PE(EnM)
RRSTN
Providing three phase and neutral (440 V) power supply with safety feature to operate washing equipments to clean HEMM for compliance of CTO and Wiring of lighting circuit arrangement in lower and upper shed situated in RR shop Tapin under Hazarib
2024_CCL_303992_1
PO/RRSTN/EnM/Tender/23-24/09
Open Tender
Electrical and Maintenance Works
Item Rate
10 days
RRSTN
Please refer Tender documents.
2 documents required · 2 mandatory
₹6,000
13 Apr 2024
6 Mar 2024
19 Mar 2024
7 Mar 2024
18 Mar 2024
7 Mar 2024
7 Mar 2024 - 11 Mar 2024
Amount
Supplying and fixing metal box of 200 mm X 125 mm X 60 mm deep sizes (nominal size) on surface or in recess with suitable size of phenolic laminated sheet cover in front including painting etc as required.
Supplying and fixing of 5/6 amps switch piano type switch/ socket on the existing switch box/ cover including connections etc. as required.excavation & refilling etc as required.
Supplying and fixing of15/16 amp piano type switch/ socket on the existing switch box/ cover including connections etc.
Supplying and fixing of 3 pin 5/6 amp socket outlet piano type switch/ socket on the existing switch box/ cover including connections etc. as required.
Supplying and fixing of 6 pin 15/16 amp socket outlet piano type switch/ socket on the existing switch box/ cover including connections etc. as required.
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load as required .Single pole and neutral. in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply and erection of approved make safe earthing electrode consisting pipe-inpipe technology as per IS 3043-1987 made of corrosion free G.I. pipes with constant ohmic value surrounded by highly conductive compound with high charge dissipation suitable for effective and maintenance free earthing in earth pit of minimum bore dia. 150mm size, as mentioned below : With 3 metre G.I. pipes having outer pipe dia of 50mm having 80-200 micron galvanizing, Inner pipe dia. of 25mm having 200-250 Micron galvanizing, connection terminal dia. of 12mm in nominal soil with 50 kg (two bag) back filling bentonite compound UL listed and confirm to relevant International/Indian standards around electrode upto ground level.
Supply & fixing 63 Amp. Four pole main switch
Supply & fixing Copper Tubular Lug
Supply & fixing Lightning Conductor
Supply & fixing PVC Flexible Electrical Conduit
Supply & fixing 10 Sq mm Single core 1100 V PVC insulated cable
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 4 X 6 sq. mm + 2 X 6 sq. mm earth wire
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 2.5 sq. mm + 1X 2.5 sq. mm earth wire
Supply & fixing 10 mm X 25 mm long tinned brass bolt with nut etc
Supply & fixing D iron clamp
Supply & fixing 100 W LED Flood Light
Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required. 15/16 amp switch
Wiring for circuit/ submain wiring alongwith earth wire with the 4 X 4 sq. mm + 2 X 4 sq. mm mm earth wire sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required
Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire
Supplying and fixing following piano type switch/ socket on the existing switch box/ cover including connections etc. as required.6 pin 15/16 A socket outlet
Supply and fixing of 100 amps ICTP switch with fuse grips on existing board
Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required
Supplying and fixing brass batten/ angle holder including connection etc. as required
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required Double pole
Total impact of GST for the purpose of CTC
M/S SANYUKTA ENTERPRISES
AHSAN AHMAD
stage.html
html • 0.03 MB
tech_eval.pdf
fin_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .