Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹26.6 LAccepted-AOC | L1 | Accepted-AOC L1 | |
| 2 | L2₹31.7 L+₹4.4 L (16.1%)Rejected-Finance INDEX NO E 29 CWE JRC 352 3 GURU NANAK PURA EAST JALANDHAR CITY PIN 144001 | JALANDHAR CITY | JALANDHAR | PUNJAB | 144001 | L2 | Rejected-Finance Other than lowest. |
Tender Value
₹25.5 L
EMD Value
₹51,000
Closing Date
24 Oct 2022, 6:00 pmClosed
GE AF Adampur
Military Engineer services Air Force Stn Adampur 144103
REPAIR / REPLACEMENT OF ELECTRIC WIRING, LIGHT FITTINGS, AND ELECTRIC FANS IN TECH AREA INCL BD-I, II AND III AT AF STN ADAMPUR
2022_MES_554314_1
GE/AF/ADM-31/2022-23
Open Tender
Civil Works
Item Rate
180 days
Under GE AF Adampur
Refer NIT and Tender Documents
9 documents required · 9 mandatory
₹500
GE AF Adampur
₹51,000
Yes
26 Nov 2022
26 Sept 2022
25 Oct 2022
26 Sept 2022
24 Oct 2022
11 Oct 2022
27 Sept 2022 - 10 Oct 2022
Amount
Point wiring with multi-stranded copper conductor, single core, PVC insulated and unsheathed cable, including PVC insulated unsheathed stranded copper conductor single core cable as earth continuity conductor to common earth and connected to earth dolly, with and including GI terminal boxes with 3 mm thick plastic laminated sheet cover having necessary cutting for fixing switches/ sockets comprising the following: -
One light point controlled by one switch or one fan point controlled by one switch & fan regulator etc. or for bell/buzzer with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
One Socket outlet three pin, 6 Amp, on the same board, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, all as specified.
One Socket outlet three pin, 6 Amp, independent, with 1.5 Sq. mm (nominal area) cable & 1.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC heavy duty concealed conduit all as specified.
One socket outlet three pin, 6/16 Amp, independent, with 2.5 Sq. mm (nominal area) cable & 2.5 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
One socket outlet three pin, 6/16 Amp, independent, with 4 Sq. mm (nominal area) cable & 4 Sq. mm (nominal area) cable as earth continuity conductor, in and including rigid non metallic PVC medium duty concealed conduit all as specified.
NOTES: (a) Switch(es) & socket(s) shall be measured & paid for separately under respective item of Schedule 'A'. (b) GI boxes shall be fixed flush to walls in position with cement mortar (1:4) complete all as directed. (c) Conduit shall be laid on surface in case of RCC ceiling surfaces.
Switch piano flush button single pole one way, 6 Amp complete all as specified.
Switch piano, bell/buzzer push, flush button single pole one way, 6 Amp complete all as specified.
Switch piano flush button single pole one way, 16 Amp complete all as specified.
Socket outlet multipurpose having provision for 2&3 pin, 6 Amp, flush type, complete all as specified.
Socket outlet multipurpose having provision for two-in-one 3 pin 6 Amp & 3 pin 16 Amp, flush type complete, all as specified.
Ceiling rose, surface bakelite, 65 x 50mm, three terminals complete, all as specified.
Lamp (angle) holder, insulated body, cord grip pattern, complete, all as specified.
Electric buzzer AC 230 volt, single pole, Ding Dong type complete, all as specified.
Fan regulator (electronic) suitable for 48”/56” sweep fan, step down type, single phase, IN REPLACEMENT, complete all as specified.
Sub main wiring (with approved colour coding as per IS) with single core FRLS PVC insulated flexible stranded copper conductor 1.1 KV grade (main cable: number of runs as indicated below along with single core FRLS PVC insulated flexible stranded copper conductor 1.1 KV grade for earthing in conduits, complete all as specified for the following: -
2 runs of 2.5 Sq. mm main cable + 1 run of 2.5 Sq. mm earth cable
2 runs of 4 Sq. mm main cable + 1 run of 4 Sq. mm earth cable
2 runs of 6 Sq. mm main cable + 1 run of 6 Sq. mm earth cable
NOTES: (i) Conduit & conduit accessories shall be measured & paid for separately. (ii) For payment purposes, total runs of main cable (each run of one running metre) as mentioned above and one run (one running metre) of earth cable shall be considered together as "1 RUNNING METRE"
Rigid non metallic, PVC concealed conduit, 20 mm bore, medium grade, ISI marked, inclusive of all fitings (such as junction boxes, bends, elbows, tees, reducers, bell mouth tube ends) and all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. for sub main wiring and the like complete all as specified.
ERW rigid conduit stove enamelled surface conduit including necessary conduit acessories like flame proof junction box(es), bend(s), reducer(s) and unions etc, ISI marked, all fixing acessories such as couplers, lock nuts, saddles, pipe hook etc. suitable for flame proof sub main wiring complete all as specified.
Sheet metal enclosure for DB for fixing MCB’s, isolators etc., having IP-43 protection, suitable for surface and flush mounting, complete all as specified comprising the following: -
SPN, 2 way with 200 Amp rated bus bar, 240 V, single door type
SPN, 4 way with 200 Amp rated bus bar, 240 V, double door type.
SPN, 8 way with 200 Amp rated bus bar, 240 V, double door type.
SPN, 12 way with 200 Amp rated bus bar, 240 V, double door type.
TPN, 4 way with 200 Amp rated bus bar, 415 V, double door type.
TPN, 4 way with 200 Amp rated bus bar, 415 V, double door type having housing and including MCCB 4 pole 63 Amp, 16kA.
MCB suitable for 240 volt AC supply, SP with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 6 to 32 Amp complete all as specified.
MCB suitable for 240 volt AC supply, SPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 40 Amp complete all as specified.
MCB suitable for 415 volt AC supply, TPN with over load and short circuit protection and rupturing capacity not less than 10 kA, 'C' curve type of rating 63 Amp complete all as specified.
Blanking plate to cover unused space in DB's complete all as specified..
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB 20 Amp, 240 volt, breaking capacity not less than 10 kA, IN REPLACEMENT, complete all as specified.
Earthing with and including GI earth plate electrode 6 mm thick of size 600 mm x 600 mm with 4 Sq. mm GI wire earthing lead complete all as shown in electrical plate No. 3 and specified in Particular Specifications clause 3.3.1 of contract, IN REPAIR. NOTE: (a) The unit rate includes earthing lead and protection pipe upto 7.5 metre from top of earth plate. (b) Factory made PCC pit with cover shall be fixed at least 500 mm away from earth pit.
Envirnment friendly, energy saving surface mounted, decorative 10 W bulk head LED luminaire with premium quality diffuser fo glarefree light, 6000K complete. MAKE: Havells Cat No. RUGBYGENXFTS10WLED865SSYMBOPC or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface mounted envirnment friendly decorative ultra slim round profile LED 10 W lighting fixture with extruded polycarbonate, 6500K, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. ENDURALINEARNEOBS10WLED865SPCWH or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface mounted envirnment friendly decorative ultra slim round profile LED 18 W lighting fixture with extruded polycarbonate, 6500K, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. LUMILINEPLUSNEOBS18WLED865SPCSSIND or equivalent in makes mentioned in Appendix 'B' here-in-after.
Surface mounted envirnment friendly decorative ultra slim round profile LED 22 W lighting fixture with extruded polycarbonate, 6500K, lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. ENDURALINEARNEOBS22WLED865SPCWH or equivalent in makes mentioned in Appendix 'B' here-in-after.
Recess mounted bottom opening LED 36W cool day light luminaire (2x2) CRCA powder coated housing, IP- 54 protection, suitable for grid ceiling lumen output should not be less than 90 lumens per watt complete. MAKE: Havells Cat No. DROPDOWNFLAT2X2PLR36WLED857 or equivalent in makes mentioned in Appendix 'B' here-in-after.
LED flood light fitting 60 watt presssure diecast aluminium housing with toughened glass & igh power LEDs and secondary lenses with, IP 66 protection, and making connection from junction box to connector block with provision of 1.5 Sq. mm PVC insulated unsheathed multistranded FRLS copper conductor cable complete. MAKE: Havells Cat No. JETAQUANTOPLUSFLP60WLED757SYMLENS or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof Point wiring with 1.5 Sqmm nominal area PVC insulated unsheathed multistranded copper conductor cable in and including ERW rigid conduit stove enamelled surface conduit for one light point / Fan point / 6Amp multipurpose switch socket with and including necessary conduit acessories like flame proof junction box(es), bend(s), reducer(s) and unions etc, independent for one light point controlled by one (MCB) including 1.5 Sqmm nominal area PVC insulated unsheathed multistranded copper conductor cable for earth wire to common earth and connected to earth dolly complete all as specified.
Flame proof LED light fitting 70 watt , CMRI certified recommended suitable for gas/vapur of IIA & IIB and Zone 1& 2 having IP-65 protection with die cast aluminium housing with heat resistant toughened glass with driver, holder, connector etc complete suitable for fixation on wall/roof including connecting up with three core suitable size twisted flexible copper conductor with complete. MAKE: SHYAM Cat No. SSPL/1233 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof tube LED light fitting 2x 16 watt with & including LED tube 16W each, CMRI certified recommended suitable for gas/vapur of IIA & IIB and Zone 1& 2 having IP-65 protection with die cast aluminium housing with heat resistant toughened glass with driver, holder, connector etc complete suitable for fixation on wall/roof including connecting up with three core suitable size twisted flexible copper conductor with complete. MAKE: CROMPTON Cat No. EXTN2LT8-16 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof weather proof LED flood light fitting100W Gas group: IIA, IIB,& IIC Exd IIC,having IP-65 protection, IN REPLACEMENT, complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/FL/1251 or equivalent in makes mentioned in Appendix 'B' here-in-after.
LED Set & driver only IN REPLACEMENT, of Flame proof weather proof LED flood light fitting 100-120W Gas group: IIA, IIB,& IIC Exd IIC,having IP-65 protection, complete. MAKE: As per Shyaam Switchgear Pvt Ltd. Cat No. SSPL/FL/1251 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof weather proof rotary switch, single pole on & off with cable termination box in LM6, 16 Amp rating, 250 volt complete. MAKE: Sudhir Cat No. RI/OA/1010-2A or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof weather proof rotary switch-socket and plug combination in LM6, three pin (two pole earth) with cable termination enclosure box, 16-25 Amp rating, 250 volt complete. MAKE: Shyaam Switchgear Pvt Ltd. Cat No. SSPL/SS/1010 or equivalent in makes mentioned in Appendix 'B' here-in-after.
Flame proof stepped type electronic fan regulator, having IP-65 protection, IN REPLACEMENT, complete.
Collecton of items like ceiling fans, exhaust fans, wall mounted fans, cabin/table fans, flame proof ceiling fans from EM store yard for repair, transporting to workshop, opening and reassembling after including necessary cleaning greasing oiling etc, testing and depositing back to EM store yard of GE (AF) Adampur including necessary loading unloading and transporting etc. complete. NOTE: Supply only spares & rewinding of fan(s) shall be measured & paid for separately under respective items of BoQ.
Rewinding fan of any description with super enamelled copper winding wire of size, gauge & weight as per original specifications providing insulating material and varnishing with synthetic varnish, oiling, greasing including replacement of bush/bearing, condenser, 'U' clamp with reel to the entire satisfaction of Engineer-in-Charge including taking out burnt winding wire after opening the ceiling fan and other unserviceable parts, of size: -
Ceiling fan 1200 mm sweep
Ceiling fan 1400 mm sweep
Exhaust fan 300 mm sweep
Exhaust fan 450 mm sweep
Wall mounted fan 650 mm sweep
Cabin/table fan 450 mm sweep
Flame proof wether proof ceiling fan any sweep & description
Flame proof wether proof exhaust fan any sweep & description
NOTE: Collecton of fan items from EM store yard, transporting to workshop and back including loading unloading shall be measured & paid for separately under respective items of BoQ.
Taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete with batten, casing caping of MS or and PVC conduit on surface or concealed, including switches, ceiling roses, pendants, regulators, sockets, mild steel terminal boxes etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge, complete all as specified.
Taking down carefully copper/aluminium sub main wiring complete, including existing batten/conduit consealed/surface etc., removing materials and making good disturbed surfaces due to taking down etc. to the entire satisfaction of Engineer-In-Charge, complete all as specified.
Dismantling of unservisible existing DBs of any description with all accessories and MCBs, isolators etc. and making good surface as per existing, complete all as specified.
Taking down carefully light fitting of any description, complete all as specified.
Taking down carefully electric bell/buzzer of any description, complete all as specified.
NOTES APPLICABLE TO SERAL ITEM NO. 1TO 41:- (i) To maintain utmost security at AF Station, contractor will arrange his workmen along with T&P in a manner that nonfunctional is made functional swiftly within 24 hour of receiving of complaint from the MES, during entire contract period. (ii) Not withstanding with the provision of "Compensation for Delay' envisaged under condition 50 of IAFW-2249, General Conditions of Contracts, additional compensation @ Rs. 500/- day will be charged from contractor in case he fails to make the functional to the entire satisfaction of Engineer-in-Charge within 24 hour of receiving of complaint from the MES regarding non working.
Northern cable fault locatoers
stage.html
html • 0.04 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .