Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.0 LAccepted-AOC | ₹24.0 L Quoted ₹25.6 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹26.1 L+₹43,655 (1.70%)Rejected-Finance | ₹26.1 L+₹43,655 (1.70%) | L2 | Rejected-Finance Higher |
| 3 | L3₹26.7 L+₹1.0 L (4.04%)Rejected-Finance 195 MAHESH NAGAR AMBALA CANTT 133001 | AMBALA | HARYANA | 133001 | ₹26.7 L+₹1.0 L (4.04%) | L3 | Rejected-Finance Higher |
| 4 | L4₹27.3 L+₹1.7 L (6.73%)Rejected-Finance | ₹27.3 L+₹1.7 L (6.73%) | L4 | Rejected-Finance Higher |
Tender Value
Refer Docs
EMD Value
₹60,000
Closing Date
15 Oct 2020, 6:00 pmClosed
GE NAMS
GE NAMS KHASA CANTT AMRITSAR
REPAIR/MAINT OF OH LINE / UG CABLE AND ALLIED WORKS IN INF BDE AREA AT NAMS
2020_MES_378601_1
GE NAMS - 52 / 2020 - 21
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
NAMS CANTT
Class D
Category b i
6 documents required · 6 mandatory
₹500
Yes
GE NAMS
₹60,000
Yes
6 Dec 2020
18 Sept 2020
16 Oct 2020
18 Sept 2020
15 Oct 2020
1 Oct 2020
Amount
Supply and fixing in replacement for earthing complete with galvanized iron earth plate electrode 600x600 x6.0mm thick burried directly in ground (earth pit not less than 2.25 mtr deep below ground level) with top edge of earth plate not less than 1.5 mtr below normal ground level, connected to GI strip of size 32X6mm as earthing lead by means of nuts, bolts, check nuts and washers of galvanized iron or steel all as shown on Electrical Plate No 3 of SSR Part-I 2009, connected to earthing test point all as specified or indicated including testing on completion. The quoted unit rate shall include the following elements as given below :- (a) Earth electrode as mentioned above (b) Main earthing lead of 32X6 mm GI strip from earth electrode to test point up to 7.5 mtrs. (c) Connecting earthing lead and electrode all as specified and testing complete. (d) Adequate quantity of charcoal and salt (e) GI protection pipe of 40 mm dia light grade of length not less than 5.00 mtrs. (f) Necessary excavation, earth work and PCC pit , angle iron 40x40x6mm frame including RCC cover.
All as per Srl Item No 2 but earth lead galvanised iron wire of 4mm dia connected by means of GI nuts, bolts and washers, 15mm bore light grade GI protection pipe
Supply laying in replacement & testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (Heavy duty_) LT 1100 volt grade with stranded aluminium conductor of size 95 sqmm 3.5 core complete all as specified and directed.
All as per srl item No 4 here-in-before but of size 70 Sqmm 3.5 core.
All as per srl item No 4 here-in-before but of size 50 Sqmm 3.5 core.
All as per srl item No 4 here-in-before but of size 35 Sqmm 3.5 core.
All as per srl item No 4 here-in-before but of size 25 Sqmm 3.5 core.
All as per srl item No 4 here-in-before but of size 16 Sqmm 4 core.
All as per srl item No 4 here-in-before but of size 16 Sqmm 2 core.
Supply and fixing in replacement of male and female contacts of gang operative switch made out of brass and rated capacity 200 amps, make matching with the existing switch complete all as specified and directed .
Supply and fixing in replacement of copper ribbon suitable for 200 amps rated capacity gang operative switch, 45 CM long complete all as specified and directed .
Material and labour for repairing existing LT Panel doors of front , back and internal sheets complete with new locking arrangement complete all as specified and directed. Note: Any part/spare found defective such as packing, nuts bolts,hinges & (welding machine works) etc shall be repaired/replaced which cost shall be deemed to be included in the unit rate quoted for this item.
Material and labour for preparing old painted surface of panel board by cleaning removing of old paint by scratching with wire brush / sand paper etc and including denting of broken / rusted surface and applied two coat of synthetic surface enamel paint by spray painting outside surface of panel as existing colour of panel all as specified and directed.
Excavates and relaying cables loops near the poles LT Panels transformers, cutting the damages/burnt parts of cable and reconnecting its into positions complete with thimbles, nut bolts, sleaves all as specified and directed by Engineer-in-Charge.
S&F in replacement 70sqmm HT 11KV single core heavy duty insulated cable from top disc insulator to GOD and disc to disc in any lenth with complete nuts & thimbles all as required at site.
Material & labour for cleaning away all grass vegetation, scapling shrubs bushes under grouth roots and trees not exceding 30 cm grith and removing rubbish upto distance of 50 mtr out the periphery of area under cleaness complete all as specified and directed.
Material & labour for providing 20mm broken stone aggregate including spreading and levelling complete all as specified and directed.
Supply,laying & fixing in replacement double wall corrugated (DWC) pipes made of high density polythyline (HDPE) with all accessories i.e. all type of joints, Sockets, Elbows, bends and End caps etc. all as specified and directed by Engr in Charge of size 50mm outer dia and 38mm inner dia
All as per items No 19 but of size 77mm outer dia and 63mm inner dia for
All as per items No 19 but of size 90mm outer dia and 76mm inner dia
All as per items No 19 but of size 145mm outer dia and 126mm inner dia
Supply and spraying anti vegetation chemical liquid of 1ltrs bottle mixed with water as per direction of Engr in charge .
Taking out existing gravels/hardcore material from the bottom of substn/equipment completely for cleaning and spraying of anti grass chemical and screnning the hardcore material and refill the same at places complete all as specified and directed by Engr in charge. Note:- Anti Grass chemical and loose filling of aggregate for topping up will be measured and paid separetly respective item of BOQ.
Taking out carefully manually by excavation of existing LT/HT cable with loops and relaying with DWC pipe the same after repair of cutting the damages / burnt parts of cable and reconnecting its into original positions complete with cable joints all as specified and directed by Engineer-in-Charge.Note:-(i) HT/LT Cable Joint & DWC Pipe will be measured and paid sepearetly. (ii) Unit rate shall be included in excavation and returning filling.
Prunning of trees of over head HT/LT lines by taking proper shutdown & removing the same from site upto a distance of 50 mtr all as directed by Engr in Charge.
Supply & fixing in replacement of stay assembly comprising of 7/2.50mm galvanized MS stay wire of reqd length, fixed to poles with and including of FI clamps made out of FI 40x6mm and nuts bolts washers of suitable size MS stay bow 14mm dia galvanized 40cm long MS galvanised stay rod threaded with nut 16mm dia 21 Cm long with washers MS stay plate galvanized 230x30x6mm incl necessary Excavation and PCC all as specified and directed by Engr-in charge
Material & labour for restrainging ACSR conductor HT/LT providing suitable proper sag all as specified and directed.
Supply & Install in replacement factory made outdoor type dust and vermin proof(IP 54 protection) feeder Pillar LT Panel board cubicle double door hinged type of suitable size 415V AC, 50Hz, fabricated of GP/CRCA sheet 3 mm thick machine pressed and angle iron frame 50mm X 50mm X 6mm grouted in PCC 1:2:4 type BI (20mm grade stone aggregated) powder coated in Nine Tank process inside and outside complete including 4 Pole aluminum Bus Bar of suitable size mounted on porcelain insulator ,concealed hinged door with 3Positioning door locking arrangement and enclosed in chamber made out of 2mm sheet thick GP/ CRCA sheet machine pressed and connection from incoming and outgoing electric cable with suitable size thimbles/lugs cable gland with open able shutters on both side and comprising of following
(i)MCCB 250 Amps 25KA 4pole 415V as a incomer-01 (ii) MCCB 25 KA 4P 160A -01 (iii) MCCB 25 KA 4P 100A -03 (iv) Aluminium Busbar of 400 Amps phase+Nutral (v)Ammeter and volt meter of suitable size (vi) Indicating lamp ( set of three RYB) -01 set Note:- Existing Old/Unserviceble Panels including accessories are removed and deposit to MES Store yard by the contractor from his own arrangement without any extra cost.
Material & labour for painting of PCC poles with two coats of synthetic enamel paint in black and white strip 30 cm wide each up to 1.5 mtr height from coping over a coat of primer including numbering of poles complete all as specified and directed.
Material & labour for 2 Pole structure complete painting to mild steel cross arms, bracing, supports, clamps, back plate etc fixed on HT Poles any height with providing two coats of aluminium paint over a coat one coat of red oxide primer complete all as specified and directed. Note:- One 2 pole mild steel struture complete on HT PCC pole steel members fixed thereon shall be considered as 'One Unit'.
M&L for testing of faulty LT cable by using LT voltage fault locating machine and finding the fault and to be repaired the same including all T&P as required on site complete all as directed. Note :- (a) Each job includes finding out the location of each fault in LT feeder. (b) Necessary excavation,returning filling and removal deemed included in this job.(c) LT straight Joint and additional LT cable if required it will be measured and paid separetly under respective item of this BOQ.
Supply and fixing in replacement of HT underground cable XLPE insulated PVC bedded, galvanised steel strip armoured electric power cables (heavy duty) with stranded aluminium conductor 11000 volts grade cross sectional area 120 sqmm 3 core laid in duct / trench/along pole etc including making connection complete all as specified and directed.
S&F in replacement disc type porcelain white, brown or green insulator including one galvanized mild steel spindle, two galvanised iron washers & one galvanised nut for working pressure 11000 volts grade.all as specified and directed by Engr-in charge
S&F in replacement pin type porcelain white, brown or green insulator including one galvanized mild steel spindle, two galvanised iron washers & one galvanised nut 150mm height,150mm dia for working pressure 11000 volts grade.all as specified and directed by Engr-in charge
M & L in replacement of out door type aluminuam bus bar chamber feeder box of cap 300 Amp , 3 phase, 4 wire, 415 Volts with porcelain insulator of size 90 x 60 x 45 cm made out of 3.15 mm CRCA Sheet duly painted with two coats of synthetic enameld paint over a red oxide primer and fixed and supported with anlge iron grouted in PCC 1:2:4 upto 0.30 mtr high from ground level all as directed by Engr-In-Charge.
Supply and fixing in replacement of HT underground cable XLPE insulated PVC bedded, galvanised steel strip armoured electric power cables (heavy duty) with stranded aluminium conductor 11000 volts grade cross sectional area 185 sqmm 3 core laid in duct / trench/along pole etc including making connection complete all as specified and directed.
Material and labour for PCC 1:4:8 type D-2 using 40mm graded broken stone aggregate as in mass concrete in foundation of poles complete all as soecified.
Material and labour for PCC 1:3:6 type D-2 using 20mm graded broken stone aggregate as in mass concrete in foundation of stays complete all as soecified.
S&F in replacement heavy duty aluminium thimble of size 185 to 240 sqmm complete all as specified
S&F in replacement heavy duty aluminium thimble of size 300 to 400 sqmm complete all as specified
Supply & Install in replacement factory made outdoor type dust and vermin proof(IP 54 protection) feeder Pillar LT Panel board cubicle double door hinged type of suitable size 415V AC, 50Hz, fabricated of GP/CRCA sheet 3 mm thick machine pressed and angle iron frame 50mm X 50mm X 6mm grouted in PCC 1:2:4 type BI (20mm grade stone aggregated) powder coated in Nine Tank process inside and outside complete including 4 Pole aluminum Bus Bar of suitable size mounted on porcelain insulator ,concealed hinged door with 3Positioning door locking arrangement and enclosed in chamber made out of 2mm sheet thick GP/ CRCA sheet machine pressed and connection from incoming and outgoing electric cable with suitable size thimbles/lugs cable gland with open able shutters on both side and comprising of following
(i)MCCB160 Amps 25KA 4pole 415V as a incomer-01 (iv) MCCB 25 KA 4P 63A -02 (iv) MCCB 25 KA 4P 100A -01 (v) Aluminium Busbar of 250 Amps phase+Nutral (vi)Ammeter and volt meter of suitable size (e) Indicating lamp ( set of three RYB) -01 set Note:- Existing Old/Unserviceble Panels including accessories are removed and deposit to MES Store yard by the contractor from his own arrangement without any extra cost.
S&F in replacement heavy duty aluminium thimble of size 70 to 95 sqmm complete all as specified
Supply and fill up transformer oil topping up having dielectric strength not less than 40 KV at 4 mm gap conforming to IS complete all as specified and directed.
Supply, installation, commissioning in replacement and testing in replacement of switch Air break, Gang operated with 12 insulator switch Triple pole, mechanicaly operated, mounted on insulator and steel frame, for current rating 200 Amp operating Voltage 11 KV out door, vertical mounted type, complete with locking arrengement, assembly with fuse mount carrier and fuse element of required capacity and isolater suitable for 11 KV including necessary electric connection and 11 KV fuse (drop out type) of capacity 10 Amp, with DO fuses assembly and one No. operating Rod of 25 mm dia bore medium grade GI pipe of suitable length, worked out from ground level and handle complete with lock and two Nos keys incl flat iron clamp 50mm x 6mm MS channel of suitable size & length for fixing GOD including nut, bolt, washers including taking down existing unservicable set all as specified and directed.
Supply and Install in replacement of factory made outdoor type dust and vermin proof feeder Pillar LT Panel board cubicle double door hinged type of suitable size 415V AC, 50Hz, fabricated of GP/CRCA sheet 3mm thick machine pressed and angle iron frame 50mm X 50mm X 6mm grouted in PCC 1:2:4 type BI (20mm grade stone aggregated) powder coated in Nine Tank process inside and outside complete including 4 Pole aluminum Bus Bar of suitable size mounted on porcelain insulator ,concealed hinged door with 3Positioning door locking arrangement and enclosed in chamber made out of 2mm sheet thick GP/ CRCA sheet machine pressed and connection from incoming and outgoing electric cable with suitable size thimbles/lugs cable gland with open able shutters on both side and comprising of following
(i) MCCB 315 Amps 36KA 4pole with microprocessor release adjustable type of as a incomer-01 (ii) MCCB 25 KA 4P 63A -01 (iii) MCCB 25 KA 4P 100A -04 (iv) MCCB 25 KA 4P 160Amp -01 (v) Aluminium Busbar of 500 Amps phase+Nutral with insulated (vi) Digital Ammeter and volt meter of suitable size Note:- Existing Old/Unserviceble Panels including accessories are removed and deposit to MES Store yard by the contractor from his own arrangement without any extra cost.
Supply and fixing in replacement LED type street light fitting pressure die cast aluminium housing IP 66,Operating Voltage 140-270 Volts, PF (0.95),with lens,Surge Voltage Protection of luminaires 90 watt LED 5700K complete fitting.
S&F in replacement loop type porcelain white, brown or green small size with cover dimensions of 65x 90 mm clearance of whole 16 mm as specified and directed by Engr-in charge.
Replacement of pin type porcelain white, brown or green insulator including one galvanized mild steel spindle, two galvanised iron washers & one galvanised nut 50mm height,65mm dia for working pressure 1100 volts grade.all as specified and directed by Engr-in charge
Supply and erect steel tubular swaged poles complete with cast iron base plate, final taper plug, bolts nuts & screws as specified type 410 SP-31 ( 9 mtr long) erecting in position all as specified and as directed by Engr-in-Charge
M & L in replacement cross arms bracings supports clamps and back plates fabricated from structural steel sections including nut bolts washers welding bending cold and hot drilling holes for bolts in any shape or size as indicate or directed and inclusive of one primer coat one under coat and one finishing coat of paint.
M & L in replacement Pre stressed concerete pole 9 mtr long of cross section of 102mm x 172mm at top and 102mm x 279 mm at bottom class 10 complying with requirement of IS-1678-1978 including painting of poles with two coats of synthetic paint in black & white step each upto 1.5 mtr high from coping over a coat of primer including numbering of poles as directed. Note:- (i) Exavation and foundation will be paid and measure separetly.
Material and labour in replacement for ACSR conductor any size drawn straight horizontal on over head lines on existing poles including binding with insulators weight of conductor shall be measured straight horizontal distance between centre of two adjacent HT/LT poles and calculating weight of conductor of size length by adding 3% extra for sag jointing jumpers etc complete all as specified and directed.
S & F in replacement straight through joint heat shinkable suitable for 3 core 11000 volts XLPE HT UG cable of size 120 Sq mm to 185 Sq mm complete all as specified and directed.
S & F in replacement End termination joint heat shrinkable of any size suitable for 3 core 11000 volts XLPE HT UG cable of size 120 Sq mm to 185 Sq mm complete all as specified and directed.
Supply & fixing in replacement of MCCB Capacity 35 KA 4 pole 400 Amps adjustable thermal magnet to release type with preader and aluminium lugs all as required at site.
All as per item 57 above but 250 Amp 25 KA
All as per item 57 above but 200 Amp 25 KA
All as per item 57 above but 100 Amp 25 KA
Supply and install in replacement LT feeder piller panel outdoor type CPRI approved made out of 3.00mm thick CRCA sheet, weather and vermin proof with both side openable, from front side & back having, locking arrangement on both sides,mounted over 50x50x6 mm angle iron stand at the bottom of height not less than 45 cm above ground level and not less than 30 cm in ground / floor mounted duly grouted in PCC 1:2:4 (using 20mm graded stone aggregate) factory made duly powder coated including taking out of old U/S panel comprising of following :-
(i) MCCB TPN 100 amps 415 volts as main incoming -01 Nos. (iv) Automatic quartz time switch 3 Phase -02 Nos (ii) MCB TPN 63 amps 415 volts 16 KA -02 Nos (iii) Bus bar suitable for 200 Amp capacity made out of Aluminium strip Note:- Existing Old/Unserviceble Panels including accessories are removed and deposit to MES Store yard by the contractor from his own arrangement without any extra cost.
Supply laying in replacement & testing cable XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable (Heavy duty_) LT 1100 volt grade with stranded aluminium conductor of size 300 sqmm 3.5 core complete all as specified and directed.
Supply & fixing in replacement of lighting arrestor metal oxide type gap less hreavy duty single pole suitable for rated system voltage 12 KV and working rated 9 KV normal discharge.
Material and labour in replacement of LT fire resistant PVC self adhesive electrical insulaion tape high quality size minimum 18 mtr long x 1.8 CM width complete.
Material and labour in replacement of fire resistant PVC double side self adhesive compound tape for water proof electrical insulaion high quality size minimum width 9 inch complete all as specified.
Supply and laying or fixing in replacement 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 10 Sqmm cable standard conductor cable flat or circular all as specified and directed by Engineer- in- Charge.
Supply and laying or fixing in replacement 1100 Volts grade heavy duty cable with PVC insulated aluminium standard conductor served with an inner sheathing of PVC tape and over all PVC Sheathed in service connections , one twin core 16 Sqmm cable standard conductor cable flat or circular all as specified and directed by Engineer- in- Charge.
Material and Labour straight through joint heats shinkable suitable for upto 50 sqmm LT 3.5 core 1100 volts XLPE cable type complete all as specified and directed.
Material and Labour straight through joint heats shinkable suitable for 70 sqmm to 120 sqmm LT 3.5 core 1100 volts XLPE cable type complete all as specified and directed.
Material and Labour straight through joint heats shinkable suitable for 185 sqmm to 300 sqmm LT 3.5 core 1100 volts XLPE cable type complete all as specified and directed.
Supply and fixing LED type street light fitting pressure die cast aluminium housing(Heat sink)for effective thermal management,IP 66,Operating Voltage 140-270 Volts, with Lens and Surge Voltage Protection of luminaires 60 watt LED 6000K complete fitting including 1.50mtr(minimum) 2core PVC insulated aluminium cable from conductor to street light fitting all as specified.
Supply and fixing street light bracket made out of GI pipe 40/32 mm suitable for 60watt LED Street light, medium grade 1.2 mtr long made to shape with fixing clamps of MS flat 40x6mm nut bolts etc for street light all as specified and directed
Supply and laying GI steel tubing, 100/80mm bore, light grade with all fittings, laid in trenches / under roads / along pole / wall for protection of Cable / GI wire / GI strip etc complete all as specified and directed.
Opening up the top cover of the transformer by taking out the transformer oil in a separate container after disconnecting/ taking out the HT/LT side electric connections from both the primary & secondary side of the transformer of any type/ description (indoor/outdoor type ) installed on floor/pole for carrying out necessary repair/rewinding to HT/LT side or any other repair as required after shifting the transformer to contractor's work shop including taking out complete core assembly, Magger the winding for identifying the fault/defective winding, seggregating the defective winding portion/taking out, cleaning the laminated core rewinding with appropriate gauge winding wire of existing description for transformer of capacity 200 to 315 KVA including assembling & testing on completion & installation the same at the site all as specified and directed by Engr-in-charge. Note : (i) Winding of coil and spares required as per repair shall be measured and paid separately under respective items. (ii) The transpotation charges and taking down/taking up of transformer are inclusive in the quoted rates. (iii) The cost for the dehydration of transformer oil if reqd shall be measured & paid separately. (iv) The cost of insulation material such as paper, cotton tape , latheroid sheet , casl sheet etc are inclusive in the quoted rate. (v) Transformer shall be returned duly repaired within 05 days failing a penal recovery (Lump Sum) of Rs 5000/- shall be made from contractor's dues.
Supply and fixing, in replacement, HT coils made out of super enameled double paper coated (DPC) HT copper winding wire of transformers, capacity 200 to 315 KVA, coils to be repalced as per existing number of turns, gauge, insulation value matching with manufactures design complete all as specified.
Supply and replacement of LT coils made out of super enameled LT copper strip of trasformer capacity 200 to 315 KVA(Note coil to be replaced shallhave same number of turns,gauge,insulation value matching with manufactures design
Supply and replacement HT 11 KV bush rod suitable for indoor / outdoor type 200 to 315 KVA transformer complete with brass stud, brass nuts, brass cup and packing gasket complete all as spd and directed.
Supply and replacement brass stud for LT side suitable for transformers 200 to 315 KVA.
Supply and replacement temperature gauge 0-100 degree Celsius range round type complete all as specified and directed.
Rubbing/scratching old paint of transformer of capacity 200 to 315 KVA, through cleaning with kerosene oil and providing two coats of metallic paint including writing MES No on Transformer body with black paint complete all as specified and directed.
Cleaning, dehydration/ reconditioning of transformer oil different location by dehydration plant including testing as per IS Specification and result not less than 40 KV at site, complete all as specified and directed by Engineer-in-Charge.
Shifting of transformer from one place to other place within the cantt area including disconnecting and reconnecting all connection any time any capacity all as directed by Engr in charge.
Taking out and transporting defective transformer pole mounted/rested on platform for repairs after disconnecting from both HT/LT network and shifting to workshop from NAMS area Sub Stn for repairs of cap 200 to 315 KVA. (Complete manpower and necessary transport/T & P shall be contractors own arrangement at no extra cost) complete all as specified and directed.
Transporting and Re-installation only of repaired transformer of capacity 200 to 315 KVA at NAMS area including necessary connections with HT/LT net work. (complete manpower and necessary transport/T & P shall be contractors own arrangement at no extra cost complete all as specified and directed.
Labour for drilling hole under the road with the help of drilling machine without damaging the road horizontally for road crossing GI tubing of any size for cable protection complete all as specified and directed.
Material and labour for sand cushioning with a layer of fine sand 8 cm thick before laying the cable and 15 cm after laying the cable in trenches to cover under ground cable complete all as specified and directed. Note :-Punned down thickness of sand shall be considered for measurement.
Supply and laying un-reinforced precast concrete cable cover factory made, class HV, type I, flat of size 300mm x 180mm x 40mm complete all as specified and directed.
Excavation in trenches in soft/ loose soil not exceeding 1.50 m wide and not exceeding 1.50 m in depth for foundation of poles, stay, cable, pipes etc and getting out complete all as specified.
Returning, filling, including spreading, leveling, watering and well ramming in layers not exceeding 25cm thick each complete all as specified.
Removal of surplus spoil to a distance not exc. 50m and depositing where directed at a level not exc. 1.5m above the starting point complete all as specified.
Material & labour for painting to mild steel cross arms, bracing, supports, clamps, back plate etc fixed on HT/LT Poles any height with providing two coats of aluminium paint over a coat one coat of red oxide primer complete all as specified and directed. Note:- Steel members fixed on single HT/LT pole shall be considered as 'One Unit'.
CHINAR ENGINEERS AND BUULDERS
Raman Electric Trading Co
Bharat Builder
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .