Awarded to POWER ENGINEERING (INDIA) PRIVATE LIMITED
₹48.5 L
Products
Product
Brand / Model
HSN
Quantity
Unit Price
Amount
500kVA Diesel Generator set
Power Engineering (India) Pvt. Ltd / PKGBU-500
8502
1 Set
4,661,190
4,661,190
Factory Acceptance Test of DG Set
Power Engineering (India) Pvt. Ltd / -
9983
1 Job
12,000
12,000
250mm dia MS Pipe for Exhaust of DG Sets
Power Engineering (India) Pvt. Ltd / -
8708
15 Meter
9,185
137,775
No Smoking and Danger Zone in Signal Red Colour
Power Engineering (India) Pvt. Ltd / -
8310
1 Each
900
900
MS support structure for exhaust fume pipes from DG Set
Power Engineering (India) Pvt. Ltd / -
8708
300 Kg
120
36,000
Documents Required
5 documents required · 5 mandatory
RequiredExperience Criteria
RequiredBidder Turnover
RequiredCertificate (Requested in ATC)
RequiredAdditional Doc 1 (Requested in ATC)
RequiredCompliance of BoQ specification and supporting document
Eligibility Criteria
Experience
3 yrs
Min Turnover
₹3
Purchase Preferences
MSE Purchase PreferenceMII Purchase Preference
Fee & Financial Details
EMD Fee Amount
₹1.6 L
Important Dates
Last Activity
3 Apr 2024
Published
20 Feb 2024
Bid Opening
5 Mar 2024
Bill of Quantities
Item Wise
GeM BOQ Items (5 items)
Item No
Item Title
Description
Qty
Unit
Consignee
Delivery (days)
Spec
1
500kVA Diesel Generator set
Supply, installation, testing and commissioning of 500 KVA CPCB-IV, 415 volt 3 phase, 1500 R.P.M, 0.8 PF radiator cooled Silent Diesel Generator set with Inbuild AMF Panel housed in an acoustic enclosure conforming to latest environment protection regulations for emmission and noise levels complete with Diesel Engine developing either 587 BHP at 1500 RPM or actual BHP calculated considering de-rating factor if any whichever is higher. DG Set shall complete with Engine, Alternator, Engine control panel and equipped with Power Command Control System Manual control Panel consisting of FP 320 Amp Moulded Case Circuit Breaker with meters, CTs and transducers for all metering and protection, fuel pipe line upto 10 metre Antivibration mountings, hospital type silencer, electric starter, batteries & battery charger, fuel tank of 8 hours capacity with level indicator, radiator including control wiring, From Power command controller to DG control Panel, first fill of lubricating oil & all accessories complete with necessary civil work such as excavation, back filling, PCC, Steel Reinforcement, cement concrete foundation, plastering, grouting, chipping, finishing etc. as required complete as per specification and as required. (DG Set foundation shall be cast as per manufacturer shop drawing and deemed to be included in quoted rates). The DG Set Installation work should be as per norms of CEA/ Central Electrical Inspectorate / Pollution control board standards.
1
Set
Krishna Bhayyaji Kurve
413801,Tukai Nagar, Daund
60
2
Factory Acceptance Test of DG Set
Factory Acceptance Test of DG Set for 13 Hrs.
1
Job
Krishna Bhayyaji Kurve
413801,Tukai Nagar, Daund
60
3
250mm dia MS Pipe for Exhaust of DG Sets
Supply and fixing of 250 mm dia of MS B Class piping with bends etc. for Exhaust of DG Sets including providing suitable self supporting arrangement at suitable intervals, painting etc. and supplying and fixing 150 mm thick Rock wool matrix (3x50 mm. thick) insulation of density 150 Kg per cubic metre on all sides of Exhaust pipe and silencer with chicken mesh wrapping and 22 SWG aluminium sheet cladding, suitable for outdoor installation complete as required including guide support, expansion joint, SS bellows as required and as per specification.
15
Meter
Krishna Bhayyaji Kurve
413801,Tukai Nagar, Daund
60
4
No Smoking and Danger Zone in Signal Red Colour
Providing & Fixing 200mm x 150mm size danger plates made of mild steel at least 2mm thick & vitreous enamelled white on both sides and with inscriptions NO SMOKING and DANGER ZONE in signal red colour on front side as required.
1
Each
Krishna Bhayyaji Kurve
413801,Tukai Nagar, Daund
60
-
5
MS support structure for exhaust fume pipes from DG Set
Providing & fixing for MS support structure for exhaust fume pipes from DG Sets (Exhaust pipe to be measured and paid for separately) along horizontal and vertical runs upto the height (as per CPCB norms) including cutting, welding etc and applying two coats of red oxide and two coats of synthetic enamelled paint of colour and shade as directed by consultant/ client. The design of the support structure shall be done by the contractor and shall be as per CPCB norms approved, also to get the approval from the consultant/ client before execution etc. complete as required. (Structure foundation shall be cast as per shop drawing and deemed to be included in quoted rates).
300
Kg
Krishna Bhayyaji Kurve
413801,Tukai Nagar, Daund
60
Stage Documents
Award of Contract
contract_GEMC-511687700671943.pdf
GEM_CONTRACT • 0.11 MB
Documents
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .