| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹4.3 CrAccepted-AOC 2ND STAGE BANGALORE KARNATAKA 560058 | BENGALURU URBAN | KARNATAKA | 560058 | ₹4.3 Cr | L1 | Accepted-AOC L1 |
| 2 | L2₹4.7 Cr+₹48.2 L (11.3%)Rejected-Finance 7 2 1813 5 A ADJ TO POST OFFICE INDUSTRIAL ESTATE SANATHNAGAR HYDERABAD TELANGANA 500018 | MEDCHAL MALKAJGIRI | TELANGANA | 500018 | ₹4.7 Cr+₹48.2 L (11.3%) | L2 | Rejected-Finance Bidder is NOT L1 |
| 3 | L3₹5.1 Cr+₹80.0 L (18.8%)Rejected-Finance PLOT NO 299 300 GIDC MAKARPURA VADODARA VADODARA GUJARAT 390010 | VADODARA | VADODARA | GUJARAT | 390010 | ₹5.1 Cr+₹80.0 L (18.8%) | L3 | Rejected-Finance Bidder is NOT L1 |
Tender Value
Refer Docs
EMD Value
₹4.0 L
Closing Date
8 Aug 2024, 2:30 pmClosed
GM (Contracts)
PLHO, Noida
Design, supply, installation, testing a commissioning of Instrumentation, PLC based Control System, Fire and Gas alarm detection system at specified stations of Jalandhar Goindwal Sahib LPG Pipeline and Annual Maintenance Contract for a period of fiv
2024_PLHO_177872_1
PLCC/JGPL/TI/24038
Open Tender
Instrumentation - All
Works
270 days
In the state of Punjab
As per tender document
7 documents required · 7 mandatory
₹4.0 L
Yes
Through VC
1 Nov 2024
1 Jun 2024
9 Aug 2024
1 Jun 2024
8 Aug 2024
16 Jun 2024
1 Jun 2024 - 13 Jun 2024
10 Jun 2024
Amount
CONTROL SYSTEM, F&G WORKS
10 SUPPLY
Dual Redundant, hot standby, PLC (microprocessor based) system, fault avoidant, complete with Processor, I/O modules, Serial interface modules, Media Converters, Relay Modules,TBs, MCBs, Data Panel (wherever applicable), interconnecting cables, data cables, Managed L-2 Switches (2 Nos with min 16 Ports each) with optical as well as copper ports , Marshalling Panels, rack power supply (dual-redundant), interrogation power supplies (dual-redundant), software auto-manual stations, emergency shutdown switch, diagnostics, firmware, power distribution cabinets, Lightning protection devices and all installation materials etc. so as to make the system complete in all respects as per system configuration, I/O list and tender specifications.
Goindwal Sahib station
Pre-Engineered Smoke Detection and extinguishing system as per technical specifications
Goindwal Sahib station
Supply of Remote I/O Panel (Front & Rear side) complete with I/O modules, communication module, Relay modules, interconnecting cables, data cables & Marshalling Panel with rack power supply, interrogation power supplies (dual-redundant), terminal blocks, MCBs, power distribution, cabinets, Lightning protection devices and all installation materials etc. so as to make the system complete in all respects as per system configuration, I/O list and tender specifications. (Panel shall be installed in Hazardous area)
Active Barriers as per technical specifications
For DI
For AI
For A/O
For Pulse
Surge Protection Devices as per technical specifications
For Analog signals (AI/AO)
For RS 232/485 signals
For LAN application
3 Phase 4 wire (415 V) TT applications
1 Phase 2 wire (230 V) applications
IT HARDWARE & NETWORKING
Process PLC Programming Terminal as per tender specifications, along with accessories (including 01 pair of KVM extender with each machine) and softwares as per scope of work and technical specifications.
Server cum Operator work station as per tender specifications for Control System HMI , along with accessories (including 01 pair of KVM extender with each machine) and softwares as per scope of work and technical specifications.
SCADA SYSTEM HMI machines as per tender specifications , along with accessories (including 01 pair of KVM extender with each machine) and softwares as per scope of work and technical specifications.
Supply of 23" Display Monitor as per tender specifications.
LED Display Unit (50" or above) System with interface complete with all inter connecting cables, cords, connectors, peripherals, OEM's make Mounting Kits etc complete in all respects as per the tender specifications & datasheet.
Industrial Grade Programming Terminal (Laptop) for BV-RTUs: 10/100/1000 MBPS Ethernet card, rain, spill, dust and vibration resistant, Li-ion battery, Power Adapter, necessary interfaces (serial & parallel), necessary software as per specifications, carrying case complete with all interconnecting cables, cords, connectors, USB to Serial (RS485) Converter & peripherals etc. complete in all respects as per tender specifications.
Industrial Grade L3 Ethernet Switch (having 4 Nos. of 10Gbps ports & 24 Nos. of 10/100/1000 MBPS ports) with cables & connectors etc. complete in all respects as per tender specifications (1 Set Comprises of 2 switches)
Industrial Grade L2 Ethernet Switch (having 24 Nos. of 10/100/1000 MBPS ports) with cables & connectors etc. with optical 1G ports 2 nos. (with SFP & OFC patch cords), complete in all respects as per ten der specifications (1 Set Comprises of 2 switches)
WAN Router (16 port) system with software, cables, connectors etc complete in all respects as per tender specifications
WAN Router (8 port) system with software, cables, connectors etc complete in all respects as per tender specifications
Firewall as per tender specifications complete with cables, connectors, software etc.as per tender specifications. Control system Firewall
Firewall as per tender specifications complete with cables, connectors, software etc.as per tender specifications. SCADA system Firewall
LaserJet Printer, c/w all interconnecting cables, cords, connectors etc., complete in all respects as per tender specs & datasheet
Industrial Grade Ethernet to 2-4 port Serial Gateway/ MODBUS TCP to MODBUS RTU Converter with required connectors, cables, power supply etc. as per tender specifications. (1 set comprises 2 converters)
Industrial grade Serial to Fiber Optic Converter compatible to Owner supplied fibre & supply of patch cords, pig tails, connectors etc. as per tender specifications. (1 SET comprises of media converter at both ends with accessories)
Industrial grade Ethernet to Fiber Optic Converter compatible to Owner supplied fibre & supply of patch cords, pig tails, connectors etc. as per tender specifications.(1 SET comprises of media converter at both ends with accessories)
Industrial grade Serial to Ethernet convertor with required connectors, cables, power supply, etc (1 set comprise of 02 converters) Material to be supplied with RJ45 Configuration kit i.e. One RJ45 to DB9F adapter and one Ethernet crossover cable to be supplied with each module.
Industrial Grade Networking & Optical fibre accessories including LIU, network termination boxes/ fibre management system, pig tails, patchcords, connectors for the complete control System as per tender specifications. (1 set comprises of 2 nos. with all accessories)
SOFTWARE
PLC programming / Ladder logic software etc. for Dual redundant PLC's
MMI Software of same make as the PLC (including one time license fee) etc as per the tender specification. 1 Set means 5 MMI license with one MMI having capability of editing/Creating new graphic screens (i.e. for Control system HMI (02 nos), Mktg HMI (01 no.), F&G HMI (01 no.) and programming terminal (1 no)).
PLC Spares
PLC Processor Module
PLC Processor power supply
Rack communication module
Rack power supply
Ethernet interface communication module
Digital input module
Digital output module
Analog input module
Analog output module
Serial Interface communication module
Field interrogation power supply
UPS Systems
UPS for Control system
15 KVA in (1+1) parallel redundant equal load sharing configuration with Power SPDs and ACDB excluding battery as per the tender specifications - For T&I Requirement
Sealed maintenance free 2V VRLA battery in dual string for 4 hrs backup considering aging, temperature & capacity factors complete with all interconnecting cables, glands, battery cables, battery stands, AC distribution boxes, connectors & lugs etc as per the tender specifications for 15 KVA T&I system UPS
1 KVA UPS with 20 minutes battery back-up for SIC Terminal/ Electrical LT control supply
UPS Spares
PCB's, one of each type for 15 KVA UPS
Pre-Engineered Smoke Detection and extinguishing system as per technical specifications
For 15 KVA UPS System
Console Desk & Other Furniture items
Console Desk suitable for mounting of all the SCC computers, telephone instruments, conference set, station logbook etc, complete as per tender specifications & datasheet.
Upto 10 sections (excluding pie sections
Server Cabinet as per tender specifications along with draw out type LCD, Keyboard, Patch Panels, Patch Chords, Horizintal and Vertical Cable managers and KVM switch complete for mounting of various IT hardware like servers, networking hardware etc complete as per tender specifications & datasheet.
Furniture & fixtures complete as per Tender Specifications.
Swivel chairs
Table for printers
Table for SIC terminal
File Cabinet/ Spares cabinet : approx. 2 m height for industrial file/ spares storage. Glass front .
Cables
Supply of CAT6 cable (unarmoured) as per tender specifications
Supply of CAT 6 Cable (Armoured) as per tender specifications
Supply of Armoured Power cable (3CX2.5 sqmm) as per tender specifications
Cat 6A, LSZH, Stranded Patchcord, 2 Mtr (reputed make) as per tender specifications.
LEL Controller (16 Channel & SIL-2 Certifed) as per tender specifications
2 loop, Addressable, Intelligent Fire Detection and Alarm Panel for automatic fire detection & annunciation of alarms for various types of detectors installed like multi sensor, heat detectors, response indicators, loop isolators, manual call points, hooters etc installed in plant area and various buildings as per tender specifications
Fire Alarm Repeat Panel to provide faithful indication of the the status of Main Fire Alarm Panel at a distance of upto 150 m.
IR Based explosion proof & weather proof (Point type) Hydrocarbon detectors along with all mounting & other accessories as per tender specifications.
Multi sensor detectors (addressable type) along with all mounting & other accessories as per the tender specifications
Multi sensor detectors (with relay based output) along with all mounting & other accessories for installation at BV-RTU locations as per the tender specifications
Explosion proof heat detectors for telecom battery room at unattended stations as per technical specifications
Response Indicators along with all mounting & other accessories as per the tender specifications.
Addressable Manual Call Point (for safe area) along with all mounting & other accessories as per the tender specifications.
Manual Call Point (Explosion Proof & Weather Proof) for hazardous area along with all mounting & other accessories as per the tender specifications.
Addressable Beacons for safe area along with all mounting & other accessories & instructions sign as per the tender specifications.
Beacons (Explosion Proof & Weather Proof) for hazardous area along with all mounting & other accessories as per the tender specifications.
Addressable Hooters / Horn / Strobe (for safe area) along with all mounting & other accessories as per the tender specifications.
Explosion Proof / Weather Proof Hooters (for hazardous area) along with all mounting & other accessories as per the tender specifications.
Isolators for isolating of signalling loop in case of any fault alongwith all mounting & other accessories as per the tender specifications.
Monitor modules along with all mounting & other accessories for third party interface as per the tender specifications.
Electric Fire Siren with control panel as per tender specifications.
Portable Gas Detector with controller, audio-visual alarm and suitable (intrisically safe) for hazardous area classified as classification Class I, Div. I Group C&D as per API-RP-500 as per tender specification
Surge Protection Devices for analog signals from 3 wire Infrared Hydrocarbon Detectors
2 Pair x 1.5 Sq. mm, unarmoured FRLS cable compliant to BS:5308, as per the tender specifications for indoor applications to be laid through conduits.
20 mm ISI marked GI conduit along with all fittings & fixtures likeTees, bends, junction boxes, etc for installation of various fire detectors in building
Flame proof and weather proof junction boxes including supply of EP/WP double compression cable glands, plugs for unused cable entries including EP/WP certificates as per the tender specifications for IR type hydrocarbon detectors in hazardous areas.
Weather proof junction boxes including supply of double compression cable glands, plugs for unused cable entries including WP certificates as per the tender specifications for various detectors in buildings.
Calibration kit for Point type Hydrocarbon detectors with gas cylinder, regulator, hose pipe, flowmeter etc. along with required accessories complete in all respect.
Testing Kit/Aerosol cans for Mutisensor detectors including one set of Fibreglass Telescopic Extension Pole 4.5 metres, Universal Removal Tool, Aerosol Smoke Dispenser, Protective Carrying / Storage Bag
Instrumentation
FIELD INSTRUMENTS complete with cable glands, fittings, accessories and other installation materials etc.,complete as per tender specifications.
Pressure Transmitters with Cable glands Range max (0 to 20 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0 - 60 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Pressure Transmitters with Cable glands Range max (0 - 120 kg/cm2); Smart type; accuracy 0.075% or better Installation: 2" Pipe Mounted
Differential Pressure Transmitter with manifold valves and Cable Glands.Range max (0 to 3 kg/cm2).Smart type; accuracy 0.1% or better
Temperature Transmitter with duplex RTD, Thermowell & Cable glands, Range max (0 to 100 degC ) Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted; RTD in thermowell on process pipe above ground installation.
Temperature Transmitter with surface mounted duplex RTD, Weld pad and dual sensors & Cable glands, Range max (0 to 100 degC); Smart type; accuracy 0.1% or better Installation: Transmitter 2" pipe mounted ; RTD in weldpad welded to process pipe surface for below ground installation.
Temperature Transmitter suitable for sub soil temperature measurement with extended RTD length, cable glands, Range max (0 to 100 degC ), Smart type; accuracy 0.2% or better, Installation: Transmitter 2" pipe mounted ; RTD in underground installation at approximate 2 meter from ground level suitable for below ground installation with required ingress protection level.
Pressure switches with junction box & cable glands suitable for low pressure side, set point 1 Kg/cm2 to 10 Kg/cm2. Proof pressure 200 kg/cm2
Pressure switches with junction box & cable glands suitable for High pressure side, set point 3 Kg/cm2 to 25 Kg/cm2. Proof pressure 200 kg/cm2
Pressure switches with junction box & cable glands suitable for High pressure side, set point 22 Kg/cm2 to 70 Kg/cm2. Proof pressure 200 kg/cm2
Pressure switches with junction box & cable glands suitable for High pressure side, set point 65 Kg/cm2 to 160 Kg/cm2. Proof pressure 200 kg/cm2
Scrapper detector- 6IN, 600 # Series -Short Neck Scrapper Detector Switch- As per Tender Specification
Jacking Bracket for 600# Scrapper Detector
INSTRUMENT FITTINGS
CS Bushing 1" Butt Welded x 1/2" FNPT as per tender specifications
SS Connector 1/2" MNPT x 1/2" OD Tube as per tender specifications
SS Connector 1/2" FNPT x 1/2" OD Tube as per tender specifications
SS Union Tee 3 x 1/2" OD tube as per tender specifications
1/2" OD SS Tube End cap as per tender specifications
SS Two valve manifold 3 x 1/2" FNPT as per tender specifications
Hex nipple (1/2" MNPT x 1/2" MNPT x 80 mm)
SS TUBE 1/2" OD (M) as per tender specifications
CONFIGURATOR AND TEST INSTRUMENTS
Field Configurator for Pressure & Temperature transmitter with Hart protocol as per tender specifications
4 1/2 Digit DMM (True RMS) as per tender specifications
Multifunction Calibrator with rechargable battery, charger, carry case, etc
Pressure Calibrator 0 - 20 bar (Portable), as per tender specifications
Pressure Calibrator 0 - 200 bar (Portable), as per tender specifications
Test Power Supply 0 - 60 V, 10 A 600 Watts, 19" rack mount, sleek 1U type as per tender specifications
Micro processor based Temperature Calibrator; Range ambient to 200 deg C, as per tender specifications
2 SERVICES
Supervison, erection, testing & commissioning of PLC at attended stations, erection and commissioning of PLC , Instruments at Station locations including supervision for termination of control cables, installation and commissioning of SCC systems, UPSs, Console Desks, Network Racks etc., laying of power cables and LAN cables for powering & interfacing the system, interfacing & integration of PLC with SCC machines and field instrumentation systems (including MVWS system) including supplied hardware/ software with station on remote & auto including development of control logics etc making all jobs complete as per drawings / specifications and acceptance of system by Owner. This include supply of all labour, consumables, tools, services rendered etc. The Job also includes configuration at PLC end for interfacing of the PLC system with RTUs for transfering Station data to SCADA System. The job includes interfacing the PLC system with the Marketing PLC for data exchange.
Goindwal Sahib station
Supervison, erection, testing & commissioning of Smoke detectors with Fire supression system in panels.
Station PLC System
UPS System
Deputing Resident Engineer during Installation and commissioning.
Supervision, erection, testing & commissioning of SIL rated LEL controller, including termination of power & signalling cables, wiring of hydrocarbon detectors, including required support for interfacing with PLC system etc making all jobs complete as per drawings / specifications and acceptance of the system by Owner. This includes supply of all labour, consumables, tools,services rendered etc
Erection, testing & commissioning of 2 Loop Fire Alarm & Detection System comprising of addressable Fire Alarm Panel, addressable detectors of various types such as multisensor detectors, rate of rise heat detectors, manual call points, hooters, etc including fire suppression system, testing of the complete system with simulation and also demonstration of working of the complete system,commissioning of the complete system including the cost of all materials, labour, consumables, equipments tools & tackles as per the specifications & instructions of Site Engineer / EIC.
Installation, testing & commissioning of various types of detectors ,laying of signalling cables (through conduit/ clamping on wall etc), clamping / fixing of GI conduit in various building etc for integration of detectors with existing Fire Alarm panel including all mounting accessories for support, junction boxes etc. as per the approved scheme to complete the work in all respects inclusive of supply of all consumables,cost of all materials, labour, painting services etc. as per specifications, drawings, International Standard practices and the directions of Site Engineer/EIC. Job includesinstallation of all types of detectors, material etc
Multi Sensor Detectors & isolators
Rate of Rise Heat Detectors for safe area & hazardous area \ Explosion proof heat detectors for SVs
Response Indicators & Monitor modules
Manual Call Point (for safe area)
Beacons / Hooters / Horn / Strobe (for safe area)
Laying of unarmoured signal cable through GI pipe / wall / tray etc for interfacing of various type of detectors e.g. multi sensor, ROR, response indicator, hooters, beacons etc
Clamping/ fixing of GI pipe on wall/roof/cable trench etc
Training on supplied system including Control system, F&G etc
Submission of as built documentation as per detailed scope of work
3 COMPOSITE
Installation of explosion proof / flame proof junction boxes for marshalling of control / signalling cables, terminating the cables at field and control panel end, mounting the junction boxes, connecting to earthing grid by supplying and installing all the required materials such as supporting structure, cement concrete, painting, GI wire etc.(excluding supply of the Junction Boxes) complete in all respects as per specifications, approved drawings and direction of EIC / Site Engineerincluding all labour, tools, materials, glanding, ferruling etc.complete in all respects.
Installation of Hooter/Beacon in Hazardous area, terminating the cables at field and control panel end, connecting to earthing grid by supplying and installing all the required material such as supporting structure, cement concrete, painting, GI wire etc. complete in all respects as per specifications.
Comprehensive Annual Maintenance Contract for the system (including supplied facilities at all the attended stations, RCP locations, MOV locations) for a period of 05 years after completion of defect liabillity period for the complete pipeline as per tender requirement for all locations.
AMC for 1st Year
AMC for 2nd Year
AMC for 3rd Year
AMC for 4thYear
AMC for 5th Year
Sitra Infotech pvt. Limited
Advanced systek Private Limited
Sitra Infotech pvt. Limited
Advanced systek Private Limited
stage.html
html • 0.04 MB
tech_eval.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .