| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹14.2 LAccepted-AOC H NO 07 SHIVAJI NAGAR PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹14.2 L Quoted ₹17.1 L | L1 | Accepted-AOC L1 |
| 2 | L2₹17.8 LRejected-Finance | ₹17.8 L | L2 | Rejected-Finance NOT BEING LOWEST |
| 3 | L3₹23.7 LRejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹23.7 L | L3 | Rejected-Finance NOT BEING LOWEST |
| Sl No | Description | Qty | Unit | satpal and brothers L3 | M/S SHAKTI ELECTRIC WORKS L1 | JANDIAL ENTERPRISES L2 |
|---|---|---|---|---|---|---|
| 1.00 | Excavation in trenches n.exc 1.5mtr wide and not exc 1.5mtr depth and getting out in any type of soil, complete all as specified and directed. | 162 | Cum | 70 ₹11,340 | 50 ₹8,100 | 60 ₹9,720 |
| 2.00 | All as per item No 1here in before but exc 1.5 mtr or part there of in depth beyond 1.5 mtr depth, complete all as specified and directed. | 8 | Cum | 200 ₹1,600 | 90 ₹720 | 95 ₹760 |
| 3.00 | Returning and filling in of excavated soil including spreading,levelling,watering and well ramming in layers not exceeding 25 cm each, complete all as specified and directed. | 120 | Cum | 5 ₹600 | 5 ₹600 | 4 ₹480 |
| 4.00 | Removal of surplus soil not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed. | 51 | Cum | 5 ₹255 | 10 ₹510 | 8 ₹408 |
| 5.00 | M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specifed and punned thickness shall be measured and paid. | 32 | Cum | 200 ₹6,400 | 300 ₹9,600 | 400 ₹12,800 |
| 6.00 | Supplying and laying un-reinforced precast concrete cable cover factory made as per IS 5820-2024, class HV,flat, type 1 , size 300mm x 180mm x 50mm etc , complete all as specified and directed. | 2,222 | Each | 15 ₹33,330 | 12 ₹26,664 | 15 ₹33,330 |
| 7.00 | Supply and erection in vertical position Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-55 (11.0 metres long) all as specified duly factory painted with two coats of black bituminous paint internally through out and externaly for embeded portion and painting with one coat of red oxide primer, applying two coats of synthetic enamel aluminium paint on remaining exposed surfaces after errection complete, painting with synthetic enamel paint of colours black and yellow alternate strips of 30cm width upto 1.5 mtr from the top of coping complete including making suitable holes where required and including dismantling of unserviceable concrete poles/ struts, any size, all as specified and directed .Note : PCC in foundation, coping, Earth work (Excavation, Returning & refilling and removal) will be measured and paid separately under relative items of Sch 'A', complete all as specified and directed. | 10 | Each | 17,000 ₹1.7 L | 13,000 ₹1.3 L | 17,000 ₹1.7 L |
| 8.00 | M&L for Plain cement concrete (1:4:8) type D-2 (Using 40 mm graded crushed stone aggregate) as in foundation for poles mass concretes or in any indicated positions etc , complete all as specified and directed. | 9 | Cum | 1,500 ₹13,500 | 2,000 ₹18,000 | 2,400 ₹21,600 |
| 9.00 | Plain cement concrete (1:2:4) type B-1 (Using 20 mm graded stone aggregate) for coping of pole, complete all as specified and directed. | 0.27 | Cum | 2,000 ₹540 | 3,000 ₹810 | 3,400 ₹918 |
| 10.00 | S&F in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, including dismantling unserviceable cross arms complete all as specified and directed. | 2 | Qtl | 6,000 ₹12,000 | 3,900 ₹7,800 | 4,300 ₹8,600 |
Updated dates
Tender Value
₹40 L
EMD Value
₹80,000
Closing Date
28 Feb 2026, 6:00 pmClosed
CWE PATHANKOT
HQ CWE PATHANKOT
CERTAIN REPAIR/MAINT OF HT OH LINES/ UG CABLES/STRUCTURES AND OTHER ALLIED SWITCHGEARS, VCBS, RMUS, PRIMARY PROTECTION RELAYS, AUXILIARY POWER SUPPLY, RE-INSULATION/ DEHYDRATION OF TRANSFORMER AND OTHER ALLIED WORKS AT DAMTAL, NANGALBHUR, KANDRORI,
2026_MES_750535_1
CWE/P-80/2025-26
Open Tender
Electrical and Maintenance Works
180 days
GE SOUTH PATHANKOT
Please refer Tender documents.
9 documents required · 9 mandatory
₹500
GE SOUTH PATHANKOT
₹80,000
28 Mar 2026
30 Jan 2026
2 Mar 2026
30 Jan 2026
28 Feb 2026
14 Feb 2026
Excavation in trenches n.exc 1.5mtr wide and not exc 1.5mtr depth and getting out in any type of soil, complete all as specified and directed.
All as per item No 1here in before but exc 1.5 mtr or part there of in depth beyond 1.5 mtr depth, complete all as specified and directed.
Returning and filling in of excavated soil including spreading,levelling,watering and well ramming in layers not exceeding 25 cm each, complete all as specified and directed.
Removal of surplus soil not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above the starting point, complete all as specified and directed.
M & L for good quality dry sand cushioning to under ground electric cable on layer of 8 cm thick before laying the cable and second layer of 15 cm thick after laying the cable all as specified in clause 19.75 of MES Schedule part-I (2009) Note : Sand shall be fined sand as specifed and punned thickness shall be measured and paid.
Supplying and laying un-reinforced precast concrete cable cover factory made as per IS 5820-2024, class HV,flat, type 1 , size 300mm x 180mm x 50mm etc , complete all as specified and directed.
Supply and erection in vertical position Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws, type 410 SP-55 (11.0 metres long) all as specified duly factory painted with two coats of black bituminous paint internally through out and externaly for embeded portion and painting with one coat of red oxide primer, applying two coats of synthetic enamel aluminium paint on remaining exposed surfaces after errection complete, painting with synthetic enamel paint of colours black and yellow alternate strips of 30cm width upto 1.5 mtr from the top of coping complete including making suitable holes where required and including dismantling of unserviceable concrete poles/ struts, any size, all as specified and directed .Note : PCC in foundation, coping, Earth work (Excavation, Returning & refilling and removal) will be measured and paid separately under relative items of Sch 'A', complete all as specified and directed.
M&L for Plain cement concrete (1:4:8) type D-2 (Using 40 mm graded crushed stone aggregate) as in foundation for poles mass concretes or in any indicated positions etc , complete all as specified and directed.
Plain cement concrete (1:2:4) type B-1 (Using 20 mm graded stone aggregate) for coping of pole, complete all as specified and directed.
S&F in replacement Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint, including dismantling unserviceable cross arms complete all as specified and directed.
M&L in replacement of ACSR conductor of any size as ordered by Engr-in-charge including tightening and binding with new binding wires to insulators, including dismantling of ACSR conductor of any size, complete all as specified and directed.
M&L in replacement pin type insulator vitreous, white, brown, or green insulator includig one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut 150 mm height, 150 mm dia for 11000 volts grade, including dismantling complete all as specified and directed.
S&F in replacement disc type insulator, porcelain, vitreous 145 mm high and 255 mm dia ball and socket type white, brown or green, single disc assembly for tension with tension clamps for conductors, working pressure 11000 Volts, including dismantling complete all as specified and directed.
M&L in replacement of anti climbing device, spikes type fabricated out of MS bars (round/square/flat) including nuts,bolts, washers and welding in two halves made to shape to suit the cross section of the pole including dismantling UNSV insulators any type, size, complete all as specified and directed.
S&F danger notice plate of 1.6 mm thick mild steel sheet, vitreous enamelled white, with letters, figures and conventional skull and bones in signal red colour and fixed with MS clamps,bolts, nuts of approved size for HT 25x20 cm size including dismantling old one, complete all as specified and directed.
Supply , install, testing and commissioning (in replacement) of HT 11 KV Switch air break, gang operated, triple pole, mechanically operated, mounted on insulators and MS channel frame, with operating mechanism made out of 25 mm dia GI medium grade pipe suitable for operation from ground level with locking arrangement complete for current rating 200 Amps, including dismantling UNSV air break gang operated switches complete all as specified and directed.
S&F in replacement expulsion fuse single phase above 50 & up to 100 AMPS capacity, 11000 Volts, complete all as specified and directed.
S&F in replacement HT lightening arrestor high tension 11000 Volts expulsion type complete with all fittings, transmission class, discharge capacity 65 kilo amp complete all as specified and directed.
M&L for fixing in repairs Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required with galvanised iron strip 32x6 mm including dismantling old one, complete all as specified and directed.
M&L for fixing in repairs Earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc. as required with 4mm dia galvanised iron or steel wire including dismantling old one, complete all as specified and directed.
Material and labour in replacement earthing with steel earth plate electrode of size 60x60cmx6mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected to galvanized iron strip of size 32x6mm as earthing lead by means of nuts, bolts and washers of steel after welding of GI strip to earth electrode to the full length of earth plate, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing)
M&L in replacement Earthing complete with galvanized steel earth plate electrode 60cmx60cmx6 mm thick buried directly in ground (Earth pit not less than 2.25 Mtr deep below normal ground level )with top edge of the plate not less than 1.5 Mtr below normal ground level connecting with galvanized iron GI earth wire 4mm dia by means of bolt nut check nuts and washers of galvanized iron and provision of GI tubing medium grade (ISI marked)of size 15mm for protection of GI earth wire upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of charcoal dust and salt layers all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, GI earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing)
Supply ,laying , testing & commissioning in replacement of HT UG cable, XLPE insulated screened PVC bedded, galvanised steel strip or wire armoured, electric power cable(heavy duty) with stranded aluminium conductor,6.35/11 KV grade (Earthed system cable) as per IS 7098 Part-II, of size 3 Core 95 Sqmm all as directed including dismantling old one, complete all as specified and directed. Note:- (a) Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection for road crossings, HT termination joints will be measured and paid separately.
M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for outdoor end termination cold shrink type joint 3 Core 50 sqmm to 95 sqmm complete with jointing material and accessories suitable for following sizes including testing after jointing complete all as directed . Note:- Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection will be measured and paid separately.
M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for Indoor end termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core 50 sqmm to 95 sqmm complete with jointing material and accessories suitable for following sizes including testing a XLPE cable including testing after jointing complete all as directed . Note:- Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection will be measured and paid separately.
M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for Indoor end termination cold shrinkable type joint complete with jointing material and accessories suitable for 3 core 120 sqmm to 185 sqmm complete with jointing material and accessories suitable for following sizes including testing a XLPE cable including testing after jointing complete all as directed . Note:- Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection will be measured and paid separately.
M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for outdoor straight through cold shrinkable type joint 3 Core 50 sqmm to 95 sqmm complete with jointing material and accessories suitable for following sizes including testing after jointing complete all as directed . Note:- Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection will be measured and paid separately.
M&L cable jointing kit for 11 KV (Earthed) grade XLPE cable for outdoor straight through cold shrinkable type joint 3 Core 120 sqmm to 185 sqmm complete with jointing material and accessories suitable for following sizes including testing after jointing complete all as directed . Note:- Earth work ( Excavation, Returning & refilling and removal), sand cushioning, concrete cable covers,GI pipe protection will be measured and paid separately.
Supply and lay GI tubes light grade 80 mm dia bore galvanised with all fittings laid in trenches etc for protection of cable complete all as specified and as directed.
M&L for painting of HT 11 KV RCC/Steel four pole structure applying one coat of zinc oxide primer on rusted portions after preparation of surfaces & a coat of aluminum paint to the entire steel structure, complete all as specified and directed.
M&L for painting of HT 11 KV RCC/Steel Two pole structure applying one coat of zinc oxide primer on rusted portions after preparation of surfaces & a coat of aluminum paint to the entire steel structure, complete all as specified and directed.
Cutting /trimming tree branches along the over head HT/LT lines up to 3.0 mtr from electric line on both sides of the span and disposing of the cut tree-branches at places, complete all as specified and directed. Note : (i) Necessary permission will be obtained from department by contractor one day prior to trimming in particuar area and shut down of that area shall be arranged by department. (ii) The overhead line shall be maintained for whole period of contract and the payment shall be made once in entire Contract period only.
M/L for restretching of HT/LT Over head line (ACSR) of any size of overhead line complete including binding with ACSR conductor near pitted conductor, complete all as specified and directed. Note: Stringing of three phase of conductor per span shall be measured and paid separately
Cutting the tarmac / hard standings and excavating in trenches across the road for laying cable including making good the excavated portion by means of PCC 1:3:6, type C1 matching with the surroundings, complete all as specified and directed.
Material & labour for fixing in repairs Stay assembly complete with accessories such as MS stay plate of size 300mmx300mmx6mm thick, stay rod 20mm dia, stay bow, nuts, bolts and check nuts of GI including GI stay strand of size 7/4 mm all as shown in electrical plate No. 1 of SSR Part-I of 2009 , complete all as specified and directed. Note: Earth work (Excavation, Returning & refilling and removal), PCC, stay clamp and loop type insulators will be measured and paid separately under relevant schedule items).
M&L in replacement for Loop type insulator large size with overall dimensions 90x140mm with clearance of hole 25.5 mm vitreous white brown or green, complete all as specified and directed including dismantling old defective.
Plain cement concrete (1:3:6) type C-2 (Using 40 mm graded stone aggregate) as in foundation filling and mass concrete for stay , complete all as specified and directed.
S&F in replacement Master Trip Relay upto 125 V DC suitable for 11 KV HT panel for protection system as per site, complete all as specified and directed.
S&F in replacement DC Supervision Relay upto 125 V DC suitable for 11 KV HT panel for pretection system as per site, complete all as specified and directed.
S&F in replacement Auxiliary Relay 110 V AC suitable for 11 KV HT panel for protection system as per site, complete all as specified and directed.
Taking down HT switch gear (Vacuum circuit breaker ) of capacity 11 KV 250/350 MVA comprising of following repairs, overhauling, servicing and refixing the same after repairs/ overhauling: (a) Tripping off the breaker, lowering the breaker with raising/lowering handle and pulling out the breaker complete from the panel along with the trolley for servicing/inspection/overhauling. (b) Servicing/Inspecting/checking of automatic safety shutter operation for serviceability and replacement of spares if required. (c)Servicing/Inspecting/checking of circuit spout and cicuit spout connections for RYB phases and replacement of spares if required.(d)Dismantling and checking of cross bar assembly, fixed contacts and current carrying parts of the breaker, trolley, insulated assembly and checking lamination with clamps, epoxy spout, isolator assembly etc. (e) Setting, reassembling, cleaning, adjustment of fixed contacts, main contact, arcing contacts and chamber baffle pot assembly, moving contact for proper setting of auxiliary contacts operating mechanism. (f) Servicing/Inspecting/checking of secondary sockets/busbar earthing plugs/earthing sockets and replacement of spares if required. (g) Checking, setting and adjustment of lowering and raising operation of the breaker trolley.
(h) Lubrication and greasing of all moving parts of the trolley, stopper bolt for proper operating and closing of shutter gear, isolation resistance of trolley of with vacuum interrupter assembly. The inspection of HT switch gear shall involve:- (i) Inspection of truck & hoist assembly. (ii) Inspection of tank assembly & barriers. (iii) Inspection of assembly & components of solenoid assembly. (iv) Inspection of assembly & components of dependent mechanism. (v) Inspection of assembly & components of spring box mechanism. (vi) Inspection of motor mechanism spring charge assembly (vii) Inspection of assembly of trip unit & related components. Notes: (i) The rate quoted shall be deemed to include for necessary T&P, nuts, bolts, washers, gasket, insulation tape, compound, painting of VCB panels with approved colour all as per exisitng etc. to put in to the VCBs and panels in serviceable condition, testing and commissioning all as specified and as directed by the Engineer-in-Charge. (ii) Major spares like Breaker bushings, vaccum interrupture assly, busbar spout, busbar spout connections, circuit spout/circuit spout connections/buffer fixed contacts, moving contacts, tank assly/barriers, solenoid spares, dependent/spring mechainsm/ motor mechanism, trip unit etc will be measured and paid separately under relevant items of Schedule 'A'. However the rate quoted shall be deemed to include for any other minor spares require replacement.
Suppy & fix the following spares suitable for 250 MVA to 450 MVA HT switch gear VCBs and 11 KV HT panel repair of work under relevant Schedule
Supply & fix the 1.5 sqmm flexible PVC stranded copper conductor cable, unshethed, 1100 V grade for control wiring.
S&F 2.5 sqmm flexible PVC stranded copper conductor cable, unshethed, 1100 V grade for control wiring.
S&F in replacement LED Indication Lamps, complete all as specified and directed.
S&F in replacement LED type push button actuators, complete all as specified and directed.
S&F in replacement Shunt trip coil 30 V DC/110 V DC , complete all as specified and directed.
S&F in replacement CTs epoxy cast wound primary CTs with minimum primary current 50/25/5+5A, double ratio, double core (Protection core-5P10 & Metering core- Class 0.5), complete all as specified and directed.
S&F in replacement CTs epoxy cast wound primary CTs with minimum primary current 100/50/5+5A, double ratio, double core (Protection core-5P10 & Metering core- Class 0.5), complete all as specified and directed.
S&F in replacement Breaker control switch , complete all as specified and directed.
S&F in replacement Breaker bushing contact, complete all as specified and directed.
S&F in replacement Vacuum interrupter assembly, complete all as specified and directed.
S&F in replacement Busbar Spout, complete all as specified and directed.
S&F in replacement Circuit spout, complete all as specified and directed.
S&F in replacement Control circuit fuses 2 A to 16 A suitable as per site, complete all as specified and directed.
S&F in replacement HRC fuse (PT HT side), complete all as specified and directed.
S&F in replacement PT plug contact, complete all as specified and directed.
S&F in replacement Spring charging motor with gear assembly, complete all as specified and directed.
S&F in replacement Ammeter of suitable capacity as per site , complete all as specified and directed.
S&F in replacement Voltmeter of suitable capacity as per site, complete all as specified and directed.
S&F in replacement Multifunction meter, Digital type (Displaying A, V, PF, Hz, KVA, KW, KVAR, KWh, KVARh etc.) Class 0.5 with RS485 port for communication in Modbus protocol, complete all as specified and directed.
S&F in replacement Cast Resin Three phase Potentail Transformer 11KV/√3/110V/√3,100VA , Cl 0.5 with desired capacity PT Fuses, complete all as specified and directed.
S&F in replacement Rachet handwheel with gear assembly, complete all as specified and directed.
Supply, install, connect, testing and commissioning in replacement of 30 V DC auxiliary power source with 2V lead acid cells for protection of power control system with battery charger comprising of the following all as standard practice and as specified including dismantling old battery power pack system complete.(a) 30V/100AH VRLA battery pack consisting of Lead acid cell batteries minimum 15 Nos with 2 V per cell in float charge condiiton, 2.75V per cell in Boost charge condiiton, 1.75V permissible cell voltage at the end of discharge complete with discharge duration of 10 hours.(b) DC buses of flat and of adequate cross section and length fixed to epoxy insulator supports as required. (c) Copper cable of adequate size and length from battery charger to bank of battery and battery bank to auxiliary supply panel.
S&F inreplacement of Plates (plain or chequered), channels, angle irons, square cut or notched (ordinary and counter sunk) forming holes, without any attachment all as directed conforming to Fe 410 -W (Gde E- 250) quality A including applying two coats of synthetic enamel paint over a coat of red oxide zinc chrome primer including dismantling old rusted cable/duct covers.
M&L for disconnecting carefully electrical connection from both HT/ LT (primary & secondary) sides of the transformer, keeping them at safe side and taking out the but transformer/Voltage stabiliser indoor/ outdoor type of capacity 250 KVA to 500 KVA, 11 KV/ 0.433 KV, step down any make for carrying out complete overhauling which shall comprise of the following:- a) M&L for lifting, transporting, handling, the transformer to workshop and opening top cover of the transformer by unscrewing nuts, bolts, washers etc. including disconnecting core assembly from HT/ LT bushing and lifting the same gently and taking out from the shell (container/ body) of the transformer. b) M&L for draining out transformer oil from the above said transformer in the suitable capacity of container /drums and keeping it in safe custody for reuse. c) M&L for cleaning the transformer body from inside, removing deposited dirt/ sludge/ foreign particles etc. from the bottom/ body of the transformer and drying up the shell from inside before refilling of the transformer oil. d) M&L for cleaning and washing thoroughly core and windings of the transformer by hosing down with clean dry oil conforming to IS 335/1983, removing deposited dirt/sludge/foreign particles from the windings/ core, thorough inspection of windings, providing insulations to leads and terminals, heating/ drying/ baking complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc, complete all as specified and directed.
e) Lifting and refixing core assembly inside the transformer shell gently and carefully, connecting primary/ secondary/ Neutral connections to the bushings assembly, fixing of tap change over including tightening of nuts, bolts, washers of the core to reduce humming noise all as directed. f) Refilling the filtered transformer oil in the shell of transformer complete. g) Refixing the top cover including replacement of cork sheet/ gasket 8mm thick, tightening of nuts/ bolts/ washers etc. and replacement of breather with silica gel crystal type all as directed by Engr-in charge. h) Lifting/ shifting to the place from where removed or to any location as directed and re-installing the transformer including connecting primary/ secondary/ neutral connections etc. all as directed by Engr-in-Charge. j) The inspection of transformer shall involve:- i) Checking of all clamps, nuts, bolts including core bolts & cover fixing bolts. ii) Checking all brazings, joints, tap heads and connection joints. iv) Checking the Buchholtz relay/ conservator MOG if any.
All as per Item No. 72 herein before but but transformer/Voltage stabiliser indoor/ outdoor type of capacity 160 kVA to 200 kVA, complete all as specified and directed.
All as per Item No. 72 herein before but but transformer/Voltage stabiliser indoor/ outdoor type of capacity 50 to 150 KVA, complete all as specified and directed.
Filtration of transformer oil of transformers installed at various locations to achieve di-electric strength not less than 50 KV at 2.5mm gap as per relevant IS with portable filtration plant, testing of the oil for the di-electric strength before filtration and after filtration , complete all as specified and directed.
Supply and topping up of transformer oil with di-electric strength not less than 50 KV in to the conservator tank/ body tank of the transformer/ OCB etc at various locations, complete all as specified and directed.
M&L for rewinding of distribution (HT/LT) transformers of capacity ( 50 KVA to 500 KVA)/ type by winding the defective coils with new copper wire as per I.S. of same gauge and existing size together with new insulated materials/ bracings before placing in to the transformer and assembling the coil with new insulation and fitting the coils in the chamber, testing and commissioning the transformer and recording the test results , complete all as specified and directed. [Note: M&L for re-insulation of serviceable coils will be measured & paid separately under relevant items.]
M&L for re-insulating windings of HT/ LT distribution transformers of capacity ( 50 KVA to 500 KVA) / size/ type by strip opening of HT/ LT coils (i.e. Primary/ secondary coils) from core assembly safely, unwinding the HT/ LT coils (i.e. Primary/ secondary coils) complete, removing the old defective insulation paper and replacing with new DPC insulation to the copper/aluminium conductor, re-varnishing of the windings with super varnish including heating/ drying/ backing complete carefully and thoroughly inside the heating chamber at suitable temperature to obtain required value of insulation resistance etc. all as per IS 1986-87 , complete all as specified and directed.
M&L for replacement of silica gel breather of assembly for HT/ LT distribution transformers of the following capacity including dismantling old one
(a) 250 KVA to 500 KVA
(b) 100 to 200 KVA
(c) 50 to 75 KVA
M&L for replacement gun metal drain valves of transformers of following size including dismantling old one:-
20 mm size
25 mm size
M&L for replacement of the LT porcelain bushings 50 to 500 KVA distribution transformers of existing transformer make/ size/ type , complete all as specified and directed including dismantling old one.
M&L for replacement of the HT porcelain bushings 50 to 500 KVA distribution transformers of existing transformer complete all as specified and directed including dismantling old one.
M&L for replacement of the LT bushing rod made out of brass with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete of following capacity distribution transformers of any make/ size/ type, complete all as specified and directed including dismantling old one.
(a) 250 to 500 KVA
(b) 100 to 200 KVA
(c) 50 to 75 KVA
M&L for replacement of the HT bushing 50 to 500 KVA rod made out of brass with threading & of suitable length/ size all as per existing including metal rings/ bolts/ washers/ rubber rings etc. complete distribution transformers of any make/ size/ type , complete all as specified and directed including dismantling old one.
M&L for replacement of (OTI) Oil Temperature indicator of following distribution transformers including dismantling old one.
(a) 63 to 500 KVA
M&L in replacement for porviding new cable box made out of MS sheet of thickness not less than 5 mm including fabrication works, welding etc. to suit the existing transformer size, including nuts, bolts, cable glands, termination of existing cables etc., complete all as specified and directed for the following capacity transformers:
(a) 200 to 500 KVA
(b) 50 to 160 KVA
M&L for preparation of old painted surfaces of transformers with coarse cloth/ brush and painting throughout externally on exposed surfaces with two coats of smoke grey colour synthetic enamel paint or as approved colour including writing of transformer details on plinth in white enamel paint on black enamel paint back ground complete including one coat of white wash for base foundation, complete all as specified and directed for the following capacity in-door/ out-door type transformer:-
(a) 160 to 500 KVA
(b) 50 to 100 KVA
Clearing of bushes/small plants upto root level around and surroundings areas E/M installations (i.e.Two Pole/ Four structures, outdoor-substation yards & Misc E/M installations etc) including spraying of chemical for anti-vegetation growth as approved, surface dressing n.exc 15 cm deep and removing debris to a distance n.exc 50m , complete all as specified and directed.
Supply and lay Graded coarse aggregate of size 40 mm dia size in outdoor sub-station yards , complete all as specified and directed.
Supply and lay Graded coarse aggregate of size 20 mm dia size in outdoor sub-station yards , complete all as specified and directed.
Supply and lay mooram/Red bajri in layers in outdoor sub-station yard, complete all as specified and directed.
M&L for shifting of transformer duly disconnecting carefully electrical connection from both HT/ LT (primary & secondary) sides of the transformer, keeping them at safe side and taking out the but transformer/Voltage stabiliser indoor/outdoor type of capacity 50 to 500 KVA, 11 KV/ 0.433 KV, step down , including lifting/ shifting , transporting, handling to the place from where removed or to any location as directed and re-installing the transformer carefully including connecting primary/ secondary/ neutral connections etc, complete all as specified and directed.
Supply only Fuse wire copper tinned 20 Amp
Supply only Fuse wire copper tinned 16 Amp
Supply only Fuse wire copper tinned 25 Amp
M&L for detecting HT/ LT UG cable faults located in any stretch/ depth with sophisticated cable fault locator consisting of microprocessor based pre-locator system, HV surge generator of capacity upto 16 KV, fault pin point surge wave reciever, cable indentification instrument , cable tracer for exact location of under ground cable routes, complete all as specified and directed. Note: The rate quoted deemed to be inclusive of transportation of equipment from any location and charges for service engineer for identifying the fault including their boarding & lodging complete.
Notes : The Schedule of Credit amount shall be deducted from the total of this schedule(BoQ) to arrive at Contract Sum.
Please Enable Macros to View BoQ information
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.51 MB
Tender80.pdf
Tender Documents • 1.15 MB
BOQ_840597.xls
BOQ • 0.45 MB
Download all tender documents and submit your bid