Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹35.0 LAccepted-AOC 114 SHASTRI NAGAR MEERUT | MEERUT | UTTAR PRADESH | 245206 | L1 | Accepted-AOC BEING LOWEST AND REASONABLE | |
| 2 | L2₹39.4 L+₹3.5 L (9.61%)Rejected-Finance C O T ALI NEAR TRIPURA CASTLE ROAD CLEVE COLONY SHILLONG 793003 MEGHALAYA | EAST KHASI HILLS | MEGHALAYA | 793003 | L2 | Rejected-Finance OTHER THAN LOWEST | |
| 3 | L3₹41.0 L+₹5.0 L (14.0%)Rejected-Finance RONGMEN B IV BARAPANI PO SHILLONG 793103 | RI BHOI | MEGHALAYA | 793103 | L3 | Rejected-Finance OTHER THAN LOWEST | |
| 4 | L4₹42.2 L+₹6.2 L (17.3%)Rejected-Finance | L4 | Rejected-Finance OTHER THAN LOWEST | |
| 5 | L5₹43.5 L+₹7.6 L (21.1%)Rejected-Finance | L5 | Rejected-Finance OTHER THAN LOWEST |
Tender Value
₹35 L
EMD Value
₹70,000
Closing Date
3 Jun 2024, 6:00 pmClosed
GE UMROI
Military Engineer Services Garrison Engineer Umroi Umroi Military Station PO - Barapani, Shillong-793 103
REPAIR / MAINTENANCE AND IMPROVEMENT OF LT PANEL AND ALLIED WORKS AT UMROI MIL STN UNDER GE UMROI
2024_MES_651305_1
8828
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
UMROI
AS PER NIT
8 documents required · 8 mandatory
₹500
GE UMROI
₹70,000
13 Jul 2024
26 Apr 2024
4 Jun 2024
26 Apr 2024
3 Jun 2024
10 May 2024
Amount
Excavation in trenches n.exc 1.5m wide and n.exc 1.5m in depth for foundation of pole and laying of UG cable and getting out soft/loose of soil, complete all as specified and directed.
Returning filling in and including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and directed.
Removing excavated material to a distance n.exc 50m and depositing where directed at a level n.exc 1.5m above the starting point , complete all as specified and directed.
M&L for PCC 1:3:6 type C-2 (using 40 mm graded stone aggregate) as in foundation filling of pole and mass concrete for stay, complete as specified and directed.
M&L for PCC 1:2:4 type B-1 (using 20 mm graded stone aggregate) for copping of pole, as in benching and finished exposed surface even and smooth including necessary form work, complete as specified and directed.
Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade, cross sectional area of size 120 sq mm 3.5 core including taking down of ACSR/old cable, complete all as specified directed.
Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade, cross sectional area of size 95 sq mm 3.5 core including taking down of ACSR/old cable, complete all as specified directed.
Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade, cross sectional area of size 50 sq mm 3.5 core including taking down of ACSR/old cable, complete all as specified directed.
Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade, cross sectional area of size 35 sq mm 3.5 core including taking down of ACSR/old cable, complete all as specified directed.
Supply, laying, testing & commissioning UG cable XLPE insulated,armoured heavy duty electric cable with aluminum conductor,1100 Volts grade, cross sectional area of size 25 sq mm 4.0 core including taking down of ACSR/old cable, complete all as specified directed.
M&L for sand cushioning in trenches for protection of under ground cable 8 cm before laying the electric cable and 15 cm after laying the cable and punning down, complete all as specified & directed. Note : For the purpose of payment only punned thickness will be measured.
M&L for common burnt clay building bricks (locally available best quality), sub-class ‘B’ designation 75 of size 230x115x75 mm to cover LT underground cables , laid dry and flat complete all as specified and directed.
S&F GI light grade tube of size 40 mm bore with all fittings laid in trenches/ wall for protection of cable complete all as specified and directed.
S&F GI light grade tube of size 50 mm bore with all fittings laid in trenches/ wall for protection of cable complete all as specified and directed.
S&F GI light grade tube of size 80 mm bore with all fittings laid in trenches/ wall for protection of cable complete all as specified and directed.
S&F GI light grade tube of size 100 mm bore with all fittings laid in trenches/ wall for protection of cable complete all as specified and directed.
S&F GI strip of earthig and making proper earth testing point from pole ,panels and transformer of size(32x6mm) complete all as specified and directed.
S&F aluminium strip of earthig and making proper earth testing point from pole ,panels and transformer (size not less than 25x3.15mm) complete all as specified and directed.
S&F cable End termination joint suitable for 1100 volt grade LT cable, outdoor type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5/4 core XLPE LT cable of size 70 sqmm to 150 sqmm complete all as specified and directed.
S&F cable End termination joint suitable for 1100 volt grade LT cable, outdoor type terminal heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5/4 core XLPE LT cable of size 185 sqmm to 300 sqmm complete all as specified and directed.
M&L for straight through LT joint kit suitable for LT cable, 1100 volt, heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5 core cable of size 70 sqmm to 150 sq mm complete all as specified and directed.
M&L for straight through LT joint kit suitable for LT cable, 1100 volt, heat shrinkable type joint complete with all jointing material and accessories suitable for 3.5 core cable of size 185 sqmm to 240 sqmm complete all as specified and directed.
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 m below normal ground level. connecting to the Galvanised iron earth wire 4.0mm dia by means of bolls, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 15mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) type B-1 including reinforcement (8mm dia @ 100 c/c bothway) and one handle of 6mm dia MS bar made to shape, GI medium grade 20mm bore pipe for watering , perforated at bottom. 1.75 metre long placed on top edge of earth plate. charcoal and common salt filled 150 mm thick all around the earth plate with fixing arraangement, funnel wire mesh and earth work in any type of soil returing filling in and removal of surplus soil to a distance not exceeding 50 meters all as per electical plate 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion.
M&L for Earthing complete with galvanised steel earth plate electrode 60 cm x 60cm x 6mm thick buried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5m below normal ground level. connecting to the Galvanised iron earth strip 32x6mm size by means of bolls, nuts, check nuts and washers of galvanised iron and earth wire protected by provision of GI medium grade pipe 40mm bore including provision of concrete pit in PCC (1:2:4) type B-1 using 20mm graded stone agregates with 40mm thick cover of RCC (1:2:4) type B-1 including reinforcement (8mm dia @ 100 c/c bothway) and one handle of 6mm dia MS bar made to shape, GI medium grade 20mm bore pipe for watering , perforated at bottom. 1.75 metre long placed on top edge of earth plate. charcoal and common salt filled 150 mm thick all around the earth plate with fixing arraangement, funnel wire mesh and earth work in any type of soil returing filling in and removal of surplus soil to a distance not exceeding 50 meters all as per electical plate 3 of SSR-2009 Part-I and connecting to earth test point all as specified or indicated including testing on completion.
Supply, install, testing and commissioning outdoor type LT panel of suitable size , CPRI approved factory made totally enclosed dust and vermin proof , double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, angle frame size 50x50x6mm and minimum staging height not less than 0.5m duly fabricated and having proper locking arrangement in both front and rear door painted with powder coated paint and aluminium bus bar 525 amps suitable for 415 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items:- Incoming :- (a) MCCB, 4 Pole, 400A, 415 V, 35 kA.- 01 No. (b) LCD multifunction meter - 01 No (c) CTs 320/5 A - set of 3 (d) Phase indicator lamps (RYB) -set of 3 (e) Aluminium bus bar 4 strip -600 amps (f) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etc Outgoing :- (a) MCCB, 4 Pole, 100 Amp, 415 V, 35 kA - 03 Nos (b) MCCB, 4 Pole, 200 A, 415 V, 35 kA - 01 No (c) MCB, TPN, 63 A, 415 V, 16 kA - 01 No
Supply, install, testing and commissioning outdoor type LT panel of suitable size , CPRI approved factory made totally enclosed dust and vermin proof , double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, angle frame size 50x50x6mm and minimum staging height not less than 0.5m duly fabricated and having proper locking arrangement in both front and rear door painted with powder coated paint and aluminium bus bar 300 amps suitable for 415 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items:- Incoming :- (a) MCCB, 4 Pole, 400A, 415 V, 35 kA.- 01 No. (b) Phase indicator lamps (RYB) -set of 3 (c) Aluminium bus bar 4 strip of 600 Amps (d) Internal connection by aluminium strip from mcb/mccb to busbar and busbar to mccb/mcb etc Outgoing :- (a) MCCB, 4 Pole, 160 A, 415 V, 25 kA - 01 Nos. (b) MCCB, 4 Pole, 125 A, 415 V, 25 kA - 03 Nos.
Supply, install, testing and commissioning outdoor type LT panel/feeder panel of size 0.6mx0.6mx0.45m , CPRI approved factory made totally enclosed dust and vermin proof , double leaf shutter in front and single leaf shutter in rear side made of 3.15 mm thick CRCA sheet, angle frame size 50x50x6mm and minimum staging height not less than 0.5m duly fabricated and having proper locking arrangement in both ront and rear door painted with powder coated paint and aluminium bus bar 300 amps suitable for 415 volts, 50 Hz , 3 phase 4 wire system and comprising with and including following accesories and mounted on PCC platform all around the panel board complete with the following items:- Incoming :- (a) MCCB, 4 Pole, 200A, 415 V, 25 kA.- 01 Nos. (b) Aluminium bus bar 4 strip of 300 amps (c) Internal connection by aluminium strip from MCB/MCCB to busbar and busbar to MCCB/MCB etc
S&F in repair MCCB microprocessor release conforms to IS/IEC 60947-2 Ics 100% Icu ETM with in- built Earth fault protection adjustable overload 40-100% adjustable short circuit 2-12 Ir, relaese range 160-400Amp in Frame 3, 4 Pole breaking capacity Icu at 415 volt AC , 36 KA , including fixing to the existing panel board matching with the existing slots, including any alteration required and with extention links properly connected to the bus bar, complete all as specified & directed.
M&L for carrying out any repair woks to panel board LT with clearing any dent /deformation to panel cover,replacing/providing bolts,nuts with welding work etc.including making up with the existing colour paint of any type and size of panel, complete all as specified & directed.
Supply, fixing and testing indication lamps with showing red, yellow and green in colour of 22.5mm dia to monitor on panel board suitable for 240V AC supply as existing at site, complete all as specified & directed. Make: L&T/C&S/CG or eqivalent make
S&F Multifunction meters 3 phase voltage, current, frequency with communication accuracy class 1 (0.5 optional) 2 output, contact for trip LED display use on LT/HT system testing, complete all as specified and directed. Make: AE/L&T/C&S/Legrand/Hager/MECO
S&F in repair 3 Pole power contactors type ML-04 with AC3 rating of 70 Amps and AC1 rating of 100 Amps- 02 Nos. Make: L&T / Legrand / Schneider
M&L for reshifting of LT pole from one location to another along with removing from ground,dismantling of PCC and transportation from one side to another complete all as specified and as directed. Note:new location excavation and PCC &coping will be measured and paid seprately.
M&L for Aluminium Painting with one coat on 9mtr LT pole and one coat of sythetic enemal paint upto 1.5 meter above the ground level with black and yellow colour alternatively 25 cm intervel from bottom of pole along with painting of channel and angle on tubular Poles, complete all as specified and as directed
M&L for numbering on tubular pole, writing neatly on the poles 1.5 meter above ground level with letters and two to three numbers using synthetic enemal paint and letters height 100mm, complete all as specified and as directed
Schedule of Credit
M/S AKC ENTERPRISE
M/s Jaiswal and Co
M/S T N CONSTRUCTION
KB Singha and Associates
M/s A L Traders
DWEL ENTERPRISE
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .