earth wire
2 X 6 sq. mm + 1 X 6 sq. mm earth wire
2 X 10 sq. mm + 1 X 6 sq. mm earth wire
2 X 16 sq. mm + 1 X 6 sq. mm earth wire
4 X 4 sq. mm + 2 X 4 sq. mm earth wire
4 X 10 sq. mm + 2 X 6 sq. mm earth wire
4 X 16 sq. mm + 2 X 6 sq. mm earth wire
Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required.
1 x 1.5 sq. mm
2 x 1.5 sq. mm
3 x 1.5 sq. mm
4 x 1.5 sq. mm
2 x 4 sq. mm
3 x 4 sq. mm
4 x 4 sq. mm
Supplying and fixing of following sizes of steel conduit along with accessories in surface/recess including painting in case of surface conduit, or cutting the wall and making good the same in case of recessed conduit as required.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
6 way , Double door
8 way , Double door
12 way , Double door
16 way Double Door
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Single pole
Supplying and fixing following rating, followings poles 240/415 V Isolator suitable for inductive load of following poles in the exsisting MCB DB complete with connections, testing and commissioning etc. as required.
Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required.
Supplying and fixing TP&N copper bus-bar chamber suitable for 415 volts capacity with 4 No. copper strip bus-bars each of length and x-section suitable for following current carrying capacities, enclosure made of sheet steel having thickness of 1.6mm, dust protected, duly powder painted with detachable gland plate and other accessories including drilling holes on the board, making connections, earthing etc. as required.
100 A Copper Busbar Chambers 15" (SS Enclosure)
Providing and installation of stationary storage type Electric water heater (Geyser) of various sizes with 8 bar pressure rating Five star BEE rating and safety valve installation by means of expansion-bolts with nuts and washers, including embedding of expansion-bolts in the wall, making good the damages, electrical connections, testing etc. complete as required:-
25 Liter capacity water heater (Cat-A)
35 Liter capacity water heater (Cat-A)
Providing and installation exhaust fan of following sizes in the existing opening, Double ball bearing type metal frame including making the hole to suit the size of the above fan, making good the damages, connections, testing and commissioning etc. as required: of Approved Make Heavy Duty type.
Exhaust Fan, Heavy duty, 300 mm sweep (900/1400rpm)
Exhaust Fan, Heavy duty, 450 mm sweep (1400rpm)
Providing & Laying of one number aluminium conductor, PVC insulated and PVC sheathed armoured/ XLPE power cable, 1.1 KV grade of following sizes on wall surface as required.
Armoured cable 6 sq. mm (twin core)
Armoured cable 10 sq. mm (twin core)
Providing and laying of one number additional PVC insulated and PVC sheathed armoured / XLPE power cable of 1.1 KV grade of following size direct in cable tray including accessories clamping.
Armoured cable 6 sq. mm (twin core)
Armoured cable 10 sq. mm (twin core)
Rewiring for light point/ fan point/exhaust fan point/call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required
Group C
Rewiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable and 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable as earth wire in existing surface/ recessed steel conduit including dismantling as required.
Twin Control
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in the front including providing and fixing 6 pin 5/6 & 15/16 A socket outlet and 15/16 A piano type switch, connection, painting etc. as required.
Supplying and fixing metal box of 150mm X 75mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in the front including providing and fixing 3 pin 5/6 amps socket outlet and 5/6 amps piano type switch, connection, painting etc. as required.
Supplying and fixing metal box of 180mm X 100mm X 60mm deep (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in the front including providing and fixing 2 No 3 pin 5/6 amps socket outlet and 2 No 5/6 amps piano type switch, connection, painting etc. as required.
Supplying and fixing metal box of 250 mm X 300 mm X 60 mm deep metal box on surface or in recess with suitable size of phenolic laminated sheet cover in the front including providing and fixing 3 No 3 pin 5/6 amps socket outlet and 3 No 5/6 amps piano type switch, connection, painting etc. as required.
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.
S.P. 5/6 amps, one way Piano switch, ISI marked
S.P. 15/16 A, one way switch, piano type ISI marked
S/E of LED Flood Light IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥80 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power Wipro/ OSRAM/ Bajaj/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Flood Light 150 W
S/E of LED suspended linear LED 1200 mm 28W/30 W IP 66 rated with aluminium body/PDC housing The fitting should be installed on existing surface The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - Polycarbonate diffuser/PMMA
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥80 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power Wipro/ OSRAM/ Bajaj/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
suspended linear LED 1200 mm 28W/30 W
S/E of LED Panel with PDC body and polycarbonate /Acrylic diffuser to be mounted in recess The job includes carriage, erection, making connections testing and commissioning of the fittings.2 * 2 feet
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - polycarbonate/acyrlic diffuser UGR <30
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥110 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Panel Light 2'x2' ≥4620Lumens.
S/E of LED Panel with PDC body and polycarbonate /Acrylic diffuser to be mounted in Surface The job includes carriage, erection, making connections testing and commissioning of the fittings.2 * 2 feet
Specification of LED fittings:
Wattage of LED fittings - As per following parameter.
Total lumens of the fittings - as per wattage
Diffuser - polycarbonate/acyrlic diffuser UGR <30
Operating voltage - 140 V to 270 V, AC supply or better.
Input frequency - 50 Hz + 1 Hz
Power factor - Minimum 0.90
Luminaire efficacy - ≥110 lm/w
Color rendering index - CRI shall be greater than 80
Working/ operating temperature - 00 to + 450c or better
Color temperature - 60000K + 10%
Electronic Driver
Drive current (LED) - As per OEM.
Operating voltage - 140 V to 270 V, AC supply or better.
Type of driver - Constant current output driver
THD - Less than 10%
Surge Protection - 2.5 KV minimum
Efficiency Driver - ≥85%
Protection - Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver - 2 years against manufacturing defect.
Fixture - Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model - Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED - 50000 burning hours at 70% lumen maintenance
Lumen output of the fitting
LED Panel Light 2'x2' ≥4620Lumens.
S/E of LED Downlighter(recess)round type with CRCA/PDC body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings :-As per following parameter.
Lumen output of the fitting:-as below
Diffuser :- Polycarbonate diffuser/pmma
Operating voltage :-140 V to 270 V, AC supply or better.
Input frequency :-50 Hz + 1 Hz
Power factor :-Minimum 0.90
Luminaire efficacy :->85 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature :-0 to + 45 c or better
Color temperature:- 6000K + 10%
Electronic Driver :-
Drive current (LED):-As per OEM.
Operating voltage :-140 V to 270 V, AC supply or better.
Type of driver :-Constant current output driver
THD :-Less than 10%
Surge Protection :-2.5 KV minimum
Efficiency Driver:->100%
Protection:-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :-2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 50,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-50000 burning hours at 70% lumen maintenance
Lumen output of the fitting 1500
S/E of LED Batten with polycarboante body and diffuser The fitting should be installed on existing surface/recess The job includes carriage, erection, making connections testing and commissioning of the fittings.
Specification of LED fittings:
Wattage of LED fittings:- As per following parameter.
Total lumens of the fittings:-as below
Diffuser Polycarbonate diffuser/PMMA
Operating voltage 140 V to 270 V, AC supply or better.
Input frequency 50 Hz + 1 Hz
Power factor Minimum 0.90
Luminaire efficacy >100 lm/w
Color rendering index:-CRI shall be greater than 80
Working/ operating temperature 0 to + 45c or better
Color temperature 6000K + 10%
Electronic Driver
Drive current (LED) As per OEM.
Operating voltage 140 V to 270 V AC supply or better
Type of driver Constant current output driver
THD Less than 10%
Surge Protection 2.5 KV minimum
Efficiency Driver>85%
Protection :-Shall have under voltage and over voltage protection.
Guarantee of LED fittings including LED driver :- 2 years against manufacturing defect.
Fixture :-Should comply with LM 79 test from UL/NABL lab.
LED Type/ Make/ Model:-Power CREE/ OSRAM/ NICHIA/ Philips LUMILED with life more than 25,000 burning hours @70% lumen maintenance complying with LM 80 test report from the manufacturer.
Life of LED:-25000 burning hours at 70% lumen maintenance
Description
Lumen output of the fitting 2000 Lumen
Please Enable Macros to View BoQ information