Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | 1st₹10.5 LAccepted-AOC | 1st | Accepted-AOC The lowest bidder M/s Lakxmi Narayan
and Sons has been accepted. | |
| 2 | 2nd₹11.8 L+₹72,215.71 (6.54%)Rejected-Finance | 2nd | Rejected-Finance L2 | |
| 3 | 3rd₹13.3 L+₹2.3 L (20.9%)Rejected-Finance 19 SAINIK COLONY BAIRAGARH BHOPAL MP 462 030 | BHOPAL | MADHYA PRADESH | 462030 | 3rd | Rejected-Finance L3 | |
| 4 | 4th₹16.6 L+₹5.5 L (50.2%)Rejected-Finance | 4th | Rejected-Finance L4 |
Tender Value
₹11.6 L
EMD Value
₹23,100
Closing Date
21 May 2020, 6:00 pmClosed
GE AWC MHOW
GE AWC MHOW
REPAIR MAINT OF DESERT COOLERS,WATER COOLERS,REFRIGERATORS,DEEP FREEZERS,SPLIT/WINDOW/ CASSETTE TYPE ACs AND ALLIED ITEMS AND MAINTENANCE/SERVICING OF PUMPING SET AND RENEWAL OF LT PANELS,GI PIPES LINES AND CONNECTED ITEMS AT AWC UNDER GE (AWC)
2020_MES_324794_3
8395 GE(AWC) /MHOW / OF 2019-20
Open Tender
Civil Works
Item Rate
180 days
GE AWC MHOW
All as per Tender Documents and NIT.
7 documents required · 7 mandatory
₹500
Yes
GE AWC MHOW
₹23,100
Yes
10 Jun 2020
17 Apr 2020
22 May 2020
18 Apr 2020
21 May 2020
1 May 2020
Amount
Repair/Maints/Servicing complaint from in respect of non functioning of any type of Air Conditioners of windows/ split type/ Tower /Cassette type of any capacity due to loose electrical connections,no power supply, gas leakage or any other minor default / defects, identifying and rectifying the defects and making the AC by replacement/ renewal of air conditioners functional complete all as specified and directed by Engr-in-Charge. Note:- (i)Parts/ accessories/articles renewed only shall be measured and paid separately under appropriate items).However minor items like nuts, bolts, washers, tapes,nails, screws, Aluminium clips,PVC rawl plugs/ sleeves, connector block, clamps, Aluminium lugs, etc. shall be deemed included in the unit rate quoted by Contractor.
Taking down of old serviceable split AC of 1.5TR/2 TR capacity from site, taking out residual refridgerent gas from the split AC by cutting the CP pipes/ tubes carefully and shifting ,transporting , fixing, installing, commissioing and testing including charging with Non CFC refrigerent gas taken out from the existing AC and making connections fixing of all piping work alongwith its insulation complete all as specified and directed .
Taking down of old serviceable Window type AC of 1.5TR/2 TR capacity from site and shifting ,transporting , fixing, installing, commissioing and testing including charging with Non CFC refrigerent gas and making connections fixing of all piping work alongwith its insulation complete all as specified and directed .
Repair/Maints/Servicing of Non functioning of 1.5 /2 TR capacity ,any type of Air Conditioners of windows/ split type/ Tower /Cassette type of any capacity by testing the leakage in system by filling of nitrogen gas upto 300 PSI and repairing of leakage spot/ joints with gas welding work , cleaning and flushing the complete system with gas, making the complete system leakproof, vaccumising and charging of gas Non CFC and testing on load including renewal of air filter complete all as specified and directed by Engr-in-Charge. Note:- (i)Parts/ accessories/articles renewed and gas ( except air filter) only shall be measured and paid separately under appropriate items).However minor items like nuts, bolts, washers, tapes,nails, screws, Aluminium clips,PVC rawl plugs/ sleeves, connector block, clamps, Aluminium lugs, etc. shall be deemed included in the unit rate quoted by Contractor.
Repair/Maints/Servicing of Non functioning of 4 TR capacity Air Conditioners Cassette type of any capacity by testing the leakage in system by filling of nitrogen gas upto 300 PSI and repairing of leakage spot/ joints with gas welding work , cleaning and flushing the complete system with gas, making the complete system leakproof, vaccumising and charging of gas Non CFC and testing on load including renewal of air filter complete all as specified and directed by Engr-in-Charge. Note:- (i)Parts/ accessories/articles renewed and gas ( except air filter) only shall be measured and paid separately under appropriate items).However minor items like nuts, bolts, washers, tapes,nails, screws, Aluminium clips,PVC rawl plugs/ sleeves, connector block, clamps, Aluminium lugs, etc. shall be deemed included in the unit rate quoted by Contractor.
Supply & fixing (in repairs) starting capacitor (conforming to IS:2993 - 1975) AC 230/270 volts in plastic container 80-100 mfd complete all as specified and directed . Make :- Havells (india) ,Bajaj ,Crompton .
Supply & fixing (in repairs) starting capacitor (conforming to IS:2993 - 1975) AC 230/270 volts in plastic container 100-120 mfd complete all as specified and directed . Make :- Havells (india) ,Bajaj ,Crompton .
M&L for renewal of running capacitor of plastic container of 36 Mfd capacity all as directed by EIC. Make :- Samsung/ LG/Videocon)
M&L for renewal of running capacitor of plastic container of 45 Mfd capacity all as directed by EIC. Make :- Samsung/ LG/Videocon)
S&F in repairs Thermostate switch for 1.5 TR / 2 TR Window type AC all as directed by EIC. Make :- Carrier/ LG/Voltas/National/Casino type.
S&F discharge copper pipe line heavy duty 3/8"dia with puff insulation and flair nuts from indoor to outdoor unit of spilt AC 1.5 / 2 TR capacity all as specified and directed.
S&F discharge copper pipe line heavy duty 1/4"dia with puff insulation and flair nuts from indoor to outdoor unit of spilt AC 1.5 / 2 TR capacity all as specified and directed.
S & F( in repairs) PVC pipe nylon imbraided 15 mm dia for condensed water drain fitted with clamps/concealed in wall all as specified and directed.
Dismantling of burnt blower motor of 1.5 TR window AC and supply & fixing new blower motor, double shaft, 1/5 HP (Suitable for Carrier/Voltas/Climiatzer make AC) as per sample complete including blower & condensing all as specified and directed.
Dismantling of burnt blower motor of 2.0/ 1.5 TR split AC( outdoor unit) and supply & fixing new blower motor as per existing HP (Suitable for Carrier/Voltas/Climiatzer make AC) as per sample complete including blower & condensing all as specified and directed.
S&F in repair oscilliating motor for indoor unit of split AC suitable for capacity 1.5 Ton/2 Ton complete all as specified and directed. Make- Carrier, Voltas, LG or Equivalent.
Dismantling of burnt blower motor of 4 TR Cassette type AC( outdoor unit) and supply & fixing new blower motor as per existing HP (Suitable for Carrier/Voltas/Climiatzer make AC) as per sample complete including blower & condensing all as specified and directed.
S&F in repair oscilliating motor for indoor unit of Cassette type AC suitable for capacity 4 TR complete all as specified and directed. Make- Carrier, Voltas, LG or Equivalent.
Dismantling of unserviceable compressors of 1.5 TR capacities including disconnecting suction / discharge copper tubing and S&F compressor reciprocating type ( or Rotary type) with and including initialy charged gas with nuts, bolts, rubber grommet and washer, connecting copper tubing by welding, flare nuts, rectifying leak and repairs if any, flushing by nitrogen & etc, Vacuumising, charging with refrigerant gas Non CFC complete all as directed by EIC.Note :_(i) The compressor of make – Emerson Model CR-22 / CR-30 or equivalent of Carrier/ Kirloskar/ Blue star
Dismantling of unserviceable compressors of 2 TR capacities including disconnecting suction / discharge copper tubing and S&F compressor rotary type or reciprocating type with and including initially charged gas with nuts, bolts, rubber grommet and washer, connecting copper tubing by welding, flare nuts, rectifying leak and repairs if any, flushing by nitrogen & etc, Vacuumising, charging with refrigerant gas Non CFC complete all as directed by EIC. Note :_(i) The compressor of make – Emerson Model CR-22 / CR-30 or equivalent of Carrier/ Kirloskar/ Blue star
Dismantling of unserviceable compressors of Cassette type 4 TR capacities AC's including disconnecting suction / discharge copper tubing and S&F compressor rotary type (cruise type) with and including initialy charged gas with nuts, bolts, rubber grommet and washer, connecting copper tubing by welding, flare nuts, rectifying leak and repairs if any, flushing by nitrogen & etc, Vacuumising, charging with refrigerant gas R-22, Mineral oil 3 Ph 50Hz 380-415V complete all as directed by EIC.Note :_(i) The compressor of make – Dalian sanyo compressor model no C- SBX180H38Cor equivalent of Carrier/ Kirloskar/ Blue star/ Emerson.
S&F in repairs coir filter suitable for window type air conditioners complete all as specified and directed of Make:- Hitech/ Denyo or equivalent make as approved by GE.
S&F in repairs air filter made out of Nylone suitable for 1.5TR/2 TR split AC capacities air conditioners make as approved by GE.
Dismantling of defective worn out wiring of indoor unit of split AC of capacity 1.5 TR / 2 TR including unserviceable corded electronic remote control, supply and fixing new control wiring and corded electronic remote control to suit / match the existing system all as specified and directed by EIC (Make of AC and remote. Make:- ITC / Carrier / Cool Air or equivalent make as approved by GE.
Dismantling of defective worn out wiring of cassette type AC of capacity 4 TR including unserviceable corded electronic remote control, supply and fixing new control wiring and corded electronic remote control to suit / match the existing system all as specified and directed by EIC (Make of AC and remote. Make:- ITC / Carrier / Cool Air) or equivalent make as approved by GE.
Supply & fixing (in repairs) Renewal of PCB ( Printed circuit Board) of split type air conditioner of existing shape and size and instalation in position to make the remote control system functional complete all as specified and directed. Make - LG/Blue star/ carrier/voltas /sumsung or equivalent make as approved by GE.
Supply & fixing (in repairs) Renewal of PCB ( Printed circuit Board) of Cassette type 4 TR outdoor PCB air conditioner of existing shape and size and instalation in position to make the remote control system functional complete all as specified and directed. Make - LG/Blue star/ carrier/voltas /sumsung.
Supply & fixing (in repairs) Renewal of PCB ( Printed circuit Board) of Cassette type 4 TR indoor PCB air conditioner of existing shape and size and instalation in position to make the remote control system functional complete all as specified and directed. Make - LG/Blue star/ carrier/voltas /sumsung or equivalent make as approved by GE.
Supply & fixing (in repairs) 3 phase Contactor switch for Cassette type AC's, 4 TR capacity all as specified and directed by EIC.
Supply only refrigerant gas R-22/410 in returnable sealed cylinder all as specified and directed by EIC. Make:- Floran / Mafron/Freon or equivalent make as approved by GE.
Supply only refrigerant gas R-134 ( Non CFC) in returnable sealed cylinder all as specified and directed by EIC. Make:- Floran / Mafron/Freon or equivalent make as approved by GE.
Supply & fixing (in repairs) Renewal of rubber ring of blower motor for window type Air conditioners of 1.5 TR capacity of existing shape and size and installation in position complete all as specified and directed.
S&F thermal overload relay range 10 - 14 amps all as specified and directed. Make:-ABB / L&T/Indo asian/ Havells or equivalent make as approved by GE.
Supply & fixing (in repairs) front grill cover of window type AC'S with filter suitable for 1.5 /2 Ton AC of blue star/Carries/Samson/LG complete all as specified and directed.
Dismantling of defective air curtain motor suitable for 1200mm span of any make capacity transporting the same to contractors workshop for rewinding with super enamelled copper wire of suitable gauge as per manufacturer pattern including varnishing etc complete and refixing after testing complete to its original position including servicing of rotor and bearing etc. complete all as specified and directed.
Taking down air curtain of 1200mm span for servicing and overhauling by oiling and greasing of blower motor and cleaning by electrical motor including renewal of unserviceable bearings, repairing to shaft to make the air curtain functional complete and fixing in position and testing all as specified and directed.
M&L for preparation and scraping old surfaces of water cooler body of any capacity and spray painting with two coats of synthetic enamelled paint of approved quality after filling a cavity with metal filling materials including necessary welding work of Bottom portion with Provn of angle iron frame, PGI sheet etc and made the bottom rusted part in good condition and writing S M No with white/ Black colour paint all as specified and directed.
Supply & fixing (in repairs) replacement of PVC sprinkle nozzles of size 15 mm dia heavy duty complete all as specified and directed.
Supply & fixing (in repairs) replacement of water pressure gauge with 3/8" brass sampling nozzle of size 7 kg/10 kg pressure of dia 100 mm complete all as specified and directed by the Engr-in- Charges.
Renewal of condenser fan motor of water cooler of 40/80 litre capacity complete all as specifiedand directed. Make :- Voltas ,Blue star , Accel or equivalent make as approved by GE.
Repair/Maint/Servicing of non functional water cooler of any capacity due to any fault including checking the serviceability of all parts, leakage if any, repair/ brazing to capalary tubing, stopping leakage from water connections, loose electric connections, cleaning flushing to condensing coil and checking of blower motor etc. and making the water cooler serviceable.
Dismantling of unserviceable compressor up to 80 litre capacity any make/brand ( Make Emmerson Model HR-13) or equivalent of other specified make from water cooler including disconnecting suction / Discharge copper tubing and supply & fixing new compressor (sealed unit) with initially gas filled with nuts, bolts, rubbers grommet and washer, connecting copper tubing by welding flare nuts, detecting leak and repairs if any flushing and pressure testing by nitrogen & etc. vaccumising, charging with non CFC refrigerant gas matching with R-134, of following capacities and make & Model complete all as directed by Engineer-in-Charge. Make:- Kirloskar ,Bluestar ,Voltas, Tecumesh.
Dismantling of unserviceable compressor of 120 to 180 litre capacity any make/brand ( Make Kirloskar Model No CAJ 2612/AE4440M) or equivalent of other specified make from water cooler including disconnecting suction / Discharge copper tubing and supply & fixing new compressor (sealed unit) with initially gas filled with nuts, bolts, rubbers grommet and washer, connecting copper tubing by welding flare nuts, detecting leak and repairs if any flushing and pressure testing by nitrogen & etc. vacuumising, charging with non CFC refrigerant gas matching with R-134, of following capacities and make & Model complete all as directed by Engineer-in-Charge. Make:- Kirloskar ,Bluestar ,Voltas, Tecumesh.
Renewal of PVC sheet rubber beading of water cooler top cover of any capacities of by screwing the same to make the cover air tight/ insect proof complete all as specified.
Supply & fixing (in repairs) CP Brass push cock (inner or outer threaded) of 15 mm bore size long noze medium size complete all as directed by the Engineer-in-Charge.
Supply & fixing (in repairs) starting relay for 40 to 180 ltr capacity water cooler complete all as specified and directed .
Supply & fixing (in repairs) running capacitor (conforming to IS:2993 - 1975) AC 440 volts in plastic container of 10 mfd capacities complete all as specified and directed. Make :- Bajaj ,Crompton ,Havells India.
Supply & fixing (in repairs) running capacitor (conforming to IS:2993 - 1975) AC 440 volts in plastic container of 15 mfd capacities complete all as specified and directed. Make :- Bajaj ,Crompton ,Havells India.
Taking out existing water tank from water cooler, tracing out leakage, removing leakage by gas welding / brazing etc. and making the tank leak proof including testing complete all as specified and directed.
Renewal of rubber hose pipe of 25mm bore with mild steel clamp with nuts and bolts for waste water outlet 1.5 M long complete all as specified and directed.
Renewal of capacitor for blower motor of water cooler of 2.5 Mfd capacity all as specified and directed . Make :- Bajaj ,Crompton ,Havells India. Epcos.
S&F ( in repairs) float valve , 15 mm bore of brass with nipple and polyethylene float ball complete all as specified.
Repair/Maint/Servicing of non functioning of desert coolers due to any defect and checking electric connection, pumps, PVC pipe and distributor, tightening the loose connections and renewal of PVC pipe and PVC elbow etc. and making the cooler functional complete all as specified and directed.
Supplying and fixing ( in repairs) mild steel brackets ( arms) set of four pieces with clamps , washers, rubber bush and nuts/ bolts to match with the existing complete all as specified and directed.
Taking out carefully 325 to 500 mm sweep desert cooler from its existing position from stand/ walls or pillar, removing the side panels, taking out wool wood pads or loose pads and disposed to a distance not exceeding 50 metres away as directed by EIC and spray painting with synthetic enamel paint of approved colour outside and one coat of black bituminous paint inside after preparation of old painted surfaces and reassembling including renewal of minor items i.e. PVC distributor, PVC nozzles and PVC pipe as required and fixing in position, writing MES No with thick synthetic enamel paint 25 mm size of letters, figures etc. complete all as specified. ( Wood pads shall be measured separately)
S&F ( in repairs) Renewal of wood wool pad of desert coolers suitable for 325 to 500 mm sweep complete.
S&F ( in repairs) Renewal of PVC front grill complete with indicator switch and regulators all as directed by EIC . Make Havells/ C&S/ Anchor .
S&F ( in repairs) Renewal of iron front grill made out from PGI sheet 22 gauge complete with indicator switch and regulators all as directed by EIC. Make Havells/ C&S/ Anchor .
S&F ( in repairs) Renewal of polycarbonate Plug top 3 pin, 6 A, cat No. 38626/ 3982 of Anchor or equivalent of other specified Make.Legrand ,Crabtree (Havells)
S&F ( in repairs) Renewal of desert cooler body complete with PVC distributor, PVC nozzles and pipe, suitable for 450 mm/500 mm sweep exhaust fan /kit, made out of 22 gauge PGI sheet and side panels set of three duly filled with Khas khas including deassembling the fan, pump and its connected fittings, grills, regulator and cable etc.from wornout body and fixing the same renwed Cooler Body complete all as specified and directed. Make ;- Champion or equivalent of other specified make as approved by the GE .
M&L renewal of kit fan, motor, single phase, 230 volt AC, complete with blade arm for 20" sweep size suitable for desert cooler all as specified and directed by EIC. Make:- Jyoti / Champion / Summer Cool/Khaitan, Polar
Supply and fixing in repairs submersible pump for desert cooler single phase, 1/40 HP, 230 volts complete all as specified.Make Khaitan/ Crompton/Cool home
S&F ( in repairs) Metal clad plug and socket assembly 20A, DP complete all as specified and directed Make - C&S Cat No. CSDBPSPN 020 and CSDBPSSPN 020 , Indo assian part No - 810387+810390, HPL part No HP2P20 + HP2S20
S&F ( in repairs) Metal clad plug and socket assembly 30A, TP with earth complete all as specified and directed.Make C&S Cat No. CSDBPTPN030 and CSDBPSTPN030, Indo assian part No - 810388+810392, HPL part No HP3P30 + HP3S30
S&F (in repairs ) PVC insulated and PVC sheathed 3 core copper conductor flexible round cable size 2.5 sqmm all as specified and directed . Make :- Polycab ,Plaza , Havells.
Repair /Maints/Servicing of refrigerator/ deep freezer in respect of non functioning of refrigerators / deep freezer due to any defect i.e. gas leakage, no power supply, low pressure, no cooling unserviceablity of compressor or any other part all as specified and directed by EIC.
M&L for renewal of sealed unit Compressor of 1/6 TR capacity duly charged with initially filled refrigerent non CFC charged including necessary brazing work to make the system leak proof complete all as specified and directed. (Make-Kirloskar, Bluestar, Voltas, Carrier, Kalvinator) for refrigerator
M&L for renewal of sealed unit Compressor of 1/8 TR capacity duly charged with initially filled refrigerent non CFC charged including necessary brazing work to make the system leak proof complete all as specified and directed. Make-Kirloskar, Bluestar, Voltas, Carrier, Kalvinator) for refrigerator
S & F over load protector for 1/6 HP refrigerator of capacity 165/300 litres all as directed by Engineer-in-Charge.
S & F in repairs thermostat defrost type for refrigerator all as directed by Engineer-in-Charge.Make :- Danfoss ,Sporlon ,Indfoss.
S & F (in repairs) Renwal of electric lamps, 15 watts, 230V, 50 Hz screw/ pin type as per existing Make Philips/ Bajaj/Havells.
S & F in repairs freezer door with spring for Refrigerator of 280/300 litres capacities all as directed by Engineer-in-Charge.
Supply & fixing ( in repairs) vegetable basket with glass suitable for refrigerator of 280/300 litres capacities all as specified and directed by Engineer-in-Charge.
Supply & fixing ( in repairs) Drain pump for cassette type Ac's capacities of 4 TR, 220-240V, 50/60Hz all as specified and directed by Engineer-in-Charge.
M&L for Repair overhauling of exahaust system installed at 'B' Mess including checque of all vents, leakage & water pipe lines etc complete all as specified and directed EIC.
M&L for Repair to foundation of motor pump set of central exhaust system of 'B' Mess. Including the following:- (a) Breaking of foundation. (b) Making good the disturbed surface. (c) M&L for PCC foundation/piller of 1:3:6 Type C2, 40mm graded aggregate including form work as specified and directed by Engr-in-Charge
M&L for Replacemrnt of unservicable rubber belt NO- 105/106 all as directed by Engineer-in-Charge.
M&L for Repair of unservicable motor of 20 HP capacity 415V, 50Hz and rewinding the same with PVC insulated copper wire of existing gauge ,weight, size etc complete including all insulations, varnishing, heating etc and making all connections & testing to make it functional complete all as directed .
M&L for Repair of unservicable star delta motor starter suitable for 20 Hp motor complete all as specified and directed EIC.
Excavation in trenches not exc 1.5 mtr wide & not exc 1.5 mtr in depth for foundation etc or for shafts , wells, cesspits, manholes, laying of pipe and exc 10 sqm on plan and n exc 1.5 m in depth getting out in Soft / loose soil complete all as specified.
Returning filling in, including spreading, levelling watering & well ramming in layers not exc 25cm thick complete all as specified and directed.
Removing excavated material to a distance not exc 50 mtr & depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified & diected.
Material and labour for narmada river sand, unwashed and screened dry for cushioning to under ground cable in trenches below and around under ground cable including spreading and levelling complete all as specified and directed.
Supply and laying reinforced precast concrete cable cover, class LV, type 1 with flat, size 250 mm x 150 mm x 40 mm complete all as directed at site. Make Mehtab or equivalent.
Taking out old unserviceable GI water tubing 50 mm to 80 mm,from the wall ,floor or from the trench including all fittings and fixtures complete all as specified and as directed.
Taking out old unserviceable GI water tubing 25 mm to 40 mm,from the wall ,floor or from the trench including all fittings and fixtures complete all as specified and as directed.
Cutting of existing GI water tubing 50 mm to 80 mm for additions or alterations complete all as specified and as directed.
Cutting of existing GI water tubing 25 mm to 40 m for addition or alterations complete all as specified and as directed.
Supply , laying, jointing and testing GI tubing medium grade 25 mm dia with one socket both end threaded in any length including cutting threading connection in new or old position and all type of GI new fittings for laid in trenches/wall/ceiling/ floor/ all as specified and directed. Make:- Tata, Jindal, Prakash
Supply , laying, jointing and testing GI tubing medium grade 40 mm bore dia with one socket both end threaded in any length including cutting threading connection in new or old position and all type of GI new fittings for laid in trenches/wall/ceiling/ floor/ all as specified and directed.Make:- Tata, Jindal, Prakash
Supply , laying, jointing and testing GI tubing medium grade 50 mm bore with one socket both end threaded in any length including cutting threading connection in new or old position and all type of GI new fittings for laid in trenches/wall/ceiling/ floor/ all as specified and directed .Make:- Tata, Jindal, Prakash
Supply , laying, jointing and testing GI tubing medium grade 80 mm dia with one socket both end threaded in any length including cutting threading connection in new or old position and all type of GI new fittings for laid in trenches/wall/ceiling/ floor/ all as specified and directed.Make:- Tata, Jindal, Prakash
Supply and Fixing Gun metal gate valve ISI marked) with spindle and iron wheel, both endsscrewed, for 25 mm bore iron pipe including fittings and fixtures, as required, complete all as specified and as directed. Make :- Kirloskar, Seiko , Leader, Zoloto
Supply and Fixing Gun metal gate valve ISI marked) with spindle and iron wheel, both endsscrewed, for 40 mm bore iron pipe including fittings and fixtures, as required, complete all as specified and as directed. Make :- Kirloskar, Seiko , Leader, Zoloto
Supply and Fixing Gun metal gate valve ISI marked) with spindle and iron wheel, both endsscrewed, for 50 mm bore iron pipe including fittings and fixtures, as required, complete all as specified and as directed. Make :- Kirloskar, Seiko , Leader, Zoloto
Lifting the 15 HP submersible pump from bore well,including flange joints of delivery pipe, dismantling the flanged joints, lowering the submersible pump after repairing, by tightening the flanged joints of column pipe, re-fixing of existing safety bucket with steel rope complete to make it operational/functional all as per specified and as directed.
Taking out the old unserviceable winding and cleaning the slots of submersible pump motor, 15 HP and rewinding the same with PVC insulated copper wire of existing gauge ,weight, size etc complete including all insulations, varnishing, heating etc and making all connections & testing to make it functional complete all as directed .
Dismantling the submersible pump of 15 HP , cleaning, repairing, overhauling replacement of all unserviceable parts, nut, bolts, impellars, bushes, thrust bearing, clutch system, bowl assembly and repairing/replacement of pump shaft and re-assembling, commissioning and testing to make it operational / functional complete all as specified and as directed
M&L for lifting the 10 HP submersible pump from bore well,including flange joints of delivery pipe, dismantling the flanged joints, lowering the submersible pump after repairing, by tightening the flanged joints of column pipe, re-fixing of existing safety bucket with steel rope complete to make it operational / functional all as per specified and directed
Taking out the old unserviceable winding and cleaning the slots of submersible pump motor, 10 HP and rewinding the same with PVC insulated copper wire of existing gauge ,weight, size etc complete including all insulations, varnishing, heating etc and making all connections & testing to make it functional complete all as directed .
Dismantling / Taking down the submersible pump of 10 HP , cleaning, repairing, overhauling replacement of all unserviceable parts, nut, bolts, impellars, bushes, thrust bearing, clutch system, bowl assembly and repairing/replacement of pump shaft and . Re-assembling, commissioning and testing to make it operational/functional complete all as specified and as directed
Taking out the old unserviceable winding and cleaning the slots of centrifugal pump motor, 5 HP to 15 HP and rewinding the same with PVC insulated copper wire of existing gauge ,weight, size etc complete including all insulations, varnishing, heating etc and making all connections & testing to make it functional complete all as directed .
Supply and fixing in repalcement of DOL startor suitable for three phase centrifugal pump upto 15 HP. Complete all as specified and as directed Make:- L&T Cat No- SS94352 or equivalent of ABB, Legrand, Schneider.
Supply and fixing in replacement startor suitable for three phase submersible pump 15 HP.complete all as specified and as directed Make:- L&T Cat No-CS94091 or equivalent of ABB, Legrand, Schneider
XLPE insulated, armoured, heavy duty electric cable with aluminium conductor, 1100 volts grade, cross- sectional area 25 sq. mm, 3.5 Core.
Vinayak Trading House
SUNIL ENTERPRISE
MODI CORPORATION
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .