CA NO. GE AF NO.1/GUR-49/2023-24 REPAIR/MAINT OF FLOOD LIGHT, SOLAR LIGHT AND ANNUAL MAINTENANCE CONTRACT FOR FIRE ALARM, AMR ELECTRIC ENERGY METERS AND OTHER MISC WORKS AT AF STATION PALAM UNDER GE (AF) GURGAON NO 1.
2023_MES_606556_1
GE AF No 1/GUR-49/2023-24
Open Tender
Miscellaneous Works
Item Rate
270 days
GE (AF) Gurgaon No 1
ALL AS PER NIT
10 documents required · 10 mandatory
₹500
GE (AF) Gurgaon No 1
₹80,000
Yes
18 Aug 2023
28 Jun 2023
31 Jul 2023
28 Jun 2023
29 Jul 2023
15 Jul 2023
Amount
Comprehensive maintenance for single phase AMR meter software hosting, GPRS Charges, meter calibration testing with multimeter, RF network monitoring and trouble shooting and repair/replacement of meter parts with manufactruing defect complete all as specified and as directed by Engr-in-charge (AMC for 430 Meter/ per month for 09 Months).
Comprehensive maintenance for for three phase AMR meter software hosting, ,GPRS Charges, meter calibration testing with multimeter, RF network monitoring and troubleshooting and repair/replacement of meter with manufactruing defect complete all as specified and as directed by Engr-in-charge.(AMC for 74 Meter/ per month for 09 Months).
Comprehensive monthly maintence of auto fire alarm system installed in 13 BRD/16 BRD /27 ED AF Stn Palam. The detail scope of work consists of the following :- (i) Cleaning inspecting, checking and repairing if required all the equipments of fire detection system. (ii) Operational test of all the equipment of fire detection system in presence of rep of users and Engr-in-charge. (iii) The contractor shall submit test report regarding functioning of all the equipments duly signed by contractor, users rep and Engr-in-Charge on monthly basis. (iv) The maintenance shall be carried out through manufacturer representative or his authorised Rep. (v) Emergency visit shall be carried out when called in addition to the normal monthly maintenance in case of any failure in the system due to any cause without additional cost. (vi) Material required for replacement shall be measured and paid separately under respective items of this schedule as 'Supply and fixing' and labour component for the same is not included in comprehensive maintanance contractor shall quote the rate accordingly. (vii) Testing of entire fire alarm system and rectification of fault complete to the entire satisfaction of engr-in-charge all as specified and directed .
Supply and fixing in replacement of gear and pinion system for high mast light fitting complete all as specified and directed.
Supply and installation in replacement of response indicator lamp complete all as specified and as directed.
S&F in replacement of addressable duct detector with multiple sensitivity level, programmable for timed automatic sensitivity and with base UL listed complete all asspecified and directed.
S&F in replacement of Analogue addressable control modules complete all as specified and directed.
S&F in replacement of Analogue addressable fault isolator module capable of monitoring shorted loop circuit and automatically restore communication when shorted conditions are re corrected complete all as specified and directed.
S&F in replacement of Addressable Dual tone electronic sounder / hooter enclosed in MS box with LED indication hooter complete all as specified and directed.
M&L 2x1.5sqmm+1x1sqmm PVC insulated unsheathed, FRL Smultistr and edcopper conductor cable,1100V grade asper IS1554 Part Idrawn through and including ERW steel conduitnot less than 20 mm dia duly painted complete all asspecified and directed.
M&L 2x4.0 sq mm +1x2.5 sq mm PVC insulated unsheathed, FRL Smultistr and edcopper conductor cable, 1100V grade asper IS1554 Part I dra wn through and including ERW steel conduit not less than 20mm dia duly painted complete all asspecified and directed.
S&F in replacement of 9 volts DC battery for wireless smoke detector complete all as specified and as directed.
S&F in replacement of hooter radio meter operating voltage 15 volts DC, indication alarm 85 db, complete all as specified and directed.make : AGNI Protection/Quatac/Honey well
S&F in replacement of MCP remote key of black colour including testing with battery complete all as specified and directed. Model no AP RE-920 of make : AGNI Protection/Quatac/Honey well
M&L in replacement of wire less smoke detector having 9 volt DC battery, smoke sencor temp range (10-70 ) degree centigrade, humidity range 20 % to 95 %, including testing complete all as specified and directed. Model no AP SD-900 of make : AGNI Protection/Quatac/Honey well
Supply and fixing in replacement of response indicator as per existing make and model complete all as specified and directed.
Supply and installation in replacement of 12 volt 7 AH battery complete all as specified and directed. Make - Exide /Amaron/ Luminous/ Amco
Taking down of old unserviceable optical type smoke detector and supply and testing of detectors complying with and type certified to EN-45 adjustable type smoke detector Photo electric / Optical with base with self built intelligence as per IS: 11360 complete all as specified and directed . Make Cooper/Honeywell/Ravel/Apollo
Supply and fixing in replacement of mother board suitable for Fire alarm system complete all as specified and directed. Make : Agni/Cooper/ Honeywell/ Ravel/Apollo
Supply and fixing in replacement of Power Supply card suitable for Fire alarm system complete all as specified and directed. Make : Agni/Cooper/ Honeywell/ Ravel/Apollo
Supply and fixing in replacement of manual call point resettable type complete as directed. Make : Agni/Cooper/ Honeywell/ Ravel/Apollo
Supply and fixing in replacement of electronic sounder cum strobe complete all as directed.Make : Agni/Cooper/ Honeywell/ Ravel/Apollo
Supply and fixing in replacement of Repeater Panel 08 Zone complete all as specified and directed. Make : Agni/Cooper/ Honeywell/ Ravel/Apollo
Supply and fixing in replacement of 1.5 sqmm three core PVC insulated sheathed ISI marked FRLS copper conductor multi stranded 1100 volt grade cable drawn through existing conduit connecting and testing all as specified and directed.
Supply and fixing in replacement of Heat Detector with Base complete all as specified and directed. Make : Apollo/ Honeywell/Ravel/ Copper
Supply, installing, connecting and testing in replacement of Three phase automatic change over switch of capacity TPN 63 Amps complete all as specified and directed. Make:- Havells Cat part No. DHACOTN8063 or equivalent out of make specified in list of make.
M&L in replacement of 4.0 sq mm 3 core PVC insulated unsheathed, FRLS multistranded copper conductor cable, 1100V grade as per IS1554 Part I drawn through and including ERW steel conduit not less than 20 mm dia duly painted complete all asspecified and directed.
Comprehensive monthly maintence of 3 X 30 KVA UPS system installed in 13 BRD AF Stn Palam. The detail scope of work consists of the following :- (i) Execute diagnostics and physical checks. (ii) Examine, clean, test, all equipment as required and repair parts as and when required. (iii) Measurement of UPS parameters like input/output voltage, frequency, current, frequency, room temperature etc. (iv) Battery Parameters like voltage, current and other relevant parameters. (v) Ensure dust free and controlled temperature conditions. (vi) The corrective maintenance may require multiple visits to site (vii) Check all Equipment LED LCD display board if any fault found to be rectified in the same cost.(viii) Checking of servicibility of MCB/MCCB if found unserviceagle to be replace without any extra cost. (ix) Checking of UPS fuse. if found us to be replace.(x) Keeping of servicibility of UPS is the responsibility of the contractor for the entire contract period. Note : Response time should be not more than 24 hours from the time of receipt of complaint on any working day between 9 AM to 6 PM.
Supply and fixing in replacement of Bus Trunking having copper bus bar of cap 40 Amp 3L+N+PE, F 50HZ with insulator and tap off unit at each 0.5 mtr intervals all as specified and directed by Engr-in-Charge.
Supply and fixing in replacement of Bus Trunking having copper bus bar of cap 60 Amp 3L+N+PE, F 50HZ with insulator and tap off unit at each 0.5 mtr intervals all as specified and directed by Engr-in-Charge.
Supply & fixing in replacement of Class II Three Phase Lightning & Surge Protection Device for Main Incoming Panel of Lab for giving Protection against LIGHTNING, SURGES, TRANSIENTS, ELECTRO MAGNETIC INTERFERENCE, RADIO FREQUENCY INTERFERENCE, THERMAL FUSING AND SHORT CIRCUIT FUSING with following specifications: a) SPD shall be suitable for a working voltage of 240/415V, 3 phase 4 wire systems and surface mount. b) Maximum continues operating voltage of the SPD shall be not less than 290V. c) SPD shall be compact and with flying leads of minimum 5 sqmm. d) SPD shall have Green , Red LED Status Indicator, Remote Signaling and Audible Alarm which triggers during fault. e) SPD must be rated for Maximum Surge Current of 80kA and a nominal discharge rating of 20kA (8/20 micro sec) . f) SPD must have a Short Circuit Current Rating of not less than 100kA Amperes Interrupting Current (AIC). g) The voltage protection rating for L-N,L-G and N-G shall be less than 1200V. h) SPD must have a filtering circuit with Max noise attenuation of -75dB for 100kHz to 100MHz to give a low residual voltage for the connected equipment during surge. i) SPD shall have ambient temperature limits of -40° C to +60° C with humidity of 95% RH (non-condensing). j) SPD shall be UL1449, 4th edition listed. k) SPD shall have EMC Compliance / BS EN: 60950: 1992; BS EN 61000-6- 2:1999 ANSI IEEE C62.45; ANSI IEEE C62.41. m) Warranty: 10 YEARS "No Fuss" Replacement.
Disconnect the unserviceable battery lead connections from 65 AH SMF battery of 30 KVA UPS and transport the us battery to work shop for reconditioning work by using dedicated battery regenerator. Sulfation on plates should be removed by using high powered pulses, replace the us battery terminals , replace the electrolyte and recharge the battery upto 24 to 36 hours to gain more than 12 volts. After completion of reconditioning work the battery will be refix at the same position including necessary testings complete all as specified and directed.
Disconnect the cable connection from unserviceable electric siren from site and refixing the same after completion of necessary repair work complete all as specified and as directed
M&L for opening of electric siren motor and , cutting the burnt winding from motor and rewinding the motor with super enamelled copper wire as per existing size and gauge with and including provision of insulating material varnishing with good quality varnish including replacement of all unserviceable parts such as safety pin, fan blade,bearings and three core copper wire etc complete all as specified and as directed by Engr-in-charge.
Repair/Servicing of Siren,horizontal double mounting, single phase,audible range 3.25 KM at 220/250 volt, 6000 rpm, 50 Hz, AC complete all as specified and directed.
M&L in replacement of 3 core copper conductor of size 2.5 sqmm cable 1100V grade complete all as specified and as directed by Engineer- in Charge.
Disconnect the cable connection from unserviceable single phase AMR meter from existing meter panel box and deposit to MES office complete all as specified and as directed
Disconnect the cable connection from unserviceable three phase AMR meter from existing meter panel box and deposit to MES office complete all as specified and as directed
S&F in replacement of unserviceable Single Phase AMR Meter with the following specifications: • AC Single Phase Two Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt Low Power Radio Frequency (LPRF) communication facility in Cyanconnode or equivalent Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy, cumulative apparent energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from billing software MAKE: Secure, L&T, Schnieder
S&F in replacement of unserviceable Three Phase AMR Meter with the following specifications: • AC Three Phase Four Wire, Tamper Proof, Static Meter of Class 1.0, 240 V, 50 Hz, 10 A-60 A conforming to IS-16444 and relevant IEC standards with inbuilt Low Power Radio Frequency (LPRF) communication facility in Cyanconnode or equivalent Mesh network with default and on demand display, billing data generation facility, anti-tamper features, Microprocessor and LED/LCD based circuitry. • Meter Should support the following data : 30 min instantaneous data for voltage, current, power factor, power, cumulative energy, cumulative apparent energy and frequency, 30 load survey data for energy, monthly billing survey for Cumulative Energy and Max Demand • Meter should have connect / disconnect functionality operable from billing software MAKE: Secure, L&T, Schnieder
M&L for repair of single phase AMR meter two wire LCD dispaly/ dial type any make 5-30 Amps complete all as specified and as directed by Engineer- in Charge.
M&L for repair of three phase AMR meter four wire LCD dispaly/ dial type any make complete all as specified and as directed by Engineer- in Charge.
Taking down any type of street light /flood light fitting to any size and type from existing LT pole, bldg, complete for repair and refixing to existing position after repairing complete all as specified and directed by Engr-in-Charge. (spares required for repair shall be measured and paid separately).
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed.
All as per srl item No. 44 above but 70 watt -ditto-.
All as per srl item No. 44 above but 90 watt -ditto-.
Supply and fixing LED flood light 70 watt 230 V AC outdoor type with thermal management in multiple optics and equipped with IP66 protection, with impact and corrosion resistant complete with driver and lamp.
All as per srl item No. 47 above but 100 watt -ditto-.
All as per srl item No. 47 above but 120 watt -ditto-.
Supply and fixing post top lantern LED type 20 watt 230 watt volts AC outdoor type with decorative post top for 360 degree indirect light IP 65 protection with impact and corrosion resistant complete with driver and lamp complete
Supply and fixing LED Solar street light fitting 36 Watt including galvanized steel pole in built, lithium ion battery, solar panel, charge controller with dusk down sensor complete. (Excavation & earth work shall be measured separately
All as per srl item No. 51 above but 24 watt -ditto-.
S&F Thermoplastic PC- GFS Polycarbonate Weatherproof Junction Box IP 66 / IP67 with multi-level knockout for cable glands in 35sqmm 3.5 core sizes with UV resistant due to solar radiation, Rainwater proof, temperature resistant., Salt water proof & shall be suitable for off-shore applications. IEC 60670-22: Particular requirements for connecting boxes and enclosures. IEC 60695 – 2 – 11: Flame – retardant & Self-extinguishing. Glow Wire tested at minimum 960 deg C. IEC 60529: IP 66 / IP 67 / IP 69 degree of protection complete all as specified and as directed. Make- Hensel, Havells, L&T or its equivalent make & model.
Ditto as item No 53 above but cable glands in 25 sqmm 4 core sizes 205 x 255 x 112 mm -ditto-
Supply and fix 3 Phase automatic timer switch with switches ON/OFF the street lights base on lux level of natural light for 5/7kW load equally distributed over 3-phase,415V 50 Hz. The sensor based timer should also have over voltage and low voltage trip with auto reset facility the sensor alongwith suitable power contactor, MCB and support terminals should be enclosed in pole/wall mountable enclosure made of rust proof electric shock proof termite proof and FR grade special moulding compounds confirming to IP 65. The contactor MCB and circuit wiring shall have enough capacity to take load of 5/7 KW equally distrubuted over 3 phase complete all as specified and as directed. Make : Healer/Universal Swtich Gear/Kakatiya Note: Fixing timer on wall/pole with the help of fastner & ms strip, nut bolt & washer is deemed to be included in quoted rates.
Supply and laying XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 sq. mm 3.5 core complete all as specified and directed.
Excavation in treanches in soft loose /soil not exc 1.5m wide and not exc 1.5m deep and getting out for taking out and laying cables foudation etc. complete all as specified and directed. Note:- Brick PCC cables protection cover shall be retrieved and kept in safe costody for reuse).
Returning filling in including spreading leveling waterning and well remmaning in layers not exc 25cm thick complete all as specified and directed.
Removing of surplus spoil to a distnce not exc 50m and depositing where directed at a level not exceeding 1.5m above the starting point complete all as specified and directed.
M&L for dry clean sand filling in trenches below and around under ground cable cushioning complete all as specified and directed. Note :- Thickness of sand cushioning shall be measured after punning.
M&L for brick protection with sub class 'B' Designation 75 old bricks laid dry flat 23cm in width over sand cushioning in trenches as perpendicular to the direction of underground cable complete all as specified and as directed.
S&F in repair GI pipe light grade 50mm bore in trenches/wall/poles for protection of cable complete all as specified and as directed.
Labour and required tools for carrying out horizontal boring below roads/PCC hard standing/Drain suitable Up to 50mm dia GI pipe all as specified as directed for inserting GI pipe of the following sze with a depth upto 1.5m & length of road upto 12m of the follwing size of bore complete all as specified and directed.
S&F in replacement of 2.5 Sqmm two core stranded PVC insulated copper conductor FRLS cable for connection of fittings complete all as specified and as directed by Engr-in-charge.
S&F in replacement of 32 Ah Li-ion solar battery suitable for 30 watt street light fitting as per sample complete all as specified and directed
Disconnecting and taking out 3 Phase forward and reverse motor of capacity 1.0/1.5 HP motor from existing highmast tower enclosure including rewinding with super enameled copper wire, replacement of neck rings, sleeves bushing , seal complete all as specified and directed.
Supply and fixing in replacement of Programmable Time Switch 24 Hour (SST - 15 min) outdoor/semi-indoor lights) for high mast tower controller panel same as per the sample in the existing High mast panel complete all as specified and directed. Make:- Nature switch or equivalent in HPL/L&T/EE.
Supply and fixing in replacement of steel wire rope for high mast light fitting complete all as specified and directed.
M&L for repair of electric meter single phase two wire LCD dispaly/ dial type any make 5-30 Amps complete all as specified and as directed by Engineer- in Charge.
M&L for repair of electric meter three phase four wire LCD dispaly/ dial type any make complete all as specified and as directed by Engineer- in Charge.
Supply and fix electronic meters temper proof LCD display with polycarbonate cover 230 V, 10-60Amp, accuracy class-I 50Hz, conforming to IS 13779, IP-54, with parameters to show data, time, current reading, load, PF, voltage and KWH complete all as specified and as directed. Make:- HPL/BENTEC/ Secure
Ditto as above item but 3 Phase, 415 volt complete all as specified and as directed.
Notes:- The amount of Rs 99920.00/- against Schedule of Credit shall be deducted from the total amount quoted against Sch 'A' while deriving the Contract Sum for Acceptance.
B S R Enterprises
M/S PARKASH ENTERPRISES
Satish Kumar Gupta
J.P. Enterprises
MAHABIR SINGH
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .