Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
| 4 | Admitted-Finance | Admitted-Finance |
| 5 | Rejected-Technical | Rejected-Technical Techno commercially Not Acceptable |
Tender Value
Refer Docs
EMD Value
₹43.5 L
Closing Date
12 Dec 2024, 3:00 pmClosed
Mr.Amit Borkar
thyssenkrupp Uhde India Pvt Ltd Vikhroli Mumbai India
ELECTRICAL WORKS FOR PFCC UNIT AT NREP
2024_NRL_826799_1
TK-1P25A-MP-RFQ-0052
Open Tender
Electrical Works
540 days
Numaligarh Refinary Limited Assam
As per Tender
9 documents required · 9 mandatory
₹0
₹43.5 L
Yes
ONLINE
17 Mar 2025
20 Sept 2024
13 Dec 2024
20 Sept 2024
12 Dec 2024
14 Oct 2024
20 Sept 2024 - 5 Oct 2024
7 Oct 2024
Amount
GENERAL NOTES (1) This document shall be read in conjunction with doc. 'ANNEXURE-II' TO SCC - 'SCOPE OF SUPPLY - ELECTRICAL'. Technical Specification for the equipment / material to be supplied by CONTRACTOR is included therein. (2) For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. (3) Refer the document 'LIST OF APPROVED VENDORS / MAKES - ELECTRICAL' for the makes of equipment / material to be supplied by CONTRACTOR (4) For all the equipment (suitable for Explosive Atmospheres) to be supplied by CONTRACTOR, relevant certification from applicable recognised approving authority shall be provided. (5) For CONTRACTOR supplied items mentioned below, procurement / supply clearance for the items shall be given to CONTRACTOR, in lots as per Project requirement. Subsequent to the receipt of procurement / supply clearance, CONTRACTOR may initiate the required action in this regard. (6) CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any miss outs in supply scope in this regard by the CONTRACTOR shall not be entertained.
EQUIPMENT
LV PANELS (WALL / CONCRETE / STEEL STRUCTURE MOUNTED) Supply of LV panels (wall / concrete / steel structure mounted) as per doc. no.TK-1ZZZA-EL-SPE-0017 (Technical specification for Industrial Equipment) and TK-1ZZZA-EL-SPE-0018 (Technical Specification for Flameproof Equipment)
Industrial Indoor type
LDB Lighting Distribution Board)
ELDB (Emergency Lighting Distribution Board)
PDB (Auxiliary Power Distribution Boards)
PDB for MMS room for Instrumentation use (Power Distribution Boards - Refer Annexure-EW4-15I for feeder details)
Industrial Outdoor type
LDB Lighting Distribution Board)
ELDB (Emergency Lighting Distribution Board)
For Explosive Atmospheres
LDB Lighting Distribution Board)
ELDB (Emergency Lighting Distribution Board)
PDB (Auxiliary Power Distribution Boards)
PDB for Hydro Jet area (Auxiliary Power Distribution Boards) feeder pillar with 1No. 400A I/C and outgoings with 2Nos.250A and 1 no.125A and 1 no. of 63A (Installation type : P10)
Isolator switch for elevator 1U64-SS15-ELV-01-ISO for 63A
LOCAL CONTROL STATIONS (LCS) Supply of Local Control Stations as per doc. no. TK-1ZZZA-EL-SPE-0021 (Technical Specification for Local Control Stations)
LCS Industrial type
Type H1 : Industrial type weatherproof : Stop PB (Red) Mushroom type, with stay put feature, with pad locking facility, with 2NO+2NC contacts + ON lamp
LCS for Explosive Atmospheres
Type A3 : Flameproof (Gas Group : IIC) : Start PB (Green); Stop PB (Red) with stay put feature, shrouded type, with pad locking facility & each PB shall have 2NO+2NC contacts
Type B3 : Flameproof (Gas Group : IIC) : Start PB (Green, shrouded type); Stop PB (Red) Mushroom type, with stay put feature, with pad locking facility & each PB shall have 2NO+2NC contacts & Ammeter (1A, MI type)
Type J3 : Flameproof (Gas Group : IIC) : Stop PB (Red), Mushroom type, with stay put feature, with pad locking facility & with 2NO+2NC contacts
Type P3 : Flameproof (Gas Group : IIC) :Trip-Neutral-Close (T-N-C) switch shall be spring return to neutral type from CLOSE position with two contacts each for time stamping & tripping signal. Switch shall be lockable in TRIP position & Ammeter (1A, MI type)
CABLES AND WIRES, GLANDING, TERMINATIONS AND CABLE ROUTING SYSTEMS
CABLE GLANDING AND TERMINATION (HV)
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE)
HV Cable gland suitable for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE) (OD 51 mm)
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE) (OD 51 mm)
HV Cable termination kit Heat shrinkable type (suitable for indoor installation) for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE) (OD 51 mm)
HV Cable termination kit Heat shrinkable type (suitable for indoor installation) for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE) (OD 51 mm)
CABLE GLANDING AND TERMINATION (LV)
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
4 x Pair x 2.5 (OD : 26.6 mm)
8 x Triad x 1.5 (OD : 33.2 mm)
3 x Triad x 2.5 (OD : -----mm)
2C x 2.5 Sq. mm (2XWY) (OD : 14 mm)
2C x 4 Sq. mm (2XWY) (OD : 15.5 mm)
2C x 6 Sq. mm (2XWY) (OD : 16.6 mm)
2C x 10 Sq. mm (2XWY) (OD : 18.5 mm)
2C x 16 Sq. mm (2XWY/2XFY) (OD : 18.8 mm)
3C x 2.5 Sq. mm (2XWY) (OD : 14 mm)
3C x 4 Sq. mm (2XWY) (OD : 15 mm)
3C x 6 Sq. mm (2XWY) (OD : 16.5 mm)
3C x 10 Sq. mm (2XWY) (OD : 18.5 mm)
3C x 16 Sq. mm (2XWY/2XFY) (OD : 19.7 mm/17.8 mm)
4C x 2.5 Sq. mm (2XWY) (OD : 15 mm)
4C x 4 Sq. mm (2XWY) (OD : 16 mm)
4C x 6 Sq. mm (2XWY) (OD : 17.5 mm)
4C x 10 Sq. mm (2XWY/2XFY) (OD : 21.8 mm)
4C x 16 Sq. mm (2XWY/2XFY) (OD : 22.8 mm/21.2 mm)
5C x 2.5 Sq. mm (2XWY) (OD : 16 mm)
6C x 2.5 Sq. mm (2XWY) (OD : 17.2 mm)
7C x 2.5 Sq. mm (2XWY) (OD : 17 mm)
8C x 2.5 Sq. mm (2XWY) (OD : 18.0 mm)
10C x 2.5 Sq. mm (2XFY) (OD : 19.5 mm)
12C x 2.5 Sq. mm (2XFY) (OD : 22.2 mm)
16C x 2.5 Sq. mm (2XFY) (OD : 22.0 mm)
24C x 2.5 Sq. mm (2XFY) (OD : 26.7 mm)
2C x 25 Sq. mm (A2XFY) (OD : 19.6 mm)
2C x 35 Sq. mm (A2XFY) (OD : 20.6 mm)
2C x 50 Sq. mm (A2XFY) (OD : 22.7 mm)
2C x 70 Sq. mm (A2XFY) (OD : 25.5 mm)
2C x 95 Sq. mm (A2XFY) (OD : 28.4 mm)
2C x 120 Sq. mm (A2XFY) (OD : 30.3 mm)
2C x 150 Sq. mm (A2XFY) (OD : 33.8 mm)
2C x 185 Sq. mm (A2XFY) (OD : 37.1 mm)
2C x 240 Sq. mm (A2XFY) (OD : 40.2 mm)
3C x 25 Sq. mm (A2XFY) (OD : 21 mm)
3C x 35 Sq. mm (A2XFY) (OD : 23 mm)
3C x 50 Sq. mm (A2XFY) (OD : 26 mm)
3C x 70 Sq. mm (A2XFY) (OD : 29 mm)
3C x 95 Sq. mm (A2XFY) (OD : 33 mm)
3C x 120 Sq. mm (A2XFY) (OD : 36 mm)
3C x 150 Sq. mm (A2XFY) (OD : 39.2 mm)
3C x 185 Sq. mm (A2XFY) (OD : 45 mm)
3C x 240 Sq. mm (A2XFY) (OD : 51 mm)
3C x 300 Sq. mm (A2XFY) (OD : 53 mm)
4C x 25 Sq. mm (A2XFY) (OD : 22.2 mm)
4C x 35 Sq. mm (A2XFY) (OD : 27 mm)
4C x 50 Sq. mm (A2XFY) (OD : 30 mm)
4C x 70 Sq. mm (A2XFY) (OD : 34 mm)
4C x 95 Sq. mm (A2XFY) (OD : 37 mm)
4C x 120 Sq. mm (A2XFY) (OD : 41 mm)
4C x 150 Sq. mm (A2XFY) (OD : 45 mm)
4C x 185 Sq. mm (A2XFY) (OD : 50 mm)
4C x 240 Sq. mm (A2XFY) (OD : 57 mm)
4C x 300 Sq. mm (A2XFY) (OD : 59.5 mm)
1C x 400 Sq. mm (A2XFY/A2XWY) (OD : 34 mm / 36.5 mm)
1C x 500 Sq. mm (A2XFY/A2XWY) (OD : 37.5 mm / 39.5 mm)
1C x 630 Sq. mm (A2XWaY) (OD : 43.5 mm)
3.5C x 150 Sq. mm (A2XFY) OD 51mm
3.5C x 300 Sq. mm (A2XFY) OD 65mm
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, unarmoured power cables (for battery banks)
1 C x 68.3 sq.mm (Uninyvin Cable) (OD : 12.4 mm)
1 C x 84.2 sq.mm (Uninyvin Cable) (OD : 14 mm)
Cable glands suitable for 650 V voltage grade, Cu conductor (stranded / solid), XLPE / PVC insulated, armoured / unarmoured cables for FIRE ALARM AND COMMUNICATION SYSTEM CABLES
1P x 0.5 sq.mm (OD : 13.2 mm)
2P x 0.5 sq.mm (OD : 16.4 mm)
5P x 0.5 sq.mm (OD : 18 mm)
10P x 0.5 sq.mm (OD : 21.0 mm)
24P x 0.5 sq.mm (OD : 29.5 mm)
1P x 1.5 sq.mm (OD : 14 mm)
2P x 1.5 sq.mm (OD : 21.4 mm)
12P x 1.5 sq. mm (OD : 32 mm)
20P x 1.5 sq.mm
50P x 1.5 sq.mm
100P x 1.5 sq.mm
1P x 2.5 sq.mm (OD : 23.3 mm)
2P x 2.5 sq.mm (OD : 23.3 mm)
4P x 2.5 sq.mm (OD : 26.6 mm)
12P x 2.5 sq. mm (OD : 38.6 mm)
20P x 2.5 sq.mm
8Fibre FO CABLE
CAT 6 CABLE
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
4 x Pair x 2.5 (OD : 26.6 mm)
8 x Tried x 1.5 (OD : 33.2 mm)
2C x 2.5 Sq. mm (2XWY) (OD : 14 mm)
2C x 4 Sq. mm (2XWY) (OD : 15.5 mm)
2C x 6 Sq. mm (2XWY) (OD : 16.6 mm)
2C x 10 Sq. mm (2XWY) (OD : 18.5 mm)
2C x 16 Sq. mm (2XWY/2XFY) (OD : 18.8 mm)
3C x 2.5 Sq. mm (2XWY) (OD : 14 mm)
3C x 4 Sq. mm (2XWY) (OD : 15 mm)
3C x 6 Sq. mm (2XWY) (OD : 16.5 mm)
3C x 10 Sq. mm (2XWY) (OD : 18.5 mm)
3C x 16 Sq. mm (2XWY/2XFY) (OD : 19.7 mm/17.8 mm)
4C x 2.5 Sq. mm (2XWY) (OD : 15 mm)
4C x 4 Sq. mm (2XWY) (OD : 16 mm)
4C x 6 Sq. mm (2XWY) (OD : 17.5 mm)
4C x 10 Sq. mm (2XWY/2XFY) (OD : 21.8 mm)
4C x 16 Sq. mm (2XWY/2XFY) (OD : 22.8 mm/21.2 mm)
5C x 2.5 Sq. mm (2XWY) (OD : 16 mm)
6C x 2.5 Sq. mm (2XWY) (OD : 17.2 mm)
7C x 2.5 Sq. mm (2XWY) (OD : 17 mm)
8C x 2.5 Sq. mm (2XWY) (OD : 18.0 mm)
10C x 2.5 Sq. mm (2XFY) (OD : 19.5 mm)
12C x 2.5 Sq. mm (2XFY) (OD : 22.2 mm)
16C x 2.5 Sq. mm (2XFY) (OD : 22.0 mm)
24C x 2.5 Sq. mm (2XFY) (OD : 26.7 mm)
3C x 25 Sq. mm (A2XFY) (OD : 21 mm)
3C x 35 Sq. mm (A2XFY) (OD : 23 mm)
3C x 50 Sq. mm (A2XFY) (OD : 26 mm)
3C x 70 Sq. mm (A2XFY) (OD : 29 mm)
3C x 95 Sq. mm (A2XFY) (OD : 33 mm)
3C x 120 Sq. mm (A2XFY) (OD : 36 mm)
3C x 150 Sq. mm (A2XFY) (OD : 39.2 mm)
3C x 185 Sq. mm (A2XFY) (OD : 45 mm)
3C x 240 Sq. mm (A2XFY) (OD : 51 mm)
3C x 300 Sq. mm (A2XFY) (OD : 53 mm)
4C x 25 Sq. mm (A2XFY) (OD : 22.2 mm)
4C x 35 Sq. mm (A2XFY) (OD : 27 mm)
4C x 50 Sq. mm (A2XFY) (OD : 30 mm)
4C x 70 Sq. mm (A2XFY) (OD : 34 mm)
4C x 95 Sq. mm (A2XFY) (OD : 37 mm)
4C x 120 Sq. mm (A2XFY) (OD : 41 mm)
4C x 150 Sq. mm (A2XFY) (OD : 45 mm)
4C x 185 Sq. mm (A2XFY) (OD : 50 mm)
4C x 240 Sq. mm (A2XFY) (OD : 57 mm)
4C x 300 Sq. mm (A2XFY) (OD : 59.5 mm)
1C x 400 Sq. mm (A2XFY/A2XWY) (OD : 34 mm / 36.5 mm)
1C x 500 Sq. mm (A2XFY/A2XWY) (OD : 37.5 mm / 39.5 mm)
1C x 630 Sq. mm (A2XWaY) (OD : 43.5 mm)
3.5C x 150 Sq. mm (A2XFY)
3.5C x 300 Sq. mm (A2XFY)
Cable glands suitable for 650 V voltage grade, Cu conductor (stranded / solid), XLPE / PVC insulated, armoured / unarmoured cables for FIRE ALARM AND COMMUNICATION SYSTEM CABLES
1P x 0.5 sq.mm (OD : 13.2 mm)
2P x 0.5 sq.mm (OD : 16.4 mm)
5P x 0.5 sq.mm (OD : 18 mm)
10P x 0.5 sq.mm (OD : 21.0 mm)
24P x 0.5 sq.mm (OD : 29.5 mm)
1P x 1.5 sq.mm (OD : 14 mm)
2P x 1.5 sq.mm (OD : 21.4 mm)
12P x 1.5 sq. mm (OD : 32 mm)
20P x 1.5 sq.mm
50P x 1.5 sq.mm
100P x 1.5 sq.mm
1P x 2.5 sq.mm (OD : 23.3 mm)
2P x 2.5 sq.mm (OD : 23.3 mm)
4P x 2.5 sq.mm (OD : 26.6 mm)
12P x 2.5 sq. mm (OD : 38.6 mm)
20P x 2.5 sq.mm
LV Cable gland reducers Industrial type
M20 x 1.5 (Male thread) to M16 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M80 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
LV Cable gland expander Industrial type
M16 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M20 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M80 x 1.5 (Female thread)
LV Cable gland reducers for Explosive Atmospheres
M20 x 1.5 (Male thread) to M16 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M80 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
LV Cable gland expander for Explosive Atmospheres
M16 x 1.5 (Male thread) to M20 x 1.5 (Female thread)
M20 x 1.5 (Male thread) to M25 x 1.5 (Female thread)
M25 x 1.5 (Male thread) to M32 x 1.5 (Female thread)
M32 x 1.5 (Male thread) to M50 x 1.5 (Female thread)
M50 x 1.5 (Male thread) to M63 x 1.5 (Female thread)
M63 x 1.5 (Male thread) to M80 x 1.5 (Female thread)
Tinned copper, insulated, Pin type lugs
Tinned copper, insulated, Ring type lugs
Tinned copper, tubular type, heavy duty lugs for bolted connection
Tinned copper, tubular type, long barrel type heavy duty lugs for bolted connection
Tinned copper, tubular type, large diameter lugs for bolted connection of earthing conductor
8 mm dia. GI wire rope
10 mm dia. GI wire rope
16 mm dia. GI wire rope
Tinned copper, insulated, Pin type lugs (for Paired Cable)
Cable entry blanking plugs Industrial type
M16 (OD 13mm)
M20 ( OD 19.5 MM)
M25 ( OD 25.5mm)
M32 (OD 32.9mm)
M50 (OD 51mm)
M63 (OD 59mm)
Cable entry blanking plugs For Explosive Atmospheres
M16 (OD 13mm)
M20 ( OD 19.5 MM)
M25 ( OD 25.5mm)
M32 (OD 32.9mm)
M50 (OD 51mm)
M63 (OD 59mm)
CABLE JOINTING
Cable straight through jointing kit indoor type - Supply of cable jointing kit along with all the associated accessories as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
HV Cable straight through jointing kit Heat shrinkable type (suitable for indoor installation) for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
HV Cable straight through jointing kit Heat shrinkable type (suitable for indoor installation) for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE)
PREFABRICATED CABLE TRAYS
Prefabricated Cable Trays (GI) - Supply of prefabricated GI perforated and ladder type cable tray / covers, tray separators along with all the associated consumable material for assembly and appropriate installation of the same, as per doc. no. TK-1ZZZA-EL-SPE-0016 (Technical Specification for GI cable Trays)
Cable Trays Perforated (GI) (Length 3 mtr per piece) including required hardware as per Installation dwg
50 mm wide
100 mm wide
150 mm wide
Coupler plates along with SS304 fixing hardware
GI Coupler plates with 3 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) for 50/100/150 W perforated cable trays mentioned above. (Note : 1 no. set = 2 nos. coupler plates each)
Stainless Steel Coupler plates with 2 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) for 50/100/150 W perforated cable trays mentioned above. (Note : 1 no. set = 2 nos. coupler plates each)
Tray Covers (length 3 mtr per piece) with fixing clamps (at every 1 meter) along with necessary SS304 hardware
150 mm wide
100 mm wide
Cable Ladders (GI) (Length 3 mtr per piece)
150 mm wide
300 mm wide
450 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree horizontal bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 300mm)
300 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Inside Vertical bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 300mm)
300 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 90 degree Outside Vertical bends (Bending Radius 1200mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree horizontal bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Inside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 300mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 600mm)
300 mm wide
600 mm wide
Pre-Fabricated 45 degree Outside Vertical bends (Bending Radius 900mm)
300 mm wide
600 mm wide
Pre Fabricated Cable Tray Reducer
600 to 300 mm Reducer, Right Hand Side
300 to 150 mm Reducer, Right Hand Side
300 to 150 mm Reducer, Left Hand Side
Pre Fabricated Equal Tee’s (Bending Radius-300 mm)
300 mm wide
600 mm wide
Pre Fabricated Equal Tee’s (Bending Radius-600 mm)
300 mm wide
600 mm wide
Pre Fabricated Equal Tee’s (Bending Radius-900 mm)
300 mm wide
600 mm wide
Pre Fabricated Unequal Tee’s (Bending Radius-300 mm)
300 x 150 x 300 mm wide
600 x 150 x 600 mm wide
600 x 300 x 600 mm wide
Pre Fabricated Unequal Tee’s (Bending Radius-600 mm)
300 x 150 x 300 mm wide
600 x 150 x 600 mm wide
600 x 300 x 600 mm wide
Coupler plates along with SS304 fixing hardware
GI Coupler plates with 3 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel nut, bolt, lock-nut) for 150/300/450/600 W ladder type cable trays mentioned above. (Note : 1 no. set = 4 nos. coupler plates each)
Stainless Steel Coupler plates with 2 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel nut, bolt, lock-nut) for 150/300/450/600 W ladder type cable trays mentioned above. (Note : 1 no. set = 4 nos. coupler plates each)
Hinged GI plates for below bends with 3 mm thick, 4 holes on both the sides of size M10 hole & M8 hardware (along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut) for 150/300/450/600 W ladder type cable trays mentioned above. (Note : 1 no. set = 4 nos. coupler plates each)
Hinged GI plates for Horizontal 45 degree bends
Hinged GI plates for Vertical 45 degree bends
Clamps for fixing 45 degree Horizontal & Vertical Cable Tray cover along with necessary fixing hardware – stainless steel (SS304) nut, bolt, lock-nut for ladder type cable trays mentioned above.
Clamps for 300 mm wide tray
Clamps for 600 mm wide tray
Cable Tray Covers (GI) (Length 3 mtr per piece)
150 mm wide
300 mm wide
450 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 900 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 900 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 900 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 900 Bends (Bending Radius-1200 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Inside Vertical 900 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
Pre Fabricated Tray Cover for Inside Vertical 900 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Inside Vertical 900 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Inside Vertical 900 Bends (Bending Radius-1200 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 900 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 900 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 900 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 900 Bends (Bending Radius-1200 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 450 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 450 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Horizontal 450 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for inside Vertical 450 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for inside Vertical 450 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
600 mm wide
Pre Fabricated Tray Cover for inside Vertical 450 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 450 Bends (Bending Radius-300 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 450 Bends (Bending Radius-600 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Outside Vertical 450 Bends (Bending Radius-900 mm) with 2 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Cable Tray Reducer with 2 nos. fixing clamps along with necessary SS304 hardware
600 to 300 mm Reducer, Right Hand Side
300 to 150 mm Reducer, Right Hand Side
300 to 150 mm Reducer, Left Hand Side
Pre Fabricated Tray Cover for Equal Tee’s (Bending Radius-300 mm) with 3 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Equal Tee’s (Bending Radius-600 mm) with 3 nos. fixing clamps along with necessary SS304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Equal Tee’s (Bending Radius-900 mm) with 3 nos. fixing clamps along with necessary S3304 hardware
300 mm wide
600 mm wide
Pre Fabricated Tray Cover for Unequal Tee’s (Bending Radius-300 mm) with 3 nos. fixing clamps along with necessary SS304 hardware
300 x 300 x 150 mm wide
600 x 600 x 150 mm wide
600 x 600 x 300 mm wide
Pre Fabricated Tray Cover for Unequal Tee’s (Bending Radius-600 mm) with 3 nos. fixing clamps along with necessary SS304 hardware
300 x 300 x 150 mm wide
600 x 600 x 150 mm wide
600 x 600 x 300 mm wide
Z Clamps for Holding Horizontal Cable Tray, Material - HDGI, thickness - 2 mm with necessary fixing hardware with (with M12 hole & M10 hardware SS304 nut, bolt, lock-nut)
Separators for Cable Ladders (GI)
300 mm / 600 mm wide
CONDUITS FOR CABLE LAYING / PROTECTION AND PULL BOXES - Supply of heavy duty rigid GI / PVC conduits and all the associated accessories - Supply of accessories such as GI clamps, joints, bends reducers / adaptors for the conduits and other consumable material such as edge protection grommet at either ends for GI conduits as per the site requirement is considered in running meter length of the conduits.
Rigid GI conduits
25 mm nominal dia
50 mm nominal dia
150 mm nominal dia
Rigid GI conduits RED coloured (For Fire Alarm System cables)
25 mm nominal dia
50 mm nominal dia
Heavy duty PVC conduits
25 mm nominal dia
50 mm nominal dia
150 mm nominal dia
Flexible PVC conduits
20 mm nominal dia
25 mm nominal dia
Pull boxes for cable pulling in conduits Supply of pull boxes (GI enclosure)
4 way Pull boxes,100mm L x 100mm W x 75mm D, 1no. 25mm knockout on all four sides
4 way Pull boxes, 115mm L x 115mm W x 75mm D, 2nos. 25 mm knockout on all four sides
4 way Pull boxes, 265mm L x 165mm W x 75mm D, 5nos. 25mm knockout at top / bottom and 2nos. 25mm knockout on each sides.
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING
Lighting fixtures Supply of lighting fixtures and associated components / accessories such as lamps, chokes, condensers, reflectors, control gear box for non-integral fixtures etc. as per doc. no. TK-1ZZZA-EL-SPE-0019 (Technical Specification for Industrial Light Fixture) and TK-1ZZZA-EL-SPE-0020 (Technical Specification for Flameproof Light Fixture)
Lighting Fixtures Industrial type
2x20W LED Tube Light Fixture
2x20W LED Tube Light Fixture Emergency
10W LED Bulkhead Light Fixture
11W Decorative Down Light fixture suitable for false ceiling
36W LED recessed mounted square fixture suitable for False Ceiling
36W LED recessed mounted square fixture suitable for False Ceiling Emergency
40W LED Well glass Light Fixture
40W LED Well glass Light Fixture Emergency
100W LED Medium Bay Light Fixture
100W LED Medium Bay Light Fixture Emergency
26W, 110V DC LED Tube Light Fixture
Lighting Fixtures for Explosive Atmospheres
40W LED Ex-d FLP Well Glass Light Fixture
40W LED Ex-d FLP Well Glass Light Fixture Emergency
100W LED Ex-d FLP Medium Bay Light Fixture
100W LED Ex-d FLP Medium Bay Light Fixture Emergency
150W LED Ex-d FLP Flood Light fixture
20W LED Ex-d FLP Aviation Light
150W LED Ex-d FLP Flood Light fixture Emergency
40W LED FLP Corrosion Resistant Tube Light Fixture
40W LED FLP Corrosion Resistant Tube Light Fixture Emergency
26W, 110V DC LED Ex-d FLP Well Glass Fixture
Special Lighting fixtures Supply of special lighting fixtures and all the associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Emergency lighting fixture with built-in battery
1x18W, Fluorescent, Industrial
1x18W, Fluorescent, for Explosive Atmospheres
Emergency EXIT sign with built-in battery Refer 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL' for the 'Type designations' (TYPE-1, TYPE-2 etc.) mentioned below.
Hand lamps
24V Industrial Hand lamps along with 20m extension cable 3c x 1.5sq.mm, YY, 20m, along with the plug suitable for 24V, 5A Industrial switch socket
24V Hand lamps for Explosive Atmospheres along with 20m extension cable 3c x 1.5sq.mm, YY, 20m, along with the plug suitable for 24V, 5A Industrial switch socket
EXHAUST FANS AND CEILING FANS
Industrial type Exhaust fans Supply of Industrial type Exhaust fans and associated accessories such as louvers and bird screen, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
300mm dia.
450mm dia.
600mm dia.
Exhaust fans for Explosive Atmospheres Supply of Exhaust fans for Explosive Atmospheres and associated accessories such as louvers and bird screen, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
300mm dia.
450mm dia.
600mm dia.
Ceiling fans
Supply of 230V, single phase Ceiling Fan 1200mm sweep with electronic speed regulator
Pedestal fans
Supply of 230V, single phase, 600mm dia. pedestal fans
SMALL POWER Supply of various small power equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Switch socket outlets
Decorative type switch socket outlets
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 1 no. modular piano type switch
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 2 nos. modular piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 3 nos. modular piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 5 nos. modular piano type switches
Decorative type single phase socket outlet with 1no. 5/15A socket
Decorative type switch in single module with 1 no. 5A modular piano type switches
Decorative type switch in double module with 2 no. 5A modular piano type switches
Decorative type switch in tripple module with 3 no. 5A modular piano type switches
Decorative type switch in quad module with 4 no. 5A modular modular piano type switches
Decorative type switch socket switchboard with 5/15A, 5 pin, socket outlet with 15A switch and 'ON' LED indication & fuse
Industrial type switch socket outlets (for Indoor Installation)
10A, single phase socket outlet with 1no. 3 pin socket, in sheet steel enclosure
10A, single phase socket outlet with 1 No. 10 A, 10 kA, SPMCB, in sheet steel enclosure
10A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 10 A, 10 kA, SPMCB, in sheet steel enclosure
20A, single phase socket outlet with 1no. 3 pin socket, in sheet steel enclosure
20A, single phase socket outlet with 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
20A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
Convenience Switch socket outlets
Industrial Convenience sockets (single phase)
16A, 3 pin single phase socket outlet with DPMCB in die cast Al LM6 enclosure, Type S02
32A, 3 pin single phase socket outlet with DPMCB in die cast Al LM6 enclosure , Type S??
Convenience sockets (single phase) for Explosive Atmospheres
16A, 3 pin,240V AC single phase socket outlet with DPMCB in die cast Al LM6 enclosure, Type S01
32A, 3 pin single phase socket outlet with DPMCB in die cast Al LM6 enclosure , Type S??
Industrial switch socket unit (portable)
24V, 5A Industrial switch socket unit with built-in 100VA, 220V / 24V transformer
Switch socket unit (portable) for Explosive Atmospheres
240V,16A and 24V, 5A combination type switch socket unit for Explosive Atmospheres, with built-in 100VA, 240V / 24V transformer
JUNCTION BOXES (JB) / POWER JUNCTION BOXES (JB) - Supply of various types of junction boxes / power junction boxes suitable for the required cable entries and all associated accessories, as per doc. no.TK-1ZZZA-EL-SPE-0017 (Technical specification for Industrial Equipment) and TK-1ZZZA-EL-SPE-0018 (Technical Specification for Flameproof Equipment) - Supply of junction boxes suitable for bottom entry of incoming and outgoing cables, inclusive of suitable terminals for undrilled gland plate, cable terminations, busbars for cable termination as required, facility for earthing cable termination inside and outside the termination, along with the associated accessories such plugs for cable openings, fixing hardware
Junction boxes Industrial type
Junction boxes (Indoor)
4 way Lighting JB, Indoor
5 way JB for small power sockets , Indoor
Junction boxes (Outdoor)
4 way Lighting JB, Outdoor
4 way Welding socket JB, Outdoor
Communication Junction Boxes
Indoor FA System JB For housing addressable module of 1 no. Exit Light Incoming : 2Px1.5 sq.mm(1 No.) - M25 + 1Px2.5 sq.mm(1 No.) - M20 Outgoing : 2Px1.5 sq.mm(1 No.) - M25 + 1Px2.5 sq.mm(1 No.) - M20
Indoor FA System JB For end of resistor / Fault Isolator Incoming : 2Px1.5 sq.mm(1 No.) - M25 Outgoing : 2Px1.5 sq.mm(1 No.) - M25
Indoor PA System JB for Speakers Incoming : 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Outdoor PA System JB for Speakers Incoming : 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Indoor PA System JB for FCS Incoming : 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Indoor Telephone System JB (IDF) Incoming : 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Junction boxes for Explosive Atmospheres
Junction boxes
4 way Lighting JB, Ex-d
5 way JB for small power sockets, Ex-d
4 way Welding socket JB, Ex-d
For 15kW Motor with Incoming cable size 1R-3Cx70sq.mm and outgoing cable size 1R-3Cx50sq.mm
For 15kW Motor with Incoming cable size 1R-3Cx95sq.mm and outgoing cable size 1R-3Cx70sq.mm (1P26-PM-7001A/B)
For 45kW Motor with Incoming cable size 1R-3Cx240sq.mm and outgoing cable size 1R-3Cx150sq.mm
For 90kW Motor with Incoming cable size 2R-3Cx240sq.mm and outgoing cable size 2R-3Cx95sq.mm
For 90kW Motor with Incoming cable size 3R-3Cx240sq.mm and outgoing cable size 2R-3Cx240sq.mm
For 110kW Motor with Incoming cable size 3R-3Cx240sq.mm and outgoing cable size 2R-3Cx240sq.mm
For 132kW Motor with Incoming cable size 4R-3Cx240sq.mm and outgoing cable size 2R-3Cx240sq.mm
For 160kW Motor with Incoming cable size 4R-3Cx300sq.mm and outgoing cable size 2R-3Cx300sq.mm
Power JB for Instrumentation Analizer Cabinet for Analyzer Transmitter (CO/CO2) & CEMS Building : Incoming cable size 1R-2Cx240sq.mm and outgoing cable size 1R-2Cx50sq.mm (Inside RxRG package)-PFCC Area
Power JB for Instrumentation CEMS Building : Incoming cable size 1R-2Cx185sq.mm and outgoing cable size 1R-2Cx50sq.mm (Inside RxRG package) -PFCC Area
Power JB for Instrumentation PRU analyzer : Incoming cable size 1R-2Cx150sq.mm and outgoing cable size 1R-2Cx50sq.mm -PFCC Area
For 160kW Motor with Incoming cable size 4R-3Cx300sq.mm and outgoing cable size 2R-3Cx300sq.mm
Welding Socket JB : 1P27-WJB-0001 , 1P27-WJB-0002, 1P27-WJB-0003 Incoming power cable : 1R-4Cx95sq.mm Outgoing power cable : 4R- 4Cx35sq.mm
Communication Junction boxes
Indoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Indoor FA System JB for housing addressable module of 1 no. MCP Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. MCP Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Hooter / Becon Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px2.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for Housing 2 addressable modules and 2 zener barrier Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (2 Nos.) NPT thread glands : 4 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for End of resistor / Fault Isolator in FA loop Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.) NPT thread glands : 2 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor Telephone System JB (IDF) Incoming : 10Px0.63 mm dia (1 No.) Outgoing : 5Px0.63 mm dia (5 Nos.) NPT thread glands : 6 Nos. Plugs : 3 Nos. (1 No. Plug for 10Px0.63 mm dia & 2 Nos. plugs for 5Px0.63 mm dia)
Outdoor PA System JB for FCS Incoming : 12Px1.5 (1 No.) Outgoing : 2Px1.5 (6 Nos.) NPT thread glands : 7 Nos. Plugs : 2 Nos. (1 No. Plug for 12Px1.5 and 1 No. for 2Px1.5)
Outdoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
Indoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
Installation Material for Junction boxes (wall / concrete / steel structure mounted) - Supply of all the Installation Material (excluding structural steel) for Junction boxes (wall / concrete / steel structure mounted) as per 'Installation Details - Power' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : L08A
Installation Type : L08B
Installation Type : L08C
Installation Type : L08D
Installation Type : L08E
Installation Type : L08F
Installation Type : L08G
Installation Type : P10A
Installation Type : P10A/P11A
Installation Type : P10B
Installation Type : P10B
Installation Type : P12A
Installation Type : P17
Installation Type : P10A/P10B
POWER SOCKET OUTLETS Supply of various types of power socket outlets and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Industrial Power Socket Outlets
Industrial type, 415V, 63A, TPN & E socket outlet, with die cast Al LM6 enclosure , Type WS1
Industrial type, 415V, 100A, TPN & E socket outlet, with die cast Al LM6 enclosure , Type WS2
Power Socket Outlets for Explosive Atmospheres
For Explosive Atmospheres, 415V, 63A, TPN & E socket outlet, with die cast Al LM6 enclosure, Type WS3
For Explosive Atmospheres, 415V, 100A, TPN & E socket outlet, with die cast Al LM6 enclosure, Type WS4
Installation Material for Power socket outlets (wall / concrete / steel structure mounted) - Supply of all the Installation Material (excluding structural steel) for Power socket outlets (wall / concrete / steel structure mounted) as per 'Installation Details - Power' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : P10A (63A) On Steel
Installation Type : P10B (63A) On Concrete
Installation Type : P17 (63A)
Installation Type : P10A (100A) on Concrete
Installation Type : P10A (100A) on Steel
Installation Type : P10B (100A) on Concrete
Installation Type : P10B (100A) on Steel
FIRE ALARM AND COMMUNICATION SYSTEMS
FIRE ALARM (FA) SYSTEM - Supply of all the Installation Material (excluding structural steel) for FA system equipment and associated accessories as per applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation of Central FA panel (Substation & SRR)
Installation of Repeater panel (Substation SS15)
FA system accessories (Industrial / For Explosive Atmospheres)
Installation Type: FAHC1
Installation Type: FAHS1
Installation Type: FAHZ1
Installation Type: FASC1
Installation Type: FASC2
Installation Type: FASS1
Installation Type: FCPC1
Installation Type: FCPC2
Installation Type: FCPP1
Installation Type: FCPP2
Installation Type: FCPR1
Installation Type: FCPS1
Installation Type: FMDC1
Installation Type: FMDF1
Installation Type: FMDF2
Installation Type: FMDF3
Installation Type: FMDS1
Installation Type: FRIC1
Installation Type: FRIF1
Installation Type: FCPS2
Installation Type: CFBC1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08D
Installation Type: L08E
PUBLIC ADDRESS (PA) SYSTEM - Supply of all the Installation Material (excluding structural steel) for PA system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation of PA Panel
Installation of Master Control Station (Installation type: CMCS1)
PA system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFR1
Installation Type: CTFR2
Installation Type: CTFS2
Installation Type: CTFS3
Installation Type: CFBC1
Installation Type: CFBR1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKC2
Installation Type: CSPKC3
Installation Type: CSPKF1
Installation Type: CSPKP1
Installation Type: CSPKS1
Installation Type: CSPKR1
Installation Type: CMCS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08C
Installation Type: L08D
Installation Type: L08E
TELEPHONE SYSTEM Supply of all the Installation Material (excluding structural steel) for Telephone system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
Installation of Network cabinets, EPABX servers, workstations, LAN/FO Cabinets
Telephone system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFR1
Installation Type: CTFR2
Installation Type: CTFS1
Installation Type: CTFS2
Installation Type: CTFS3
Installation Type: CTFZ1
Installation Type: CTFC3
Installation Type: CFBC1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08C
Installation Type: L08D
Installation Type: L08E
Installation Type: L08F
Installation RJ45 Telephone Socket
Installation RJ45 LAN Socket
CCTV SYSTEM Supply of all the Installation Material (excluding structural steel) for CCTV system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
Installation of Network cabinets, servers, workstations, monitoring equipment & power supplies
CCTV system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTVC1
Installation Type: CTVC2
Installation Type: CTVR1
Installation Type: CTVS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08D
Installation Type: L08E
Installation Type: L08F
Installation Type: L08G
EARTHING AND LIGHTNING PROTECTION
EARTHING MATERIAL
Earthing conductor Supply of GI strip / bare copper conductor for earthing
25 x 6 mm GI strip
50 x 6 mm GI strip
75 x 10 mm GI strip
8 SWG SOLID G.I. WIRE
10 MM (3/8") DIA G.I WIRE ROPE
16 MM (5/8") DIA G.I WIRE ROPE
1C x 95 Sq.mm Cu Cable
1C x 10 Sq.mm Cu Cable
Earth / lightning protection electrodes Supply of Earth / lightning protection electrodes along with the associated accessories / material as per 'Installation Details - Earthing', including any additional hardware as per site requirement so as to ensure the completeness of installation work
Installation Type : E01A :100 mm Dia, 3 m length GI pipe earth electrode for Electrical Safety earth
Installation Type : E01B : 100 mm Dia, 6 m length GI pipe earth electrode for Instrument clean earth
Installation Type : E01A : 100 mm Dia, 3 m length GI pipe lightning protection electrode
Earth buses - Supply of Earth buses along with the associated accessories (excluding structural steel) as per 'Installation Details - Earthing' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : E02A GI earth bus for Electrical safety
Installation Type : E02B GI earth bus for Electrical safety
Installation Type : E02A - GI earth bus for instruments
Installation Type : E02B - GI earth bus for instruments
Installation Type : E20 - Mounted on cable tray for Electrical
Installation Type : E22 - Cu insulated earth bus
LIGHTNING PROTECTION MATERIAL
Lightning protection conductor - Supply of GI strip / bare copper conductor/aluminium/HDGI Round conductor for Lightning protection and associated accessories - Supply of accessories such as test links, cross connectors, parallel connectors for lightning protection down conductors, epoxy insulator supports and the associated accessories as per 'Installation Details - Lightning Protection' / as indicated in applicable construction documents / as per the site requirement, are considered in running meter length of lightning protection down conductors.
Installation Type: E16 Roof Conductor (Conductor Size- 25x6mm)
Installation Type: E16 Down Conductor (Conductor Size- 25x6mm)
Test Link : E16 : 50x6mm GI Link 150mm Long
Lightning Strike Counter device with enclosure
Lightning protection rods / finials - Supply of Lightning protection rods / finials (lightning arrestors) along with the associated accessories (excluding structural steel) as per 'Installation Details - Lightning Protection' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : E24
Installation Type : E25
Installation Type : E26
STRUCTURAL STEEL - Supply of structural steel - The quantity of structural steel indicated below is matching with the quantity of steel indicated in SECTION-F of doc. 'BILL OF QUANTITIES - INSTALLATION (ELECTRICAL)'. - Section wise requirement shall be estimated by CONTRACTOR, as per the applicable construction documents / various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document. - Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance.
Structural steel (MS) Supply of coating material and paint as required for surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI-SPE-0003 (Technical Specification for Painting) is included in scope.
Structural steel (Hot deep galvanized GI)
MISCELLANEOUS ITEMS
CANOPIES - Supply of GI / FRP canopies for various equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. - Site visit as required to confirm the actual dimensions / arrangement of various equipment installed at site, so as to fabricate canopy exactly suitable for the equipment is considered in the scope. - Supply of all the Installation Material (including steel supporting frame as required) required as per site requirement is included in the scope.
Canopies for Motors
GI canopy complete with louvers backed up by wire mesh
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6kV) Motors
CIVIL WORK
Anchor fasteners - Supply of anchor fasteners for supporting various equipment in brick work / concrete work, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. - Supply of anchor fasteners indicated below excludes those already considered in various 'Installation Details' mentioned in 'SECTIONS - A to E' in this document.
Anchor fasteners M8 type x 60mm
Anchor fasteners M10 type x 75 mm
Anchor fasteners M12 type x 100 mm
Supply of certified soft sand of known resistivity, red coloured concrete tiles of appropriate voltage grade for cable protection, ordinary bricks, warning tapes, cable markers (including steel & RFID tag)
Certified soil (soil resistivity 150 0C/cm/W))
SAFETY ITEMS Supply of safety items as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents ALL SAFETY ITEMS SHALL BE OF REPUTED MAKE & SHALL HAVE PROVEN PAST TRACK RECORD. LOCAL MAKES ARE NOT ACCEPTABLE
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for 33 kV systems - tested as per applicable standard
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for 6.6 kV systems - tested as per applicable standard
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for upto 1.1 kV systems - tested as per applicable standard
First aid boxes along with required medicines / medical equipment
First aid information chart (for electrical hazards such as Shock treatment)
CO2 Fire extinguishers 6.8 kg capacity
DCP Fire extinguishers capacity 2 kgs
DCP Fire extinguishers.capacity 5 kgs
GI stand for installation of buckets along with 4nos. GI buckets filled with dry river sand
Enameled caution boards for 33 kV.
Enameled caution boards for 6.6 kV.
Enameled caution boards for 1.1 kV.
Enameled Danger plates to be installed in electrical rooms such as transformer bay, switchgear room etc.
Industrial electrical Rubber hand gloves, Class 1 Class 4(36kV) of reputed make
HV discharge rod for discharging / earthing of <= 33kV AC busbars
Epoxy insulating floor coating (Valency Compound Make - Valency-111 CLASS A or equivalent (up to 33 kV system)
Sheath Voltage Limiters (SVL) for 33kV system
Fire proof painting for cables for 3 m length at entry points of both ends
Star Crimping Tool
Ferrule/Label Printing machine with cartridge
Ferrule Sleeves (4.5mm )
Ferrule Sleeves (3.2mm)-
Transformer Oil Filtration Machine(6000LPH) - Reputed make with with PTR to be offered
Portable 110V DC Power Pack - Reputed make with with PTR to be offered
Earth Tester
Primary Current Injection Test Kit - Reputed make with with PTR to be offered
GENERAL ITEMS Supply of following items and all the associated accessories as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Office tables of reputed make
Office chairs of reputed make
Full size Cupboard of reputed make, sheet steel enclosure (for documentation)
Tool Cabinet, Wall Mounted
Key Cabinet, Wall Mounted
Tarpaulin (for weather protection of stored electrical equipment)
Insulated step ladder of reputed make (suitable for indoor work in switchgear rooms)
3 ply Lamicoid tag plates of appropriate size for various equipment, with White letters on Black background, as per the site requirement
Supply of motorised Rolling shutter in electrical substation.
LV Switchgear Components
6A, 9 kA, SP MCB
10A, 9 kA, SP MCB
20A, 9 kA, SP MCB
Terminal Blocks
LOTO with multiple locks (HESP) of reputed make
Locks with keys of reputed make
Electrical safety suit with goggles >33kV voltage grade with statutory marking
Description of Work / Item(s)
Amount
GENERAL NOTES (1) This document shall be read in conjunction with doc. 'ANNEXURE-I' TO SCC - 'SCOPE OF WORK - ELECTRICAL'. (2) For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. (3) CONTRACTOR shall only use 'Released for Construction (RFC)' drawings / documents for execution of work during the Construction phase. (4) Dismantling activities shall be paid at 30% of the unit rates of the respective installation work. Dismantling activities shall only be paid to CONTRACTOR if instructed by OWNER / CONSULTANT, and not for erroneous execution done by CONTRACTOR. (5) All the fixing hardwares such as nuts, bolts, U-bolts, screws, washers & clamps shall be of Stainless Steel (SS304). (6) CONTRACTOR shall ensure that the rates quoted for execution of electrical works take into account all requirements, services, activities & responsibilities defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. (7) Special attention shall be given to include the efforts necessary to implement & comply with the relevant safety practices to be followed for the electrical works at the Plant Site, as per the applicable HSE documents. (8) CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any missouts in supply scope in this regard by the CONTRACTOR shall not be entertained.
EQUIPMENT
TRANSFORMERS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of assemblies / sub-assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, filtration of oil, touch up painting, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of associated equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for various equipment / assemblies / sub-assemblies as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
Power transformers (Oil filled) - (F)
TAG : 1U64-SS15-TR-204A/B - Rating : 33.5 / 40 MVA, 33 kV / 6.9 kV, ONAN / ONAF, Dyn11 WITH OCTC, 2 winding - Approx. Dimensions (LxBxH) : 6250 x 4980 x 4650 mm - Oil capacity : 10850 ltrs. (9000kg.) - Approx. Weight : 48000 kg (including oil)
TAG : 1U64-SS15-TR-205A/B - Rating : 15 MVA, 6.6 kV, ONAF, VFD Converter Transformer - Approx. Dimensions (LxBxH) : 7000 x 5000 x 5200 mm - Oil capacity : 10365 ltrs. - Approx. Weight : 36000 kg (including oil)
Distribution transformers (Oil filled)
TAG : 1U64-SS15-TR-316A/B, 317A/B, 318A/B, 319A/B, 320A/B, 321A/B - Rating : 2500 kVA, 6.6 kV / 433 V, ONAN, Dyn11 WITH OCTC - Approx. Dimensions (LxBxH) : 3450 x 3450 x 3225 mm - Oil capacity : 1600 ltrs. - Approx. Weight : 7425 kg (including oil)
Lighting transformers (dry type)
TAG : 1U64-SS15-TR-503A/B - Rating : 350 kVA, 415 V / 433 V, 2 winding, indoor installation - Approx. Dimensions (LxBxH) : 2100 X 1850 X 1650 mm - Approx. Weight : 1880 Kg
TAG : 1U64-SS15-TR-504A/B - Rating : 75 kVA, 415 V / 433 V, 2 winding, indoor installation - Approx. Dimensions (LxBxH) : 1500 X 1500 X 1000 mm - Approx. Weight : 350 Kg
TAG : 1U64-SS15-TR-6383 (FOR PRT Package) - Rating :5 kVA, 415 V / 180/200/220 V, 2 winding, indoor installation - Approx. Dimensions (LxBxH) : 550 X 325 X 610 mm - Approx. Weight : LATER
TAG : 1U64-SS15-TR-322 (Dry type Trafo for Heater Transformer) - Rating : 1250 kVA, 6.6 kV / 433 V, 2 winding, indoor installation - Approx. Dimensions (LxBxH) : 3500 X 2500 X 2000 mm - Approx. Weight : 5000 Kg
Oil filteration and drying out of transformer (per day basis) Applicable only if additional oil to be filtered above the stated quantity.
BUSDUCTS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of shipping sections / assemblies / sub-assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, alignment for appropriate termination of busbars at both the ends, fixing of flexible joints, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Minor civil work such as chipping and modifications in the wall cutout, as required, for making busduct wall opening suitable for busduct entry etc., replastering and making area good as per the site requirement (including the supply of consumable material for the same), sealing with fire proofing compound, is included in the scope. - Fabrication and installation of steel support structure / supporting frames (inside and outside the substation building) for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS15-BD-204A - 6.6 kV, 4000 A, 40kA for 1 sec. - Construction : Sheet steel enclosure, Phase Segregated - From : 1U64-SS15-TR-204A - To : 1U64-SS15-AIS-204 - Approx. length : 11 m (Indoor) + 7 m (Outdoor) - Approx. Weight : 300 kg / m
TAG : 1U64-SS15-BD-204B - 6.6 kV, 4000 A, 40kA for 1 sec. - Construction : Sheet steel enclosure, Phase Segregated - From : 1U64-SS15-TR-204B - To : 1U64-SS15-AIS-204 - Approx. length : 15.5 m (Indoor) + 7 m (Outdoor) - Approx. Weight : 300 kg / m
TAG : 1U64-SS15-BD-316A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-316A - To : 1U64-SS15-PMCC-316 - Approx. length : 8 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-316B - 415 V, 4000 A, 65kA for 1sec. - From : 1U64-SS15-TR-316B - To : 1U64-SS15-PMCC-316 - Construction : Sandwich type - Approx. length : 9.5 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-317A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-317A - To : 1U64-SS15-PMCC-317 - Approx. length : 10.5 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-317B - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-317B - To : 1U64-SS15-PMCC-317 - Approx. length : 15 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-318A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-318A - To : 1U64-SS15-PMCC-318 - Approx. length : 18 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-318B - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-318B - To : 1U64-SS15-PMCC-318 - Approx. length : 18 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-319A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-319A - To : 1U64-SS15-PMCC-319 - Approx. length : 7 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-319B - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-319B - To : 1U64-SS15-PMCC-319 - Approx. length : 5.5 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-320A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-320A - To : 1U64-SS15-PMCC-320 - Approx. length : 23 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-320B - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-320B - To : 1U64-SS15-PMCC-320 - Approx. length : 17 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-321A - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-321A - To : 1U64-SS15-PMCC-321 - Approx. length : 20 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
TAG : 1U64-SS15-BD-321B - 415 V, 4000 A, 65kA for 1sec. - Construction : Sandwich type - From : 1U64-SS15-TR-321B - To : 1U64-SS15-PMCC-321 - Approx. length : 20 m (Indoor) + 9 m (Outdoor) - Approx. Weight :125 kg / m
NEUTRAL GROUNDING RESISTOR (NGR) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment and accessories, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS15-NGR-204A/B - Rating : 10.5 Ohms, 400 A for 30 sec - Approx. Dimensions (LxBxH) : 1250 x 1250 x 1600 mm - Approx. Weight : 600 kgs
TAG : 1P25-SS15-NGR-6383 (FOR PRT) - Rating : 10.5 Ohms, 400 A for 10 sec - Approx. Dimensions (LxBxH) : 1460 x 1425 x 1740 mm - Approx. Weight : 775 kgs
Synchronous Generator (M/s Elliott / TDPS) - Alternator handling, mounting on table top foundation, alignment with turbine shaft will be done by mechanical contractor under supervision of package vendor. - Cable termination, motor testing, precommissioning activities, commissioning assistanceas required by MANUFACTURER's supervisor is included in the scope. - Rating :12500KVA, 6.6kV, 1093A, 50Hz. Ex-ec Indoor Installation - Approx. Dimensions (LxBxH) : 5000 x 3000 x 4000mm - Approx. Weight : 31150kg
HV SWITCHBOARDS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of various shipping sections / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, interpanel wiring, stenciling with paint on equipment enclosures as required, and other associated work so as to ensure the completeness of installation work - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS15-AIS-204 (6.6kV Switchboard) - Rating : 6.6 kV, 4000 A, 40kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 79 - Approx. Dimensions (LxBxH)mm : 800 x 2300 x 2800mm (per vertical section) - Approx. Weight : 1200 kg (per vertical section) Intrapanel Busduct for 2 section of panel
TAG : 1U64-SS15-GCPP-204 (GCB Panel : PRT Package) - Rating : 6.6 kV, 1250 A, 40kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 2 - Approx. Dimensions (LxBxH)mm : 600 x 2150 x 2700mm (per vertical section) - Approx. Weight : 1300 kg
TAG : 1U64-SS15-AIS-223 (O/P BKR Panel : WGC Pacakge) - Rating : 6.6 kV, 1250 A, 40kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 3 - Approx. Dimensions (LxBxH)mm : 650 x 1545 x 2200mm (per vertical section) - Approx. Weight : 1200 kg (per vertical section)
TAG : 1U64-SS15-AIS-221 (O/P BKR Panel : HPC Package) - Rating : 6.6 kV, 1250 A, 40kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 3 - Approx. Dimensions (LxBxH)mm : 650 x 1545 x 2200mm (per vertical section) - Approx. Weight : 1200 kg (per vertical section)
TAG : 1P25-KAM-3181-SOS (Soft Starter : HPC Package) - Rating : 6.6 kV, 1250 A, 40kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 3 - Approx. Dimensions (LxBxH)mm : 2000 x 2300 x 2700mm (per vertical section) - Approx. Weight : 1500 kg (per vertical section)
TAG : 1U64-SS15-CAP-204A/B (HV Capacitor Panel) - Power factor improvement 6.6kV, 3750 kVAr (effective) Capacitor bank consists of multiple capacitors with series reactor, Isolator, RVT, APFC panel & all associated components & accessories. -Installation work includes assembling of separately supplied equipment / assemblies / sub-assemblies. Capacitor banks with APFC panel shall be located indoor inside substation equipment floor. - Rating : 6.6 kV, 3750 kVAR, 40kA for 1 sec. - No. of steps :1000kVAr x 3 Nos. + 500kVAr x 1 Nos. + 250kVAr x 1 Nos. - Construction : Floor mounting, single front - Nos. of vertical sections : 5 - Approx. Dimensions (LxBxH)mm : 2000 x 1600 x 2000mm (per shipping section) - Approx. Weight : 1500 kg (per vertical section)
LV SWITCHBOARDS (FLOOR MOUNTED) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of various shipping sections / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, interpanel wiring, stenciling with paint on equipment enclosures as required, and other associated work so as to ensure the completeness of installation work - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS15-PMCC-316 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 29 - Approx. Dimensions (LxBxH)mm : 800 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section )
TAG : 1U64-SS15-PMCC-317 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 25 - Approx. Dimensions (LxBxH)mm : 800 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-PMCC-318 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 28 - Approx. Dimensions (LxBxH)mm : 800 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-PMCC-319 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 23 - Approx. Dimensions (LxBxH)mm : 800 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-PMCC-320 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 30 - Approx. Dimensions (LxBxH)mm : 800 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-EPMCC-321 - Rating : 415 V, 4000 A, 65kA for 1 sec. - Construction : Floor mounting, single front - Nos. of vertical sections : 42 - Approx. Dimensions (LxBxH)mm : 900 x 1800 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-416 - Rating : 415 V, 800 A, 65kA for 1 sec. - Construction : Floor mounting, double front - Nos. of vertical sections : 11 - Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) - Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-417 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-418 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 13 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-419 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-420 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 14 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-421 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-422 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 13 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-423 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 13 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-424 Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-425 (By RxRG Packge : M/s GRE) Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MCC-426 (by PRT Package : M/s Elliott) Rating : 415 V, 800 A, 65kA for 1 sec. Construction : Floor mounting, double front Nos. of vertical sections : 12 Approx. Dimensions (LxBxH)mm : 900 x 1500 x 2500mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-MLDB-502 Rating : 415V, 800A, 20kA for 1 sec. Construction : Floor mounting, Single / Double front Nos. of vertical sections : 5 Approx. Dimensions (LxBxH)mm : 1500 x 1000 x 2200mm (per shipping section) Approx. maximum Weight : 300 KGS. (per shipping section)
TAG : 1U64-SS15-EMLDB-502 Rating : 415V, 150A, 10kA for 1 sec. Construction : Floor mounting, Single / Double front Nos. of vertical sections : 3 Approx. Dimensions (LxBxH)mm : 1500 x 1000 x 2200mm (per shipping section) Approx. maximum Weight : 300 KGS. (per shipping section)
TAG : 1U64-SS15-ASB-502 Rating : 415V, 800A, 65kA for 1 sec. Construction : Floor mounting, Double front Nos. of vertical sections : 14 Approx. Dimensions (LxBxH)mm : 800 x 1000 x 2100mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-TCP-001 (Electrical Heater Package : M/s Marathon) Rating : 415V, 2000A, 50kA for 1 sec. Construction : Floor mounting, Single front Nos. of vertical sections : 6 Approx. Dimensions (LxBxH)mm : 800 x 1000 x 2100mm (per shipping section) Approx. maximum Weight : 800 KGS. (per shipping section)
TAG : 1U64-SS15-CRP-223 (WGC Package : M/s BHEL/ABB) Rating : NA Control Realy Panel Construction : Floor mounting Nos. of vertical sections : 1 Approx. Dimensions (LxBxH)mm : 600 x 600 x 2200mm Approx. maximum Weight : 200 KGS.
TAG : 1U64-SS15-SYNC-204 (PRT Package : M/s GRE/Schneider) Rating : NA Generator Control Panel Construction : Floor mounting Nos. of vertical sections : 1 Approx. Dimensions (LxBxH)mm : 1000 x 800 x 2300mm Approx. maximum Weight : 600 KGS.
TAG :1U64-SS15-GEP-204 (PRT Package : M/s GRE/ABB) Rating : NA Generator AVR Panel Construction : Floor mounting Nos. of vertical sections : 1 Approx. Dimensions (LxBxH)mm : 800 x 750 x 2100mm Approx. maximum Weight : 450 KGS.
LV PANELS (WALL / CONCRETE / STEEL STRUCTURE MOUNTED) (Industrial / For Explosive Atmospheres) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation of LV panels (wall / concrete / steel structure mounted) shall be as per 'Installation Details - Power' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work is included in the scope
LDB and ELDB (6way / 9way / 12way / 15way / 18way) TAG :LDB / ELDB Construction : Non Compartmentalised single front, fixed type Installation Type: P17 Location : Outdoor
LDB and ELDB (6way / 9way / 12way / 15way / 18way) TAG :LDB / ELDB Construction : Non Compartmentalised single front, fixed type Installation Type: P10B / P17 Location : Indoor
PDB (Power Distribution Boards) (6way / 9way / 12way / 15way / 18way)TAG : PDB Construction : Non Compartmentalised single front, fixed type Installation Type: P17 Location : Outdoor
PDB (Power Distribution Boards) (6way / 9way / 12way / 15way / 18way)TAG : PDB Construction : Non Compartmentalised single front, fixed type Installation Type: P10B / P17 Location : Indoor
PDB (Power Distribution Boards) for Hydro Jet area TAG : PDB feeder pillar with 1No. 400A I/C and outgoings with 2Nos.250A and 1 no.125A and 1 no. of 63A (Installation type : P10) Construction : Non Compartmentalised single front, fixed type Approx. maximum Dimensions (LxBxH) : 900 x 900 x 250 mm (per panel) Approx. maximum Weight : 100 kgs (per panel) Installation Type: P10B / P17 Location : Outdoor
LCP (Local Control Panel) for package units TAG : XXX Construction : Non Compartmentalised single front, fixed type Approx. maximum Dimensions (LxBxH) : 1000 x 1200 x 600 mm (per panel) Approx. maximum Weight : 125 kgs (per panel) Installation Type: Wall/column/structure mounted Location : Indoor / Outdoor
BATTERY CHARGER (DC UPS) AND BATTERY - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Assembly of battery rack, placement of battery cells on the support rack, electrolyte filling and associated work as recommended by MANUFACTURER is included in the scope. - Installation of battery MCCB with enclosure at the location indicated in the applicable layouts is included in the scope. - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for various equipment / assemblies as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SS15-ECH-503 (For Switchgear Control)
Battery charger Rating : 110 VDC, 300 A, Dual Redundant Battery charger Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 4000 x 800 x 2000 mm Approx. Weight : 2000 kgs (Overall) Mounting : Floor
Battery bank : 1U64-SS15-BAT-503A/B Battery type : Ni-Cd Nos. of cells : 95 Approx. Dimensions (LxBxH) : 195 x 176 x 500 mm (per cell) Approx. Dimensions (LxBxH) : 4600 x 800 x 1250 mm (overall) Mounting : floor mounted battery rack, multi-tier
DCDB : 1U64-SS15-DCDB-503 Rating : 110 VDC, 160 A, Construction : Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 3000 x 600 x 2000 mm Approx. Weight : 850 kgs (Overall) Mounting : Floor
Battery Isolator Construction : Non Compartmentalised, Single / Double front, fixed type Approx. Dimensions (LxBxH) : XXX x XXX x XXX mm (per panel) Approx. Weight : XX kgs (per panel) Mounting : Wall
TAG : 1U64-SS15-ECH-504 (For DC cirtical lighting)
Battery charger Rating : 110 VDC, 90 A, Single Non- Redundant Battery charger and integral DCDB Construction : Compartmentalised, Single front Approx. Dimensions (LxBxH) : 2800 x 800 x 2000 mm Approx. Weight : 1500 kgs (Overall) Mounting : Floor
Battery bank : 1U64-SS15-BAT-504Battery type : Ni-Cd Nos. of cells : 95 Approx. Dimensions (LxBxH) : 105 x 139 x 375 mm (per cell) Approx. Dimensions (LxBxH) : 2600 x 800 x 1750 mm (overall) Mounting : floor mounted battery rack, multi-tier
DCDB : 1U64-SS15-DCDB-504 Rating : 110 VDC, 63 A Construction : Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 1800 x 600 x 2000 mm Approx. Weight : 850 kgs (Overall) Mounting : Floor
Battery Isolator Construction : Non Compartmentalised, Single / Double front, fixed type Approx. Dimensions (LxBxH) : XXX x XXX x XXX mm (per panel) Approx. Weight : XX kgs (per panel) Mounting : Wall
AC UPS AND BATTERY - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment / assemblies, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Assembly of battery rack, placement of battery cells on the support rack, electrolyte filling and associated work as recommended by MANUFACTURER is included in the scope. - Installation of battery MCCB with enclosure at the location indicated in the applicable layouts is included in the scope. - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for various equipment / assemblies as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1U64-SRR7-UPS-501
UPS Rating : 115V, 50 Hz, 135 kVA, Dual Redundant UPS with stabilised By pass supply & 2x100% Ni-Cd battery, with ACDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 8500 x 1000 x 2000 mm (Overall) Approx. Weight : 7000 kgs (Overall) Mounting : On False floor supported with structural steel base frame
Battery bank Battery type : Ni-Cd Nos. of cells : 300 Approx. Dimensions (LxBxH) : 195 x 176 x 500 mm (per cell) Approx. Dimensions (LxBxH) : 5000 x 1500 x 1800 mm (overall) Mounting : floor mounted battery rack, multi-tier
ACDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 6000 x 1200 x 2000 mm Approx. Weight : 2500 kgs Mounting : On False floor supported with structural steel base frame
Battery Isolator Construction : Non Compartmentalised, Single / Double front, fixed type Approx. Dimensions (LxBxH) : XXX x XXX x XXX mm (per panel) Approx. Weight : XX kgs (per panel) Mounting : Wall
TAG : 1U64-SRR7-UPS-502
UPS Rating : 115V, 50 Hz, 80 kVA, Dual Redundant UPS with stabilised By pass supply & 2x100% Ni-Cd battery, with ACDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 8500 x 1000 x 2000 mm (Overall) Approx. Weight : 7000 kgs (Overall) Mounting : On False floor supported with structural steel base frame
Battery bank Battery type : Ni-Cd Nos. of cells : 300 Approx. Dimensions (LxBxH) : 195 x 176 x 500 mm (per cell) Approx. Dimensions (LxBxH) : 5000 x 1500 x 1800 mm (overall) Mounting : floor mounted battery rack, multi-tier
ACDB Construction : Non Compartmentalised, Single / Double front Approx. Dimensions (LxBxH) : 6000 x 1200 x 2000 mm Approx. Weight : 2500 kgs Mounting : On False floor supported with structural steel base frame
Battery Isolator Construction : Non Compartmentalised, Single / Double front, fixed type Approx. Dimensions (LxBxH) : XXX x XXX x XXX mm (per panel) Approx. Weight : XX kgs (per panel) Mounting : Wall
VARIABLE FREQUENCY DRIVES (with CONDITION MONITORING) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment and accessories, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment / accessories as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope.
TAG : 1P25-EAM-0551B-VFD Rating : 1.5 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 400 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-EAM-2452B/D-VFD Rating : 5.5 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 400 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P25-EAM-3053-1/2/3/4-VFD, 1P25-EAM-5651B-VFD Rating : 11 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 500 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-FAM-6081A/B-VFD Rating : 22 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 500 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-EAM-2453B-VFD,1P25-EAM-2351B-VFD,1P25-EAM-3052-1/2/3/4-VFD,1P27-EAM-3051B-VFD Rating : 15 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 500 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P25-EAM-3051-1/2/3/4/5/6/ 7/8/9/10/11/12/13/14/15/16/17/18/19/20/21/22/23/24-VFD Rating : 18.5 kW Approx. Dimensions (LxBxH) : 1000 x 800 x 2000 mm Approx. Weight : 500 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-EAM-2651B/D-VFD, 1P27-EAM-2454B/D-VFD Rating : 30 kW Approx. Dimensions (LxBxH) : 1200 x 800 x 2000 mm Approx. Weight : 700 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-EAM-2451B/D-VFD, 1P27-FAM-6083-A/B-VFDRating : 37 kW Approx. Dimensions (LxBxH) : 1400 x 800 x 2000 mm Approx. Weight : 700 kgs (Per VFD) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P27-FAM-6082A/B-VFD Rating : 45 kW Approx. Weight : 1000 kgs (Per VFD) Approx. Dimensions (LxBxH) : 1400 x 800 x 2000 mm Mounting : On floor Construction : Non Compartmentalised, Single / Double front
TAG : 1P25-KM-3781-VFD-1/2 (Hot Standby VFD panel) Rating : 12040 kW Approx. Dimensions (LxBxH) : 10000 x 2000 x 2500 mm Approx. Weight : 8800 kgs (Overall) Mounting : On floor Construction : Non Compartmentalised, Single / Double front
Testing, precommissioning and commissioning of INDUCTION MOTORS AND CANOPIES Testing, precommissioning and commissioning activities are included in the scope.
LV (415V) Motors
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6 kV) Motors
200 kW to 315 kW
391 kW to 850 kW
12040kW (Wet Gas Compressor motor)
Canopies - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of canopy for the motor - as per applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work, minor modifications (cutting, drilling etc.) in the canopy fitting arrangemet if required - Supply of all fixing hardware as per the site requirement is included in the scope
LV (415V) Motors
Upto 3.0 kW
3.7 kW to 15 kW
18.5 kW to 37.0 kW
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6 kV) Motors
185kW to 315 kW
391 kW to 850 kW
LOCAL CONTROL STATIONS (LCS) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation of Industrial/ Explosive Atmospheres type LCS (wall / concrete / steel structure mounted) shall be as per 'Installation Details - Power' and applicable construction documents.
Installation Type: P07A
Installation Type: P07B
Installation Type: P07C
Installation Type: P08A
Installation Type: P08B
Installation Type: P09B
Installation Type: P11A
Installation Type: P12A
Installation Type: P13A
AUXILLIARY BOARDS (Floor mounted) excluding panels listed under Sr. No. 4 to 12 - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Minor civil work such as chipping, grouting for fixing of equipment / assemblies and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Fabrication and installation of steel support structure / supporting frames for various equipment/assmblies as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation of boards shall be as per applicable construction documents.
Shipping section / Unit weight upto 100 kgs
Shipping section / Unit weight from 101 kgs to 500kgs
Shipping section / Unit weight from 501 kgs to 1000kgs
Shipping section / Unit weight from 1001 kgs to 1500kgs
Shipping section / Unit weight from 1501 kgs to 3000kgs
CABLE / WIRE LAYING, TERMINATION AND CABLE ROUTING SYSTEMS
CABLE LAYING - Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of cables / wires in cable trays (either located above ground or inside RCC cable trenches) / directly buried underground / in sand filled cable trenches (trench constructed by others) / through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits (excluding lighting circuit cables, from SLDB / ESLDB onwards upto the lighting fixtures) - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Supply and installation of certified trefoil clamps of non-magnetic material, spacer bars and saddles, dressing of cables using Stainless Steel cable ties, cable tags(RFID tags) and ferrules (including all fixing hardware) as per the site requirement are included in the scope. - Supply of water / fireproof compound (of reputed make) and sealing of openings for cable entries by applying the same (whether spare openings or openings with cables passing through) is included in the scope. - Refer 'Annex-EW4-6' - 'Details of openings to be sealed', for quantity estimation of sealant to be applied at various locations. - Minor civil work such as chipping / drilling of through-holes / cutouts in floor / walls, replastering and making area good after work done, providing sleeves during the cable laying as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. - Installation of cable route markers (as applicable including RFID tags) shall be as per 'Installation Details - Power' and applicable construction documents.
HV CABLES All cables indicated below are laid in air (above ground / in cable trays installed in RCC cable trenches), unless otherwise indicated.
6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
33 / 33 kV (UE) grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE)
LV CABLES All cables indicated below are laid in air (above ground / in cable trays installed in RCC cable trenches), unless otherwise indicated.
600 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, armoured power / control / lighting / signal cables
4 x Pair x 2.5
8 x Tried x 1.5
3 x Tried x 2.5
2C x 2.5 Sq. mm (2XWY)
2C x 4 Sq. mm (2XWY)
2C x 6 Sq. mm (2XWY)
2C x 10 Sq. mm (2XWY)
2C x 16 Sq. mm (2XWY/2XFY)
2C x 240 Sq. mm (2XFY)
3C x 2.5 Sq. mm (2XWY)
3C x 2.5 Sq. mm (2XWY) Directly Buried Cable
3C x 4 Sq. mm (2XWY)
3C x 6 Sq. mm (2XWY)
3C x 10 Sq. mm (2XWY)
3C x 16 Sq. mm (2XWY) / (2XFY)
4C x 2.5 Sq. mm (2XWY)
4C x 4 Sq. mm (2XWY)
4C x 6 Sq. mm (2XWY)
4C x 10 Sq. mm (2XWY)
4C x 16 Sq. mm (2XWY/2XFY)
5C x 2.5 Sq. mm (2XWY)
6C x 2.5 Sq. mm (2XWY)
7C x 2.5 Sq. mm (2XWY)
8C x 2.5 Sq. mm (2XWY)
10C x 2.5 Sq. mm (2XFY)
12C x 2.5 Sq. mm (2XFY)
16C x 2.5 Sq. mm (2XFY)
24C x 2.5 Sq. mm (2XFY)
2C x 25 Sq. mm (A2XFY)
2C x 35 Sq. mm (A2XFY)
2C x 50 Sq. mm (A2XFY)
2C x 70 Sq. mm (A2XFY)
2C x 95 Sq. mm (A2XFY)
2C x 120 Sq. mm (A2XFY)
2C x 150 Sq. mm (A2XFY)
2C x 185 Sq. mm (A2XFY)
2C x 240 Sq. mm (A2XFY)
3C x 25 Sq. mm (A2XFY)
3C x 35 Sq. mm (A2XFY)
3C x 50 Sq. mm (A2XFY)
3C x 70 Sq. mm (A2XFY)
3C x 95 Sq. mm (A2XFY)
3C x 120 Sq. mm (A2XFY)
3C x 150 Sq. mm (A2XFY)
3C x 185 Sq. mm (A2XFY)
3C x 240 Sq. mm (A2XFY)
3C x 300 Sq. mm (A2XFY)
4C x 25 Sq. mm (A2XFY)
4C x 35 Sq. mm (A2XFY)
4C x 50 Sq. mm (A2XFY)
4C x 70 Sq. mm (A2XFY)
4C x 95 Sq. mm (A2XFY)
4C x 120 Sq. mm (A2XFY)
4C x 150 Sq. mm (A2XFY)
4C x 185 Sq. mm (A2XFY)
4C x 240 Sq. mm (A2XFY)
4C x 300 Sq. mm (A2XFY)
1C x 400 Sq. mm (A2XFY/A2XWY)
1C x 500 Sq. mm (A2XFY/A2XWY)
1C x 630 Sq. mm (A2XWaY) / A2XFY
3.5C x 150 Sq. mm (A2XFY)
3.5C x 300 Sq. mm (A2XFY)
1100V grade, Al / Cu conductor (stranded / solid), XLPE insulated, unarmoured power cables (for battery banks)
1 C x 68.3 sq.mm (Uninyvin Cable)- U0
1 C x 84.2 sq.mm (Uninyvin Cable)- U00
EARTHING CABLES (laid above ground) Earthing cables laid underground are to be considered separately in SECTION - E.
1100V Al / Cu conductor, PVC insulated, unarmoured earthing cables
1 C x 6 sq.mm
1 C x 16 sq.mm
1 C x 25 sq.mm
1 C x 70 sq.mm
1 C x 95 sq.mm
1 C x 120 sq.mm
1 C x 185 sq.mm
GI Wire ropes
8 SWG Solid G.I. Wire
10mm (3/8") Dia G.I. Wire Rope
16mm (5/8") Dia G.I. Wire Rope
FIRE ALARM AND COMMUNICATION SYSTEM CABLES 650 V voltage grade, Cu conductor (stranded / solid), XLPE insulated, screened, armoured communication cables
1P x 0.5 sq.mm (Jelly Filled)
2P x 0.5 sq.mm
5P x 0.5 sq.mm (Jelly Filled)
10P x 0.5 sq.mm (Jelly Filled)
24P x 0.5 sq.mm
1P x 1.5 sq.mm
2P x 1.5 sq.mm
12P x 1.5 sq. mm
20P x 1.5 sq.mm
50P x 1.5 sq.mm
100P x 1.5 sq.mm
1P x 2.5 sq.mm
2P x 2.5 sq.mm
4P x 2.5 sq.mm
12P x 2.5 sq. mm
20P x 2.5 sq.mm
3C x 2.5 Sq. mm (2XWY)
FIBRE OPTIC CABLES
Fibre Optic Cable - 6 / 8 Fibre
Fibre Optic Cable - 12 Fibre
Fibre Optic Cable - 24 Fibre
FLEXIBLE CONDUCTOR CABLES
650V / 1100V (Uo / U) voltage grade, Multistranded Cu conductor, PVC insulated, flexible cable
3C x 2.5 Sq.mm
4C x 2.5 Sq.mm
Special cables
CAT 6A Cable
4-pair (23 AWG) shielded twisted pair (STP) LAN
CABLE GLANDING AND TERMINATION (HV) (Industrial / For Explosive Atmospheres) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of HV cable termination kit and cable glands with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of tinned copper lug, drilling and treading of gland plate, termination of cable at designated location and other associated work so as to ensure the completeness of installation work. - Cable termination shall be carried out by experienced, competent & certified personnel from the termination kit MANUFACTURER / installation CONTRACTOR. - Raychem Make termination kits shall be used.
Glanding and Termination of 6.6 / 6.6 kV (UE) voltage grade, Al / Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
Glanding and Termination of 33 / 33 kV (Uo / U)grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE)
CABLE GLANDING AND TERMINATION (LV) (Industrial / For Explosive Atmospheres) - Handling, shifting from site-store / yard to the installation location, unpacking,erection, alignment, assembly and installation of cable glands (industrial / For Explosive Atmospheres type) with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of lug, drilling and treading of gland plate, termination of cable (excluding lighting circuit cables, from SLDB / ESLDB onwards upto the lighting fixtures) at designated location and other associated work so as to ensure the completeness of installation work. - Tinned Copper Lugs shall be used for Stranded Copper (Cu) conductor cables and Aluminium Lugs for Aluminium conductor cables (Al).
LV CABLES
Glanding and Termination of 650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
4 x Pair x 2.5
8 x Tried x 1.5
2C x 2.5 Sq. mm (2XWY)
2C x 4 Sq. mm (2XWY)
2C x 6 Sq. mm (2XWY)
2C x 10 Sq. mm (2XWY)
2C x 16 Sq. mm (2XWY/2XFY)
3C x 2.5 Sq. mm (2XWY)
3C x 4 Sq. mm (2XWY)
3C x 6 Sq. mm (2XWY)
3C x 10 Sq. mm (2XWY)
3C x 16 Sq. mm (2XWY/2XFY)
4C x 2.5 Sq. mm (2XWY)
4C x 4 Sq. mm (2XWY)
4C x 6 Sq. mm (2XWY)
4C x 10 Sq. mm (2XWY/2XFY)
4C x 16 Sq. mm (2XWY/2XFY)
5C x 2.5 Sq. mm (2XWY)
6C x 2.5 Sq. mm (2XWY)
7C x 2.5 Sq. mm (2XWY)
8C x 2.5 Sq. mm (2XWY)
10C x 2.5 Sq. mm (2XFY)
12C x 2.5 Sq. mm (2XFY)
16C x 2.5 Sq. mm (2XFY)
24C x 2.5 Sq. mm (2XFY)
2C x 25 Sq. mm (A2XFY)
2C x 35 Sq. mm (A2XFY)
2C x 50 Sq. mm (A2XFY)
2C x 70 Sq. mm (A2XFY)
2C x 95 Sq. mm (A2XFY)
2C x 120 Sq. mm (A2XFY)
2C x 150 Sq. mm (A2XFY)
2C x 185 Sq. mm (A2XFY)
2C x 240 Sq. mm (A2XFY)
3C x 25 Sq. mm (A2XFY)
3C x 35 Sq. mm (A2XFY)
3C x 50 Sq. mm (A2XFY)
3C x 70 Sq. mm (A2XFY)
3C x 95 Sq. mm (A2XFY)
3C x 120 Sq. mm (A2XFY)
3C x 150 Sq. mm (A2XFY)
3C x 185 Sq. mm (A2XFY)
3C x 240 Sq. mm (A2XFY)
3C x 300 Sq. mm (A2XFY)
4C x 25 Sq. mm (A2XFY)
4C x 35 Sq. mm (A2XFY)
4C x 50 Sq. mm (A2XFY)
4C x 70 Sq. mm (A2XFY)
4C x 95 Sq. mm (A2XFY)
4C x 120 Sq. mm (A2XFY)
4C x 150 Sq. mm (A2XFY)
4C x 185 Sq. mm (A2XFY)
4C x 240 Sq. mm (A2XFY)
4C x 300 Sq. mm (A2XFY)
1C x 400 Sq. mm (A2XFY/A2XWY)
1C x 500 Sq. mm (A2XFY/A2XWY)
1C x 630 Sq. mm (A2XWaY)
3.5C x 150Sq. mm (A2XFY)
3.5C x 300Sq. mm (A2XFY)
Glanding and Termination of 650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, unarmoured power cables (for battery banks)
1 C x 68.3 sq.mm (Uninyvin Cable)
1 C x 84.2 sq.mm (Uninyvin Cable)
Termination of 1100V Al / Cu conductor, PVC insulated, unarmoured EARTHING CABLES
1 C x 6 sq.mm
1 C x 10 sq.mm
1 C x 35 sq.mm
1 C x 95 sq.mm
1 C x 120 sq.mm
1 C x 185 sq.mm
GI Wire ropes
8 SWG Solid G.I. Wire
10mm (3/8") Dia G.I. Wire Rope
16mm (5/8") Dia G.I. Wire Rope
Glanding and Termination of FIRE ALARM AND COMMUNICATION SYSTEM CABLES 650 V voltage grade, Cu conductor (stranded / solid), XLPE insulated, screened, armoured communication cables
1P x 0.5 sq.mm (OD : 13.2 mm)
2P x 0.5 sq.mm (OD : 16.4 mm)
5P x 0.5 sq.mm (OD : 18 mm)
10P x 0.5 sq.mm (OD : 21.0 mm)
24P x 0.5 sq.mm (OD : 29.5 mm)
1P x 1.5 sq.mm (OD : 14 mm)
2P x 1.5 sq.mm (OD : 21.4 mm)
12P x 1.5 sq. mm (OD : 32 mm)
20P x 1.5 sq.mm
50P x 1.5 sq.mm
100P x 1.5 sq.mm
1P x 2.5 sq.mm (OD : 23.3 mm)
2P x 2.5 sq.mm (OD : 23.3 mm)
4P x 2.5 sq.mm (OD : 26.6 mm)
12P x 2.5 sq. mm (OD : 38.6 mm)
20P x 2.5 sq.mm
Glanding and Termination of FIBRE OPTIC CABLES Scope includes preparation of all fibres and splicing / patching Supply of adequate consumables for the execution of the work (such as fibre optic connectors suitable for the application) is included in scope.
Fibre Optic Cable - 6 / 8 Fibre
Fibre Optic Cable - 12 Fibre
Fibre Optic Cable - 24 Fibre
Glanding & Termination of Special cables
CAT 6A Cable
4-pair (23 AWG) shielded twisted pair (STP) LAN
CABLE JOINTING - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of straight through joint kits, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, and other associated work so as to ensure the completeness of installation work. - Civil work such as construction of concrete chamber with cover (for cables directly buried underground) as per the site requirement (including the supply of consumable material for the same) is included in the scope.
HV CABLES
Straight through joint for 6.6 / 6.6 kV (UE) voltage grade, Al / Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
Straight through joint for 33 / 33 kV (Uo / U)grade, Al conductor, XLPE insulated, screened, armoured power cable
1C x 630 sq.mm A2XCEWaY (UE)
LV CABLES
650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control cables
All sizes from 2.5 sq.mm to 10 sq.mm (1C)
All sizes from 2.5 sq.mm to 10 sq.mm (3C / 4C)
All sizes from 16 sq.mm to 25 sq.mm (1C)
All sizes from 16 sq.mm to 25 sq.mm (3C / 4C)
All sizes from 35 sq.mm to 50 sq.mm (1C)
All sizes from 35 sq.mm to 50 sq.mm (3C / 4C)
All sizes from 70 sq.mm to 95 sq.mm (3C / 4C)
All sizes from 120 sq.mm to 185 sq.mm (3C / 4C)
All sizes from 240 sq.mm to 300 sq.mm (3C / 4C)
PREFABRICATED CABLE TRAYS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of prefabricated galvanized steel ladder type / perforated cable trays / FRP cable trays (above ground or inside concrete trenches) with all associated accessories such as bends, reducers, T-joints, fixing clamps, earthing continuity conductors etc. - as recommended by MANUFACTURER / applicable construction documents, fixing of cable trays / associated accessories to steel supports, stenciling with paint as required and other associated work so as to ensure the completeness of installation work. - Site fabrication of cable tray accessories such as bends, reducers, T-joints etc. from cable tray straight runs as per the site requirement is included in the scope. - Fabrication and installation of steel support / bracket for cable trays / accessories as per the site requirement, is considered separately in this BOQ. - Supply of all fixing hardware as per the site requirement is included in the scope.
Cable Trays Perforated (GI) and Accessories Installation of cable tray accessories such as bends, reducers, T-joints etc. is considered in cable tray running length.
50 mm wide
100 mm wide
150 mm wide
Cable Ladders (GI) and Accessories Installation of cable tray accessories such as bends, reducers, T-joints etc. is considered in cable tray running length.
150 mm wide
300 mm wide
450 mm wide
600 mm wide
Cable Tray Covers (GI) and Accessories
150 mm wide
300 mm wide
450 mm wide
600 mm wide
Separators for Cable Ladders (GI)
300 mm / 600 mm wide
CONDUITS FOR CABLE LAYING / PROTECTION - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of heavy duty rigid GI / PVC conduits on wall / concrete / steel structure (with edge protection grommet at either ends for GI conduits), cutting, bending of conduits and other associated work so as to ensure the completeness of installation work. Installation of GI clamps, reducers / adaptors for the conduits, tees, pull boxes as per the site requirement and the associated work is included in the scope. - Supply of waterproof compound (of reputed make) and sealing of conduit openings after laying of cable by applying the same is included in the scope. Civil work such as chipping / drilling of through-holes / cutouts in floor / walls (as per the site requirement) and replastering and making area good after installation of conduits as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation of conduits and associated accessories for 'Point Wiring for Office buildings / Control rooms / Other rooms with false ceiling' is considered separately in SECTION - C.
Rigid GI conduits
25 mm nominal dia
50 mm nominal dia
150 mm nominal dia
Rigid GI conduits RED coloured (For Fire Alarm System cables)
25 mm nominal dia
50 mm nominal dia
Heavy duty PVC conduits
25 mm nominal dia
50 mm nominal dia
150 mm nominal dia
Flexible PVC conduits
20 mm nominal dia
25 mm nominal dia
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of lighting fixtures, assembling and installation of components / accessories such as lamps, chokes, condensers, reflectors, control gear box for non-integral ffixtures etc. supplied separately - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Installation of lighting fixtures shall be as per 'Installation Details - Lighting' and applicable construction documents. - Control gear boxes for non-integral type lighting fixtures are a separate item, and installation type designation for the same is indicated as separate line item below. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F.
Fluorescent lighting fixtures
Installation Type : L09A
Installation Type : L09B
Installation Type : L09C
Installation Type : L10
Well glass lighting fixtures
Installation Type : L07B
Installation Type : L07C
Installation Type : L07D
Installation Type : L07E
Installation Type : L07F
Installation Type : L04
Installation Type : L05
Medium bay / high bay lighting fixtures
Installation Type : L13A
Installation Type : L13B
Installation Type : L13C
Flood lighting fixtures
Installation Type : L12A
Installation Type : L12B
Installation Type : L12C
Installation Type : L02
Installation Type : L11
Emergency lighting fixture with built-in battery (Installation types same as listed under Section C1.1.1 to C1.1.5)
Insatallation Type : L09B
Emergency EXIT sign with built-in battery
Installation Type : L16
Installation Type : L17
Installation Type : L18
Installation Type : L19
Installation Type : L20
Installation Type : L21
Aviation light (flashing / steady burning) with controller
Installation Type : L14A
Point Wiring for Office buildings / Control rooms / Other rooms with false ceiling - Installation of surface wiring / concealed wiring (in brick wall / decorative type aluminium partition in office rooms) using 2.5sq. mm flexible copper PVC wires, GI / PVC conduits, assembly and installation / embedding of heavy duty rigid GI / PVC conduits on / in wall / concrete structure (with edge protection grommet at either ends for GI conduits), cutting, bending of conduits - as per the applicable construction documents and other associated work so as to ensure the completeness of installation work - Installation of GI clamps, reducers / adaptors for the conduits, tees, pull boxes as per the site requirement and the associated work is included in the scope. - Civil work such as chipping / drilling of through-holes / cutouts in walls (as per the site requirement) and replastering and making area good after embedding of conduits as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Testing, precommissioning and commissioning activities are included in the scope. - Supply 2.5 sq.mm flexible copper PVC wires as requried, supply GI / PVC conduits and associated accessoreis such as GI clamps, reducers / adaptors for the conduits, tees, pull boxes, along with all fixing hardware as per the site requirement is included in the scope. - For installation of wires above false ceiling / below false floor, conduits can be installed on surface of wall / concrete structure, after consultation with OWNER / CONSULTANT. Elsewhere, installation of wires shall be in concealed conduits.
Primary Circuit (From SLDB / ESLDB / Lighting Junction Box upto Switch Box for local control)
1 point (wire length approx. 20m)
1 point (wire length approx. 30m)
1 point (wire length approx. 40m)
Secondary Circuit (From Switch Box for local control upto the lighting fixture / 5A/15A switch socket outlet / fan etc.)
1 point (total wire length approx. 7m)
2 point (total wire length approx. 15m)
3 point (total wire length approx. 22m)
4 point (total wire length approx. 30m)
5 point (total wire length approx. 40m)
6 point (total wire length approx. 50m)
Laying, Glanding and Termination for lighting circuit cables (650 / 1100V (Uo / U) voltage grade, Cu conductor (stranded / solid), XLPE insulated, armoured) from SLDB / ESLDB onwards upto the lighting fixtures / associated control gear boxes / junction boxes (applicable for all Lighting Fixtures, excluding Street Lighting Fixtures and Lighting Fixtures for Office buildings / Control rooms / Other rooms with false ceiling) - Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of lighting circuit cables / wires in cable trays / through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits / by cleating of cables to concrete / wall / steel structrues by saddles - as per applicable construction documents and other associated work so as to ensure the completeness of installation work.Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of cable glands (industrial / For Explosive Atmospheres type) with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of lug, termination of cable at designated location and other associated work so as to ensure the completeness of installation work Supply of all fixing hardware such as spacer bar, saddles, UV resistant PVC cable ties, Al cable tags, PVC hoods, etc. as as per the site requirement is included in the scope.Quantity of Lighting Fixtures, associated control gear boxes / junction boxes is defined in this document under the respective headings. The quantity of total looping cable length required for the work is mentioned below.
3 C X 2.5 sq.mm
EXHAUST FANS AND CEILING FANS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of exhaust / ceiling fans and associated accessories - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Minor civil work such as chipping, modifications in the wall cutout as required, grouting of frame, replastering and making area good etc.as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
Industrial type Exhaust fans
300mm dia.
450mm dia.
600mm dia.
Exhaust fans For Explosive Atmospheres
300mm dia.
450mm dia.
600mm dia.
Ceiling fans
Ceiling Fan 1200 mm sweep with electronic speed regulator
SMALL POWER - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of small power equipment and associated accessories such as control switches, socket outlets, modular box, face plate etc. - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Minor civil work such as chipping, grouting for fixing of various equipment, replastering and making area good etc.as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
SWITCH SOCKET OUTLETS Civil work such as chipping of walls (as per the site requirement) and replastering and making area good after embedding of modular boxes for switch boxes, as per the site requirement (including the supply of consumable material for the same) is included in the scope.
Decorative type switch socket outlets
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 1 no. piano type switch
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 2 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 3 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 4 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit and 5 nos. piano type switches
Decorative type switch socket box with 1 no. 5/15A switch socket unit
Decorative type switch in single module with 1 no. 5A piano type switches
Decorative type switch in double module with 2 no. 5A piano type switches
Decorative type switch in tripple module with 3 no. 5A piano type switches
Decorative type switch in quad module with 4 no. 5A piano type switches
Decorative type switch socket switchboard with 5/15A, 5 pin, socket outlet with 15A switch and 'ON' LED indication & fuse
Industrial type switch socket outlets (for Indoor Installation)
10A, single phase socket outlet with 1no. 3 pin socket, in sheet steel enclosure
10A, single phase outlet with 1 No. 10 A, 10 kA, SPMCB, in sheet steel enclosure
10A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 10 A, 10 kA, SPMCB, in sheet steel enclosure
20A, single phase socket outlet with 1no. 3 pin socket, in sheet steel enclosure
20A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
20A, single phase switch socket outlet with 1no. 3 pin socket and 1 No. 20 A, 10 kA, SPMCB, in sheet steel enclosure
CONVENIENCE SWITCH SOCKET OUTLETS Installation of Industrial / Explosive Atmospheres type Switch Socket Outlets shall be as per 'Installation Details - Lighting Power' and applicable construction documents.
16 Amp , 230V , 1Phase, Industrial Socket Outlet
16 Amp , 230V , 1Phase, Flameproof Socket Outlet
24V, 5A switch socket unit for Explosive Atmospheres, with built-in 100VA, 220V / 24V transformer
JUNCTION BOXES (JB) AND POWER JUNCTION BOXES (PJB) FOR MOTORS / OTHER EQUIPMENT - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of junction boxes / power junction boxes and associated accessories on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F. Installation of Junction Boxes shall be as per 'Installation Details - Power' and applicable construction documents. - Refer 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL' for the 'Type designations' mentioned below.
Industrial Junction Boxes
TYPE-L08B (4 way JB for lighting indoor) Approx. Dimensions (LxBxH) : 100 x 100 x 50 mm Mounting : wall / concrete / steel structure
TYPE-L08B/L08C (4 way JB for lighting outdoor) Approx. Dimensions (LxBxH) : 100 x 100 x 50 mm Mounting : wall / concrete / steel structure
TYPE-L08B (JB for Single Phase Loads) Approx. Dimensions (LxBxH) : 200 x 100 x 100 mm Mounting : wall / concrete / steel structure
TYPE-P10A/B (JB for Welding sockets) Approx. Dimensions (LxBxH) : 400 x 150 x 100 mm Mounting : wall / concrete / steel structure
Junction Boxes for Explosive Atmospheres
TYPE-L08A/B/C (4 way JB for lighting outdoor) Approx. Dimensions (LxBxH) : 150 x 100 x 100 mm Mounting : wall / concrete / steel structure
TYPE-L08A/B/C (JB for Single Phase Loads) Approx. Dimensions (LxBxH) : 250 x 100 x 100 mm Mounting : wall / concrete / steel structure
TYPE-L08A (JB for street lighting) Approx. Dimensions (LxBxH) : 250 x 150 x 100 mm Mounting : on Street Lighting Pole
TYPE-P10A/B (JB for Welding sockets) Approx. Dimensions (LxBxH) : 400 x 150 x 100 mm Mounting : wall / concrete / steel structure
Power Junction boxes for motors / other equipment for Explosive Atmospheres
TYPE- P10A/B (TAG : Motor JB) Installation Type : P10A/B, P11A/B, P12A/B, P17 Approx. Dimensions (LxBxH) : 400 x 300 x 400 mm Approx. Weight : 30 kgs Mounting : concrete / steel structure / Self Satnding Pedestal
Isolator for Lift - TYPE-P10A/B
TAG :1U64-SS15-ELV-01-ISO Approx. Dimensions (LxBxH) : XX x XX x XX mm Mounting : wall / concrete / steel structure
Isolator for EOT - TYPE-P10A/B
TAG : As per Vendor dwg Approx. Dimensions (LxBxH) : 500 x 300 x 900 mm, Weight - 35kg (approx.) Mounting : wall / concrete / steel structure
POWER SOCKET OUTLETS - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of switch socket outlets and associated accessories such as control switches, socket outlets, junction box, front plate etc. on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F. - Installation of Industrial / Explosive Atmospheres type Power socket outlets shall be as per 'Installation Details - Power' and applicable construction documents.
Industrial / Explosive Power Socket Outlets
Installation Type : P10A/B (63A)
Installation Type : P17 (63A)
Installation Type : P10A/B (100A)
FIRE ALARM AND COMMUNICATION SYSTEMS
FIRE ALARM (FA) SYSTEM - Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in FA system and associated accessories such as manual call points, plug-in devices, bases for devices etc. on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required andand other associated work so as to ensure the completeness of installation work. - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation shall be as per 'Installation Details - Fire Alarm System' and applicable construction documents. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Central FA panel TAG : XXX Approx. Dimensions (LxBxH) : 600 x 600 x 2000 mm Approx. Weight : 200 kgs Mounting : On False floor supported with structural steel base frame Location : SRR (Indoor)
Repeater Panel Mounting : Wall
FA system accessories Industrial type / Explosive Atmospheres
Installation Type: FAHC1
Installation Type: FAHS1
Installation Type: FAHZ1
Installation Type: FASC1
Installation Type: FASC2
Installation Type: FASS1
Installation Type: FCPC1
Installation Type: FCPC2
Installation Type: FCPP1
Installation Type: FCPP2
Installation Type: FCPR1
Installation Type: FCPS1
Installation Type: FMDC1
Installation Type: FMDF1
Installation Type: FMDF2
Installation Type: FMDF3
Installation Type: FMDS1
Installation Type: FRIC1
Installation Type: FRIF1
Installation Type: FCPS2
Installation Type: CFBC1
Installation Type: CFBS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08D
Installation Type: L08E
PUBLIC ADDRESS (PA) SYSTEM - Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in PA system and associated accessories such as field call stations, acoustic hoods etc. on desk / wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Central PA panel Approx. Dimensions (LxBxH) : 600 x 600 x 2000 mm Approx. Weight : 250 kgs Mounting : On False floor supported with structural steel base frame Location : SRR (Indoor)
Master Control Station Installation of Master Control Station (MCS) consisting of control key board, Loud speaker, goose-neck microphone, console mounted handset, headset and other accesories (Installation Type: CMCS1) Mounting : Desk stop Location : SRR (Indoor)
PA system accessories Industrial type / Explosive Atmospheres
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFR2
Installation Type: CTFS2
Installation Type: CTFS3
Installation Type: CFBC1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKC2
Installation Type: CSPKC3
Installation Type: CSPKF1
Installation Type: CSPKS1
Junction boxes
Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08C
Installation Type: L08D
Installation Type: L08E
TELEPHONE SYSTEM
Installation of network cabinets, EPABX servers, workstations, interconnecting cables etc. Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents.
Telephone ( Industrial type / Explosive Atmospheres)
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFR2
Installation Type: CTFS2
Installation Type: CTFS3
Installation Type: CTFZ1
Installation Type: CFBC1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08C
Installation Type: L08D
Installation Type: L08E
Installation Type: L08F
Installation RJ45 Telephone Socket
Installation RJ45 LAN Socket
CCTV SYSTEM
Installation of network cabinets, servers, workstations, monitoring equipment, power supplies, interconnecting cables etc. Installation shall be as per 'Installation Details - Communication & PA System' and applicable construction documents.
Cameras Installation of wiper & washer system as applicable are included in scope
Installation Type: CTVC1
Installation Type: CTVC2
Installation Type: CTVR1
Installation Type: CTVS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08D
Installation Type: L08E
Installation Type: L08F
Installation Type: L08G
EARTHING AND LIGHTNING PROTECTION - Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of earthing and lightning protection systems and accessories underground / wall / concrete / steel structure / cable trays - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope.
EARTHING Installation shall be as per 'Installation Details - Earthing' and applicable construction documents.
Installation of earth conductor laid underground - Excavation of soil up to the required depth, installation of earth conductor (GI strip / bare copper conductor / insulated copper cable), back filling and compacting of soil and disposing the excess soil, termination as required - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope.
25x 6 mm GI strip
50 x 6 mm HDGI strip
75 x 10 mm HDGI strip
1C x 95 Sq,mm Cu Cable
1C x 35 Sq,mm Cu Cable
1C x 70 Sq,mm Cu Cable
Installation of earth conductor laid on wall / concrete / steel structure / cable trays - Installation of earth conductor (GI strip) on wall / concrete / steel structure / cable trays by cleating at every 500mm, termination as requied - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
50 x 6 mm HDGI strip
75 x 10 mm GI strip
8 SWG SOLID G.I. WIRE
10 MM (3/8") DIA G.I WIRE ROPE
16 MM (5/8") DIA G.I WIRE ROPE
1C x 95 Sq.mm Cu Cable
1C x 10 Sq.mm Cu Cable
Installation of earth conductor to be embedded in finished concrete floors - Installation of earth conductor (GI strip / bare copper) on concrete floors -For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. - Civil work such as chipping / drilling of through-holes / cutouts in floor and replastering and making area good after installation of conductor as per the site requirement (including the supply of consumable material for the same) is included in the scope.
50 x 6 mm GI strip
75 x 10 mm GI strip
Installation of earthing / lightning protection electrodes - Excavation of soil upto the required depth, installation and testing of earth electrode, filling of the pit with the appropriate material as required, earthing connection of earth electrode with main earth grid, back filling, compacting of soil, disposing the excess soil. - Civil work including construction of concrete chamber with cover for the earth pit as per the site requirement is included in the scope.
Installation Type : E01A
Installation Type : E01B
Installation of earth buses - Installation and testing of earth buses on wall / concrete / steel structure / cable trays. - Supply of all fixing hardware as per the site requirement is included in the scope. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Installation Type : E02A
Installation Type : E02B
Installation Type : E20
Installation Type : E22
LIGHTNING PROTECTION - Installation shall be as per 'Installation Details - Lightning Protection' and applicable construction documents.
Installation of lightning protection conductor laid on wall / concrete / steel structure / roof - Installation of lightning protection conductor (GI strip) on wall / concrete / steel structure including the installation of test links and accessories, insulator supports, termination as required. - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
25 x 6 mm HDGI strip : E16
Installation of lightning protection rods / finials - Installation of of lightning arrestors, including the required supporting arrangement. - Supply of all fixing hardware as per the site requirement is included in the scope.
Installation Type : E24
Installation Type : E25
Installation Type : E26
STRUCTURAL STEEL - Fabrication, erection (by welding / fixing by anchor fastners), surface preparation and painting of structural steel as per the applicable construction documents so as to ensure the completeness of installation work for all the electrical equipment / items mentioned in Section A to E above, and chequered plates as per the applicable construction documents. - Supply of all consumables such as welding electrodes (Advani Oerlikon or equivalent), gas for cutting etc. are included in the scope. - Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance. - Surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI-SPE-0003. (Technical Specification for Painting)
Structural steel (MS)
Galvanised Iron (GI)
MISCELLANEOUS ITEMS
CIVIL WORK
Excavation - Excavation in soil for the purpose of cable laying activity up to a depth of 2m (maximum) and width of trench 4m (maximum) considering all the relevant safety standards, backfilling the excavated area after cable laying activity, consolidation after backfilling and disposing the surplus earth at required location - Installation of soft sand of known resistivity, red coloured concrete tiles of appropriate voltage grade for cable protection, warning tapes, cable markers(including RFID tags) etc. (after cable laying activity is completed) is included in the scope.
Soft / medium soil (Excavation & Back-filling)
Miscellaneous civil work - Activities indicated below are already included in 'SECTIONS - A to E' of this document. Unit rates are requested in the event that additional work is required over and above that already identified in 'SECTIONS - A to E'. - The below mentioned rates shall be applicable only if specifically agreed & approved by OWNER / CONSULTANT.
Chipping / drilling of through-holes / cutouts in concrete floor / beam, replastering and finishing the same
Chipping / drilling of through-holes / cutouts in brick walls and replastering the same.
Manual excavation of all types of soil and backfilling the excavated area, consolidation after backfilling and disposing the surplus earth at a point outside the site
Laying of RCC hume pipes of dia 150mm for road crossing including excavation of road upto a depth of 1500 mm back filling and consolidating the surface. - Supply of RCC hume pipes of reputed make as required, and civil work such as excavation, installation of hume pipes (including the supply of consumable material for the same), backfilling is included in the scope.
Installation of certified soft sand of known resistivity in the concrete trenches build by others after laying of cables, compacting the same
Anchor fasteners - Installation of heavy duty SS anchor fasteners for supporting various equipment, in brick work / concrete work - Installation of anchor fasteners indicated below excludes those already considered in various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document.
Anchor fasteners M8 type x 60mm
Anchor fasteners M10 type x 75 mm
Anchor fasteners M12 type x 100 mm
SAFETY ITEMS - Installation of safety items mentioned below, in all the electrical rooms / buildings / transformer yards, etc. as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents. - Installation of below listed items referrs to the quantity of items as mentioned in doc. 'BILL OF QUANTITIES - SUPPLY (ELECTRICAL)'.
Epoxy insulating floor coating (Valency Compound Make - Valency-111 CLASS A or equivalent (up to 33 kV system)
Enameled caution boards for 33 kV.
Enameled caution boards for 11 kV.
Enameled caution boards for 1.1 kV.
Sheath Voltage Limiters (SVL) for 33 kV system
Fire proof painting for cables for 3 m length at entry points of both ends
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for 33 kV systems - tested as per applicable standard
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for 6.6 kV systems - tested as per applicable standard
Synthetic Insulating Mat of appropriate thickness, 1000 mm wide for upto 1.1 kV systems - tested as per applicable standard
GENERAL ITEMS - Installation of general items mentioned below, as required. - Installation of below listed items referrs to the quantity of items as mentioned in doc. 'BILL OF QUANTITIES - SUPPLY (ELECTRICAL)'.
Office tables of reputed make
Office chairs of reputed make
Full size Cupboard of reputed make, sheet steel enclosure (for documentation)
Tool Cabinet, Wall Mounted
Key Cabinet, Wall Mounted
Tarpaulin (for weather protection of stored electrical equipment)
Insulated step ladder of reputed make (suitable for indoor work in switchgear rooms)
Installation of Motorised Rolling shutter in electrical substation.
ELECTRICAL STATUTORY APPROVAL - Obtaining approval on applicalbe Released for Construction (RFC) / Final drawings, commencement certificate from concerned authorities, approval of installations, liasoning with electrial inspector, organising inspector visits to site as required as per applicable statutory norms, etc. and all the associated work
MANPOWER SUPPLY RATES PER DAY - The below mentioned rates for Manpower Supply shall be applicable only for work performed over and above the electrical works already defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. - The below mentioned rates shall be applicable only if specifically agreed & approved by OWNER / CONSULTANT.
Supervisor
HSE Supervisor
Electrician / Wireman / Technician
Fitter
Welder / Gas Cutter
Rigger
Mason
Helper / Semi-skilled
Testing Engineer
Cable Jointer
Qualified Electrical Engineer
Description of Work / Item(s)
Amount
GENERAL NOTES (1) This document shall be read in conjunction with doc. 'ANNEXURE-II' TO SCC - 'SCOPE OF SUPPLY - ELECTRICAL'. Technical Specification for the equipment / material to be supplied by CONTRACTOR is included therein. (2) For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. (3) Refer the document 'LIST OF APPROVED VENDORS / MAKES - ELECTRICAL' for the makes of equipment / material to be supplied by CONTRACTOR (4) For all the equipment (suitable for Explosive Atmospheres) to be supplied by CONTRACTOR, relevant certification from applicable recognised approving authority shall be provided. (5) For CONTRACTOR supplied items mentioned below, procurement / supply clearance for the items shall be given to CONTRACTOR, in lots as per Project requirement. Subsequent to the receipt of procurement / supply clearance, CONTRACTOR may initiate the required action in this regard. (6) CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any miss outs in supply scope in this regard by the CONTRACTOR shall not be entertained.
EQUIPMENT
LV PANELS (WALL / CONCRETE / STEEL STRUCTURE MOUNTED) Supply of LV panels (wall / concrete / steel structure mounted) as per doc. no.TK-1ZZZA-EL-SPE-0017 (Technical specification for Industrial Equipment) and TK-1ZZZA-EL-SPE-0018 (Technical Specification for Flameproof Equipment)
PDB (Auxiliary Power Distribution Boards)
LOCAL CONTROL STATIONS (LCS) Supply of Local Control Stations as per doc. no. TK-1ZZZA-EL-SPE-0021 (Technical Specification for Local Control Stations)
LCS for Explosive Atmospheres
Type P3 : Flameproof (Gas Group : IIC) :Trip-Neutral-Close (T-N-C) switch shall be spring return to neutral type from CLOSE position with two contacts each for time stamping & tripping signal. Switch shall be lockable in TRIP position & Ammeter (1A, MI type)
CABLES AND WIRES, GLANDING, TERMINATIONS AND CABLE ROUTING SYSTEMS
CABLE GLANDING AND TERMINATION (HV)
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE)
HV Cable gland suitable for 33 / 33 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
HV Cable gland suitable for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE) (OD 51 mm)
HV Cable termination kit Heat shrinkable type (suitable for indoor installation) for 6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE) (OD : 69 mm)
1C x 630 sq.mm A2XCEFY (UE) (OD 51 mm)
CABLE GLANDING AND TERMINATION (LV)
Cable glands suitable for 650 / 1100 V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
8 x Triad x 1.5 (OD : 33.2 mm)
3C x 2.5 Sq. mm (2XWY) (OD : 14 mm)
3C x 4 Sq. mm (2XWY) (OD : 15 mm)
8C x 2.5 Sq. mm (2XWY) (OD : 18.0 mm)
10C x 2.5 Sq. mm (2XFY) (OD : 19.5 mm)
3C x 240 Sq. mm (A2XFY) (OD : 51 mm)
Cable glands suitable for 650 V voltage grade, Cu conductor (stranded / solid), XLPE / PVC insulated, armoured / unarmoured cables for FIRE ALARM AND COMMUNICATION SYSTEM CABLES
1P x 1.5 sq.mm (OD : 14 mm)
2P x 1.5 sq.mm (OD : 21.4 mm)
1P x 2.5 sq.mm (OD : 23.3 mm)
2P x 2.5 sq.mm (OD : 23.3 mm)
12P x 2.5 sq. mm (OD : 38.6 mm)
8Fibre FO CABLE
CAT 6 CABLE
Tinned copper, insulated, Pin type lugs
Tinned copper, insulated, Ring type lugs
Tinned copper, tubular type, heavy duty lugs for bolted connection
Tinned copper, tubular type, long barrel type heavy duty lugs for bolted connection
PREFABRICATED CABLE TRAYS
Prefabricated Cable Trays (GI) - Supply of prefabricated GI perforated and ladder type cable tray / covers, tray separators along with all the associated consumable material for assembly and appropriate installation of the same, as per doc. no. TK-1ZZZA-EL-SPE-0016 (Technical Specification for GI cable Trays)
Separators for Cable Ladders (GI)
300 mm / 600 mm wide
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING
Lighting fixtures Supply of lighting fixtures and associated components / accessories such as lamps, chokes, condensers, reflectors, control gear box for non-integral fixtures etc. as per doc. no. TK-1ZZZA-EL-SPE-0019 (Technical Specification for Industrial Light Fixture) and TK-1ZZZA-EL-SPE-0020 (Technical Specification for Flameproof Light Fixture)
Lighting Fixtures for Explosive Atmospheres
40W LED Ex-d FLP Well Glass Light Fixture
40W LED Ex-d FLP Well Glass Light Fixture Emergency
100W LED Ex-d FLP Medium Bay Light Fixture
100W LED Ex-d FLP Medium Bay Light Fixture Emergency
150W LED Ex-d FLP Flood Light fixture
150W LED Ex-d FLP Flood Light fixture Emergency
20W LED Ex-d FLP Aviation Light
26W, 110V DC LED Ex-d FLP Well Glass Fixture
Hand lamps
24V Hand lamps for Explosive Atmospheres along with 20m extension cable 3c x 1.5sq.mm, YY, 20m, along with the plug suitable for 24V, 5A Industrial switch socket
SMALL POWER Supply of various small power equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'.
Convenience Switch socket outlets
Convenience sockets (single phase) for Explosive Atmospheres
16A, 3 pin,240V AC single phase socket outlet with DPMCB in die cast Al LM6 enclosure, Type S01
Switch socket unit (portable) for Explosive Atmospheres
240V,16A and 24V, 5A combination type switch socket unit for Explosive Atmospheres, with built-in 100VA, 240V / 24V transformer
JUNCTION BOXES (JB) / POWER JUNCTION BOXES (JB) - Supply of various types of junction boxes / power junction boxes suitable for the required cable entries and all associated accessories, as per doc. no.TK-1ZZZA-EL-SPE-0017 (Technical specification for Industrial Equipment) and TK-1ZZZA-EL-SPE-0018 (Technical Specification for Flameproof Equipment) - Supply of junction boxes suitable for bottom entry of incoming and outgoing cables, inclusive of suitable terminals for undrilled gland plate, cable terminations, busbars for cable termination as required, facility for earthing cable termination inside and outside the termination, along with the associated accessories such plugs for cable openings, fixing hardware
Junction boxes Industrial type
Communication Junction Boxes
Outdoor PA System JB for Speakers Incoming : 12Px2.5 sq.mm(1 No.) - M40 Outgoing : 2Px2.5 sq.mm(12 Nos.) - M25 (9 Nos. Gland + 3 Nos. Plug)
Junction boxes for Explosive Atmospheres
Junction boxes
4 way Lighting JB, Ex-d
5 way JB for small power sockets, Ex-d
For 110kW Motor with Incoming cable size 3R-3Cx240sq.mm and outgoing cable size 2R-3Cx240sq.mm
For 160kW Motor with Incoming cable size 4R-3Cx300sq.mm and outgoing cable size 2R-3Cx300sq.mm
Communication Junction boxes
Indoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. MCP Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Hooter / Becon Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px2.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for housing addressable module of 1 no. Detector Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.), 1Px1.5 (1 Nos.) NPT thread glands : 3 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor FA System JB for End of resistor / Fault Isolator in FA loop Incoming : 2Px1.5 (1 No.) Outgoing : 2Px1.5 (1 No.) NPT thread glands : 2 Nos. Plugs : 2 Nos. (Plug for 2Px1.5 size)
Outdoor Telephone System JB (IDF) Incoming : 10Px0.63 mm dia (1 No.) Outgoing : 5Px0.63 mm dia (5 Nos.) NPT thread glands : 6 Nos. Plugs : 3 Nos. (1 No. Plug for 10Px0.63 mm dia & 2 Nos. plugs for 5Px0.63 mm dia)
Outdoor PA System JB for FCS Incoming : 12Px1.5 (1 No.) Outgoing : 2Px1.5 (6 Nos.) NPT thread glands : 7 Nos. Plugs : 2 Nos. (1 No. Plug for 12Px1.5 and 1 No. for 2Px1.5)
Outdoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
Indoor PA System JB for Speakers Incoming : 12Px2.5 (1 No.) Outgoing : 2Px2.5 (12 Nos.) NPT thread glands : 13 Nos. Plugs : 3 Nos. (1 No. Plug for 12Px2.5 and 2 Nos. for 2Px2.5)
Installation Material for Junction boxes (wall / concrete / steel structure mounted) - Supply of all the Installation Material (excluding structural steel) for Junction boxes (wall / concrete / steel structure mounted) as per 'Installation Details - Power' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : L08A
Installation Type : L08B
Installation Type : L08C
Installation Type : P10A
Installation Type : P10A/P11A
Installation Type : P10B
FIRE ALARM AND COMMUNICATION SYSTEMS
FIRE ALARM (FA) SYSTEM - Supply of all the Installation Material (excluding structural steel) for FA system equipment and associated accessories as per applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
FA system accessories (Industrial / For Explosive Atmospheres)
Installation Type: FAHZ1
Installation Type: FCPC1
Installation Type: FCPC2
Installation Type: FCPR1
Installation Type: FCPS1
Installation Type: FMDC1
Installation Type: FMDF1
Installation Type: FMDF2
Installation Type: FMDS1
Installation Type: FRIC1
Installation Type: FRIF1
Installation Type: FCPS2
Installation Type: CFBC1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08E
PUBLIC ADDRESS (PA) SYSTEM - Supply of all the Installation Material (excluding structural steel) for PA system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
PA system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTFC1
Installation Type: CTFC2
Installation Type: CTFS2
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKC3
Installation Type: CSPKF1
Installation Type: CSPKS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation Type: L08C
Installation Type: L08D
Installation Type: L08E
TELEPHONE SYSTEM Supply of all the Installation Material (excluding structural steel) for Telephone system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
Installation of Network cabinets, EPABX servers, workstations, LAN/FO Cabinets
Telephone system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTFC1
Installation Type: CTFS2
Installation Type: CTFZ1
Installation Type: CFBC1
Installation Type: CFBS1
Installation Type: CSPKC1
Installation Type: CSPKS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08B
Installation RJ45 Telephone Socket
Installation RJ45 LAN Socket
CCTV SYSTEM Supply of all the Installation Material (excluding structural steel) for CCTV system equipment and associated accessories as per "Installation standards- Communication & PA System" and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work
CCTV system accessories (For Industrial / Explosive Atmospheres)
Installation Type: CTVC2
Installation Type: CTVS1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08E
Installation Type: L08G
EARTHING AND LIGHTNING PROTECTION
EARTHING MATERIAL
Earthing conductor Supply of GI strip / bare copper conductor for earthing
50 x 6 mm GI strip
75 x 10 mm GI strip
8 SWG SOLID G.I. WIRE
10 MM (3/8") DIA G.I WIRE ROPE
16 MM (5/8") DIA G.I WIRE ROPE
Earth / lightning protection electrodes Supply of Earth / lightning protection electrodes along with the associated accessories / material as per 'Installation Details - Earthing', including any additional hardware as per site requirement so as to ensure the completeness of installation work
Installation Type : E01A :100 mm Dia, 3 m length GI pipe earth electrode for Electrical Safety earth
Installation Type : E01B : 100 mm Dia, 6 m length GI pipe earth electrode for Instrument clean earth
Installation Type : E01A : 100 mm Dia, 3 m length GI pipe lightning protection electrode
Earth buses - Supply of Earth buses along with the associated accessories (excluding structural steel) as per 'Installation Details - Earthing' and applicable construction documents, including any additional material as per site requirement so as to ensure the completeness of installation work - Supply of steel support structure / supporting frames for above shall be considered separately in SECTION - F.
Installation Type : E02A GI earth bus for Electrical safety
Installation Type : E02B GI earth bus for Electrical safety
Installation Type : E02B - GI earth bus for instruments
LIGHTNING PROTECTION MATERIAL
Lightning protection conductor - Supply of GI strip / bare copper conductor/aluminium/HDGI Round conductor for Lightning protection and associated accessories - Supply of accessories such as test links, cross connectors, parallel connectors for lightning protection down conductors, epoxy insulator supports and the associated accessories as per 'Installation Details - Lightning Protection' / as indicated in applicable construction documents / as per the site requirement, are considered in running meter length of lightning protection down conductors.
Installation Type: E16 Roof Conductor (Conductor Size- 25x6mm)
Installation Type: E16 Down Conductor (Conductor Size- 25x6mm)
Test Link : E16 : 50x6mm GI Link 150mm Long
STRUCTURAL STEEL - Supply of structural steel - The quantity of structural steel indicated below is matching with the quantity of steel indicated in SECTION-F of doc. 'BILL OF QUANTITIES - INSTALLATION (ELECTRICAL)'. - Section wise requirement shall be estimated by CONTRACTOR, as per the applicable construction documents / various applicable 'Installation Details' mentioned in 'SECTIONS - A to E' in this document. - Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance.
Structural steel (MS) Supply of coating material and paint as required for surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI-SPE-0003 (Technical Specification for Painting) is included in scope.
Structural steel (Hot deep galvanized GI)
MISCELLANEOUS ITEMS
CANOPIES - Supply of GI / FRP canopies for various equipment and all associated accessories, as per 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL'. - Site visit as required to confirm the actual dimensions / arrangement of various equipment installed at site, so as to fabricate canopy exactly suitable for the equipment is considered in the scope. - Supply of all the Installation Material (including steel supporting frame as required) required as per site requirement is included in the scope.
Canopies for Motors
GI canopy complete with louvers backed up by wire mesh
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6kV) Motors
SAFETY ITEMS Supply of safety items as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents ALL SAFETY ITEMS SHALL BE OF REPUTED MAKE & SHALL HAVE PROVEN PAST TRACK RECORD. LOCAL MAKES ARE NOT ACCEPTABLE
Fire proof painting for cables for 3 m length at entry points of both ends
Description of Work / Item(s)
Amount
GENERAL NOTES (1) This document shall be read in conjunction with doc. 'ANNEXURE-I' TO SCC - 'SCOPE OF WORK - ELECTRICAL'. (2) For 'Limit of Variation' in the rates / quantities / total value of work, please refer 'SPECIAL CONDITIONS OF CONTRACT'. (3) CONTRACTOR shall only use 'Released for Construction (RFC)' drawings / documents for execution of work during the Construction phase. (4) Dismantling activities shall be paid at 30% of the unit rates of the respective installation work. Dismantling activities shall only be paid to CONTRACTOR if instructed by OWNER / CONSULTANT, and not for erroneous execution done by CONTRACTOR. (5) All the fixing hardwares such as nuts, bolts, U-bolts, screws, washers & clamps shall be of Stainless Steel (SS304). (6) CONTRACTOR shall ensure that the rates quoted for execution of electrical works take into account all requirements, services, activities & responsibilities defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. (7) Special attention shall be given to include the efforts necessary to implement & comply with the relevant safety practices to be followed for the electrical works at the Plant Site, as per the applicable HSE documents. (8) CONTRACTOR should read entire specification to understand in totality the scope of supply and Installation. Every line item for Supplies and Installation should be read along with the respective Installation standard / hook up drawings related to that specific line item to understand the scope of supply and Installation in totality. Any missouts in supply scope in this regard by the CONTRACTOR shall not be entertained.
Testing, precommissioning and commissioning of INDUCTION MOTORS AND CANOPIES Testing, precommissioning and commissioning activities are included in the scope.
LV (415V) Motors
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6 kV) Motors
200 kW to 315 kW
7910kW (Heat Pump compressor motor)
Canopies - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of canopy for the motor - as per applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work, minor modifications (cutting, drilling etc.) in the canopy fitting arrangemet if required - Supply of all fixing hardware as per the site requirement is included in the scope
LV (415V) Motors
45.0 kW to 90 kW
110 kW to160 kW
HV (6.6 kV) Motors
185kW to 315 kW
LOCAL CONTROL STATIONS (LCS) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of equipment, assembling and installation of components / devices supplied separately - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation of Industrial/ Explosive Atmospheres type LCS (wall / concrete / steel structure mounted) shall be as per 'Installation Details - Power' and applicable construction documents.
Installation Type: P07A
Installation Type: P08A
CABLE / WIRE LAYING, TERMINATION AND CABLE ROUTING SYSTEMS
CABLE LAYING - Handling, shifting of cable drums from site-store / yard to the installation location, unpacking, laying of cables / wires in cable trays (either located above ground or inside RCC cable trenches) / directly buried underground / in sand filled cable trenches (trench constructed by others) / through above ground conduits (PVC / GI) clamped on wall or structure or through floor conduits (excluding lighting circuit cables, from SLDB / ESLDB onwards upto the lighting fixtures) - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work - Testing, precommissioning and commissioning activities are included in the scope. - Supply and installation of certified trefoil clamps of non-magnetic material, spacer bars and saddles, dressing of cables using Stainless Steel cable ties, cable tags(RFID tags) and ferrules (including all fixing hardware) as per the site requirement are included in the scope. - Supply of water / fireproof compound (of reputed make) and sealing of openings for cable entries by applying the same (whether spare openings or openings with cables passing through) is included in the scope. - Refer 'Annex-EW4-6' - 'Details of openings to be sealed', for quantity estimation of sealant to be applied at various locations. - Minor civil work such as chipping / drilling of through-holes / cutouts in floor / walls, replastering and making area good after work done, providing sleeves during the cable laying as per the site requirement and replastering the same (including the supply of consumable material for the same) is included in the scope. - Installation of cable route markers (as applicable including RFID tags) shall be as per 'Installation Details - Power' and applicable construction documents.
HV CABLES All cables indicated below are laid in air (above ground / in cable trays installed in RCC cable trenches), unless otherwise indicated.
6.6 / 6.6 kV (UE) voltage grade, Al conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
LV CABLES All cables indicated below are laid in air (above ground / in cable trays installed in RCC cable trenches), unless otherwise indicated.
600 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, armoured power / control / lighting / signal cables
8 x Tried x 1.5
3C x 2.5 Sq. mm (2XWY)
3C x 4 Sq. mm (2XWY)
8C x 2.5 Sq. mm (2XWY)
10C x 2.5 Sq. mm (2XFY)
3C x 240 Sq. mm (A2XFY)
FIRE ALARM AND COMMUNICATION SYSTEM CABLES 650 V voltage grade, Cu conductor (stranded / solid), XLPE insulated, screened, armoured communication cables
10P x 0.5 sq.mm (Jelly Filled)
2P x 1.5 sq.mm
3C x 2.5 Sq. mm (2XWY)
CABLE GLANDING AND TERMINATION (HV) (Industrial / For Explosive Atmospheres) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of HV cable termination kit and cable glands with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of tinned copper lug, drilling and treading of gland plate, termination of cable at designated location and other associated work so as to ensure the completeness of installation work. - Cable termination shall be carried out by experienced, competent & certified personnel from the termination kit MANUFACTURER / installation CONTRACTOR. - Raychem Make termination kits shall be used.
Glanding and Termination of 6.6 / 6.6 kV (UE) voltage grade, Al / Cu conductor, XLPE insulated, screened, armoured power cable
3C x 240 sq.mm A2XCEFY (UE)
1C x 630 sq.mm A2XCEFY (UE)
CABLE GLANDING AND TERMINATION (LV) (Industrial / For Explosive Atmospheres) - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembly and installation of cable glands (industrial / For Explosive Atmospheres type) with PVC hoods, installation of components supplied separately - as recommended by MANUFACTURER / applicable construction documents, installation of lug, drilling and treading of gland plate, termination of cable (excluding lighting circuit cables, from SLDB / ESLDB onwards upto the lighting fixtures) at designated location and other associated work so as to ensure the completeness of installation work. - Tinned Copper Lugs shall be used for Stranded Copper (Cu) conductor cables and Aluminium Lugs for Aluminium conductor cables (Al).
LV CABLES
Glanding and Termination of 650 / 1100V (Uo / U) voltage grade, Al / Cu conductor (stranded / solid), XLPE insulated, screened, armoured power / control / lighting cables
8 x Tried x 1.5
3C x 2.5 Sq. mm (2XWY)
3C x 4 Sq. mm (2XWY)
8C x 2.5 Sq. mm (2XWY)
10C x 2.5 Sq. mm (2XFY)
3C x 240 Sq. mm (A2XFY)
Glanding and Termination of FIRE ALARM AND COMMUNICATION SYSTEM CABLES 650 V voltage grade, Cu conductor (stranded / solid), XLPE insulated, screened, armoured communication cables
1P x 0.5 sq.mm (OD : 13.2 mm)
1P x 1.5 sq.mm (OD : 14 mm)
2P x 1.5 sq.mm (OD : 21.4 mm)
1P x 2.5 sq.mm (OD : 23.3 mm)
2P x 2.5 sq.mm (OD : 23.3 mm)
LIGHTING, SMALL POWER, WELDING SOCKETS AND JUNCTION BOXES
LIGHTING - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of lighting fixtures, assembling and installation of components / accessories such as lamps, chokes,condensers, reflectors, control gear box for non-integral ffixtures etc. supplied separately - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Installation of lighting fixtures shall be as per 'Installation Details - Lighting' and applicable construction documents. - Control gear boxes for non-integral type lighting fixtures are a separate item, and installation type designation for the same is indicated as separate line item below. - Fabrication and installation of steel support structure / supporting frames for equipment as per the site requirement, is considered separately in SECTION - F.
Well glass lighting fixtures
Installation Type : L07A
Installation Type : L07B
Installation Type : L07C
Installation Type : L07D
Installation Type : L05
Medium bay / high bay lighting fixtures
Installation Type : L13B
Flood lighting fixtures
Installation Type : L12A
Installation Type : L02
Installation Type : L11
Aviation light (flashing / steady burning) with controller
Installation Type : L14A
JUNCTION BOXES (JB) AND POWER JUNCTION BOXES (PJB) FOR MOTORS / OTHER EQUIPMENT - Handling, shifting from site-store / yard to the installation location, unpacking, erection, alignment, assembling and installation of junction boxes / power junction boxes and associated accessories on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, checking of internal wiring, stenciling with paint on equipment enclosures as required and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F. Installation of Junction Boxes shall be as per 'Installation Details - Power' and applicable construction documents. - Refer 'ANNEXURE-II to SCC - SCOPE OF SUPPLY - ELECTRICAL' for the 'Type designations' mentioned below.
Junction Boxes for Explosive Atmospheres
TYPE-L08A/B/C (4 way JB for lighting outdoor) Approx. Dimensions (LxBxH) : 150 x 100 x 100 mm Mounting : wall / concrete / steel structure
TYPE-L08A/B/C (JB for Single Phase Loads) Approx. Dimensions (LxBxH) : 250 x 100 x 100 mm Mounting : wall / concrete / steel structure
Power Junction boxes for motors / other equipment for Explosive Atmospheres
TYPE- P10A/B (TAG : Motor JB) Installation Type : P10A/B, P11A/B, P12A/B, P17 Approx. Dimensions (LxBxH) : 400 x 300 x 400 mm Approx. Weight : 30 kgs Mounting : concrete / steel structure / Self Satnding Pedestal
FIRE ALARM AND COMMUNICATION SYSTEMS
FIRE ALARM (FA) SYSTEM - Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of various components in FA system and associated accessories such as manual call points, plug-in devices, bases for devices etc. on wall / concrete / steel structure - as recommended by MANUFACTURER / applicable construction documents, stenciling with paint on equipment enclosures as required andand other associated work so as to ensure the completeness of installation work. - Testing and precommissioning activities, commissioning assistance as required by MANUFACTURER's supervisor is included in the scope. - Minor civil work such as chipping, grouting for fixing of various equipment and replastering the same as per the site requirement (including the supply of consumable material for the same) is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope. - Installation shall be as per 'Installation Details - Fire Alarm System' and applicable construction documents. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
FA system accessories Industrial type / Explosive Atmospheres
Installation Type: FAHZ1
Installation Type: FCPC1
Installation Type: FCPC2
Installation Type: FCPR1
Installation Type: FCPS1
Installation Type: FMDC1
Installation Type: FMDF1
Installation Type: FMDF2
Installation Type: FMDS1
Installation Type: FRIC1
Installation Type: FRIF1
Installation Type: FCPS2
Installation Type: CFBC1
Junction boxes Installation shall be as per 'Installation Details - Lighting' and applicable construction documents.
Installation Type: L08E
EARTHING AND LIGHTNING PROTECTION - Handling, shifting from site-store / yard to the installation location, unpacking, assembling and installation of earthing and lightning protection systems and accessories underground / wall / concrete / steel structure / cable trays - as recommended by MANUFACTURER / applicable construction documents and other associated work so as to ensure the completeness of installation work. - Testing, precommissioning and commissioning activities are included in the scope.
EARTHING Installation shall be as per 'Installation Details - Earthing' and applicable construction documents.
Installation of earth conductor laid underground - Excavation of soil up to the required depth, installation of earth conductor (GI strip / bare copper conductor / insulated copper cable), back filling and compacting of soil and disposing the excess soil, termination as required - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope.
50 x 6 mm HDGI strip
75 x 10 mm HDGI strip
Installation of earth conductor laid on wall / concrete / steel structure / cable trays - Installation of earth conductor (GI strip) on wall / concrete / steel structure / cable trays by cleating at every 500mm, termination as requied - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
50 x 6 mm HDGI strip
75 x 10 mm GI strip
8 SWG SOLID G.I. WIRE
10 MM (3/8") DIA G.I WIRE ROPE
16 MM (5/8") DIA G.I WIRE ROPE
Installation of earthing / lightning protection electrodes - Excavation of soil upto the required depth, installation and testing of earth electrode, filling of the pit with the appropriate material as required, earthing connection of earth electrode with main earth grid, back filling, compacting of soil, disposing the excess soil. - Civil work including construction of concrete chamber with cover for the earth pit as per the site requirement is included in the scope.
Installation Type : E01A
Installation Type : E01B
Installation of earth buses - Installation and testing of earth buses on wall / concrete / steel structure / cable trays. - Supply of all fixing hardware as per the site requirement is included in the scope. - Fabrication and installation of steel support structure as per the site requirement, is considered separately in SECTION - F.
Installation Type : E02A
Installation Type : E02B
LIGHTNING PROTECTION - Installation shall be as per 'Installation Details - Lightning Protection' and applicable construction documents.
Installation of lightning protection conductor laid on wall / concrete / steel structure / roof - Installation of lightning protection conductor (GI strip) on wall / concrete / steel structure including the installation of test links and accessories, insulator supports, termination as required. - For GI earthing conductors, laying of conductor including bending, drilling, welding / jointing as required is included in the scope. - For GI earthing conductors, supply and application of coal tar bituminous paint or cold galvanising paint on welded joints is included in the scope. - Supply of all fixing hardware as per the site requirement is included in the scope.
25 x 6 mm HDGI strip : E16
STRUCTURAL STEEL - Fabrication, erection (by welding / fixing by anchor fastners), surface preparation and painting of structural steel as per the applicable construction documents so as to ensure the completeness of installation work for all the electrical equipment / items mentioned in Section A to E above, and chequered plates as per the applicable construction documents. - Supply of all consumables such as welding electrodes (Advani Oerlikon or equivalent), gas for cutting etc. are included in the scope. - Measurement of steel quantity for installation shall be based on actual quantities installed at site without wastage allowance. - Surface preparation and painting of steel shall be as per doc. TP-1ZZZA-PI- SPE-0003. (Technical Specification for Painting)
Structural steel (MS)
Galvanised Iron (GI)
MISCELLANEOUS ITEMS
SAFETY ITEMS - Installation of safety items mentioned below, in all the electrical rooms / buildings / transformer yards, etc. as per applicable statutory requirements / HSE documents / as indicated in applicable construction documents. - Installation of below listed items referrs to the quantity of items as mentioned in doc. 'BILL OF QUANTITIES - SUPPLY (ELECTRICAL)'.
Fire proof painting for cables for 3 m length at entry points of both ends
MANPOWER SUPPLY RATES PER DAY - The below mentioned rates for Manpower Supply shall be applicable only for work performed over and above the electrical works already defined as forming part of CONTRACTOR’s scope in the Tender Document / Contract. - The below mentioned rates shall be applicable only if specifically agreed & approved by OWNER / CONSULTANT.
Supervisor
HSE Supervisor
Electrician / Wireman / Technician
Fitter
Welder / Gas Cutter
Rigger
Mason
Helper / Semi-skilled
Testing Engineer
Cable Jointer
Qualified Electrical Engineer
Konstelec Engineers Limited (BID ID -3123066)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3115564)
Offshore Infrastructures Ltd (BID ID -3115703)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3115564)
Offshore Infrastructures Ltd (BID ID -3115703)
Konstelec Engineers Limited (BID ID -3123066)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3115564)
Konstelec Engineers Limited (BID ID -3123066)
Offshore Infrastructures Ltd (BID ID -3115703)
M/s SterlingElectro Enterprises.P.Ltd (BID ID -3115564)
Offshore Infrastructures Ltd (BID ID -3115703)
Konstelec Engineers Limited (BID ID -3123066)
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid