Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹32.9 LAccepted-AOC R O 218 05 OPP J D A COMPLEX TRIKUTA NAGAR JAMMU J K PIN 180020 | JAMMU | JAMMU AND KASHMIR | 180020 | L1 | Accepted-AOC BEING LOWEST BIDDER | |
| 2 | L2₹44.5 L+₹11.1 L (33.3%)Rejected-Finance | L2 | Rejected-Finance BEING OTHER THAN LOWEST | |
| 3 | Rejected-Technical | - | Rejected-Technical REJECTED DUE TO NO REMARKS IN WLR OF DELHI ZONE LETTER DT 30 AUG 2023 AND JABALPUR ZONE LETTER DT 01 SEP 2023 | |
| 4 | Rejected-Technical | - | Rejected-Technical REJECTED DUE TO NOT ENLISTED IN REQUISITE CATEGORY |
Tender Value
₹38.3 L
EMD Value
₹76,600
Closing Date
30 Oct 2023, 6:00 pmClosed
GE(AF) Leh
GE(AF) Leh PIN - 194101
SPECIAL REPAIR TO INTERNAL AND EXTERNAL ELECTRIC SUPPLY SYSTEM AND ASSOCIATED WORKS AT 114 HU AND OTHER AREAS AT AF STN LEH
2023_MES_615560_2
GE (AF)/LEH/T-52/2023-24
Open Tender
Electrical and Maintenance Works
Item Wise
180 days
GE(AF) Leh
Please refer Tender documents.
8 documents required · 8 mandatory
₹500
GE(AF) Leh
₹76,600
Yes
3 Jan 2024
7 Oct 2023
2 Nov 2023
7 Oct 2023
30 Oct 2023
16 Oct 2023
Amount
Taking down carefully copper/Aluminium point wiring (Light,fan,socket or power) complete including fitting such as switches, socket, bell pushes, ceiling roses, pendants/batten holder, call bell, regulators etc all as specified and directed by Engr-in-charge.
M&L for point wiring for one light point controlled by one switch one way in & including PVC conduit or casing and capping as per site requirement using FRLS PVC unsheathed multistrand copper conductor cable 1.5 sqmm single core for one light/fan point/bell point controlled by one switch including 3 mm thick plastic laminated sheet cover over PVC / wooden Box for earth continuity insulated PVC unsheathed(green colour) 1.5 sqmm copper earth wire connected to common earth dolly using and making good to distrubed surfaces of wall/floor including matching the existing colour complete all as specified and directed by Engr-in-charge. Note : (a) wiring shall be done by using proper colour coding.
All as per srl item No. 02 here-in-before but for 05 Amp socket outlet on indendent board complete all as specified.
All as per srl item No. 02 here-in-before but for 05 Amp socket outlet on same board complete all as specified.
All as per srl item No. 02 here-in-before but for 15 Amp independent socket outlet using 2.5 sqmm ingle core wire complete all as specified.
S&F Socket outlet 2-in-1 3 pin 6 Amps flush type 230 volts complete all as specified.
S&F Switch piano, flush type 5 Amps One Way 230 volts complete all as specified.
S&F Socket outlet 2-in-1 3 pin 5 & 15 Amps flush type 230 volts complete all as specified.
S&F Switch one way 15 Amps flush type 230 volts complete all as specified.
S&F Ceiling rose 3 terminal size 50x65mm surface type 230 volts complete all as specified.
S&F Holder insulated body with back plate for batten fitting suitable for LED lamp complete all as specified and directed by Engineer-in-Charge.
S&F Crystal glass LED tube light of 18W T8 , 4ft. (double side connection with LED driver) with very high efficacy suited for installation in existing tubelight G13 lamp holders to give glare free light complete all as directed by Engr-In-charge.
S&F universal Regal batten for LED tube Double side connection Complete 1x22 Watt.
M&L for sub main wiring with two run (for Phase & Neutral) of 4.0 Sqmm FRLS PVC sheathed, copper conductor cable, 1100 Volt, and one run of copper earth wire 4.0 sqmm drawn through & including PVC casing caping/ PVC Conduit whichever suitable at site, complete all as specified. Note: Copper conductor two run and one run of copper earth wire along with casing caping/ conduit shall be measured as one length. Make : Polycab/Finolex/Havells/Kalinga
M&L for sub main wiring with two run (for Phase & Neutral) of 4.0 Sqmm FRLS PVC sheathed, copper conductor cable, 1100 Volt, and one run of copper earth wire 4.0 sqmm drawn through & including steel Conduit with all conduit fittings complete all as specified. Note: Copper conductor two run and one run of copper earth wire along with casing caping/ conduit shall be measured as one length. Make : Polycab/Finolex/Havells/Kalinga
S&F 63 Amp TPN/FP, 440 V, 50 Hz, 3P+N+E Plug and socket of metal enclosure all as specified and directed by Engr-in-charge.
S&F single pole and neutral enclosure with two pin and earth plug and socket complete with on single pole MCB 20 Amp complete all as specified and directed by Engineer-in-charge.
Supply & Fixing in replacement of new generation energy saving and environmental friendly long life 120 watt LED flood light fitting made up of pressure die cast aluminium housing with high power LED as lighting source with 100 lumens/watt colour ,temperature 5700-6500K and lens embedded PC cover having top opening separate driver compartment with IP 66 protection and impact resistance of IK07 with 10 KV built in surge protection device as light source complete all as specified & directed.
S&F Sheet metal enclosure double door for DB's SPN 8 way 240 V having 200 A rated bus bar complete all as specified and directed by Engr-Incharge.
S&F Sheet metal enclosure double door for DB's SPN 4 way 240 V having 200 A rated bus bar complete all as specified and directed by Engr-Incharge.
S&F Sheet metal enclosure single door for DB's SPN 4 way 240 V having 200 A rated bus bar complete all as specified and directed by Engr-Incharge.
Material labour and labour for elapp brass copper lightning arrestor 9.2mm diameter and 915 mm in in legth and Elapp epoxy electrical insulator (red) screwed properly on copper strip complete all as specified and directed.
Material and labour for copper strip of 20mm x 3.0mm with screws/ washers etc. over epoxy insulator/PVC saddles/spacers on wall and roof of building complete all as specified and as directed by Engr-in-Charge. Note : Max distance between spacers/saddles is 0.5 mtr
Material and labour for test point terminal block made out of gun metal or phosphorus bronze size 75 x 75 x 25mm drilled and screwed including 3 Nos 8mm dia 25 mm long hax. head screw complete all as specified and as directed by Engr-in-Charge.
Taking down carefully and shifting of LT panel complete outside building/hanger after carefully disconnecting the electric supply and cables for re-use complete all as specified and as directed by Engr-in-Charge.
Taking down carefully and shifting of voltage stabilizer complete in new elect panel room after carefully disconnecting the electric cables for re-use complete all as specified and as directed by Engr-in-Charge.
Taking down carefully and shifting of Sub Main wiring/LT cables in new elect panel room after carefully disconnecting the electric supply for re-use complete all as specified and as directed by Engr-in-Charge.
S&F MCB SP 32 Amps - 10KA 240 Volts all as specified and as directed by Engineer-in-charge.
S&F MCB SPN 32 Amps - 10KA 240 Volts all as specified and as directed by Engineer-in-charge.
Supply only MCB 63 Amp TPN 415 volts 50 Hz 25 KA, complete with all accessories as required on site & as directed by engineer-in-charge.
Supply and fixing factory made sheet metal enclosure DB VTPN 415V 8 way double door with 200 Amp rated copper bus bar IP-42 sheet steel enclosure horizontal type along with suitable size copper PVC cable sheathed cable for earth continuity and suitable for having 250 Amp MCCB as incomer and MCBs as outgoing complete all as specified and directed by Engr-in-charge. Make : C&S/Standard/Havells/L&T
Supply and fixing factory made sheet metal enclosure DB VTPN 415V 4 way double door with 200 Amp rated copper bus bar IP-42 sheet steel enclosure horizontal type along with suitable size copper PVC cable sheathed cable for earth continuity and suitable for having 250 Amp MCCB as incomer and MCBs as outgoing complete all as specified and directed by Engr-in-charge. Make : C&S/Standard/Havells/L&T
Material and labour for point wiring in steel conduit unsheathed multistrand copper conductor cable of 1.5 sqmm single core FRLS for one light/fan point controlled by one flame proof switch including continuouse earth continuity copper earth wire of same size connected to common earth dollycomplete all as specified and directed by Engr-in-charge. Note : (a) wiring shall be done by using proper colour coding.
All as per item No 33 here-in-above but using 2.5 sqmm wire for 15 Amps flame proof socket
S&F LED flameproof light fitting 1 x 20 Watts, CIMFR approved and recommended for gas/vapor group of IIA & IIB, Zone 1 & 2 and IP65 protection with die cast aluminium housing with heat resistant toughned glass with LED tube light fixtures, driver, holder, connector etc. complete with all accessories pre-wired and including connecting up with three core flexible copper conductor wire of suitable size complete all as specified and as directed by Engr-in-Charge.
S&F flame proof switch socket & plug combination in LM6 cable termination box in LM6, 16 Amps, 250 volts, 2P + earth. Make : Sudhir Switchgears or equivalent
S&F flameproof exhaust fan of size 450mm sweep including lowers with IP-66 protection, complete with all accessories pre-wired and connecting up with twin core twisted flexible copper conductor wire of suitable size complete all as specified and as directed by Engr-in-Charge.
S&F Switch flame proof rotary type with termination box in LM6, 16 Amps, single pole 250 volts. Make : Sudhir Switchgears or equivalent
S&F Ceiling rose 3 terminal size 50x65mm surface type 230 volts.
S&F Flame proof SPN DB 8 way 240 V having 200 A rated bus bars with 32 Amps SPN MCB-01 No and 16-32 Amps SP MCB's - 06 Nos complete all as specified and directed by Engr-In-charge. Make : Sudhir Switchgears or equivalent.
Material & labour for cutting openings, through brick/stone walls built in cement mortar for exhaust fans of 300mm sweep and other openings, including providing, fixing and removing shoring, cleaning and stacking bricks, removing surplus serviceable bricks, hard-core etc. to store and rubbish not exc. 50m, including forming jambs in CM 1:4 and making good to match existing wall finishes, complete all as specified and as directed.
Excavation, in trenches not exceeding 1.5 mtr wide and not exc 1.5 mtr in depth for laying under ground cable in soft/llose soil and getting out complete all as specified & directed by Engineer-in-Charge.
Returning, filling in, including spreading, leveling watering and well ramming in layers not exc 25 cm thick all as specified & directed by Engineer-in-Charge..
Removal of surplus excavated material to a distance not exc 50 mtr and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed by Engineer-in-Charge.
Sand cushioning to under ground cable with dry sand locally available 8cm thick before laying the cable and 15 cm above the cable, stretching and testing of cable complete all as specified & directed by Engineer-in-Charge.
Supply & laying un-reinforced pre cast concrete cable covers class LV, type-1, flat, of size 250mm x 150 mm x 40mm all as specified & directed by Engineer-in-Charge.
M&L for cutting existing road / PCC hard standing / pavement / drain for taking out / laying of underground cable and including necessary earth work and making good to match with the existing surface with PCC 1:2:4 type C1 using 20mm graded aggregates complete all as specified
Supply and lay in replacement LT UG cable PVC insulated screened PVC bedded, galvanized steel strip of wire armoured, electric power cables (heavy duty) 1100 volts grade with stranded aluminium conductor of 70 sqmm x 3.5 core all as per specified & as directed by Engineer-in-charge. Make : Grandly / Havells / Kalinga.
All asper srl item No.48 here-in-befor but of size 16 sqmm x 4 core.
All asper srl item No.48 here-in-befor but of size 16 sqmm x 2 core.
Supply and fix cable jointing kit for 1.1 KV grade cable for indoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3.5 core XLPE, armoured, Al conductor cable of size 70 Sqmm
S&F in replacement of 40 mm Steel tubing light grade galvanised laid in trench or fixed to wall for cable protection, complete all as specified & as directed by Engineer-in-charge.
Material and labour for replacement of LT distribution panel, made out of 3.15 mm thick MS sheet, powder coated, dust & vermin proof, IP-66 Protection, Outdoor type factory made cubical totally enclosed type with front and rear door opening as per engineering practice provided with locking arrangement for opening of panel with provision of seperate chamber in upper part to enclose Aluminium busbar of cap 600 Amps on epoxy insulators in horizontal position with min 20cm distance between busbars & panel body and 08 Nos separate chambers of adequate size embedded in 40mm thick PCC 1:2:4 type B-1 (using 20mm graded aggregate), on angle iron of size 40x40x6mm with footing 30 cm clear space between bottom of panel and flooring including all accessories prewired with insulated copper wires of suitable size. The panel shall compromise of the following fittings and fixture :- (Location at Technical power house supply feeding from New power house for distribution)
(a) MCCB 320 Amps, 35 KA 4 pole with adjustable thermal and adjustable magnetic settings - 01 No (incoming)
(b) MCCB 125 Amps, 35 KA , 4 pole with adjustable thermal and adjustable magnetic settings – 02 Nos
(c) MCCB 250 Amps, 25KA , 4 pole with adjustable thermal and adjustable magnetic settings – 02 Nos
(d) MCCB 160 Amps, 25KA , 4 pole with adjustable thermal and adjustable magnetic settings – 02 Nos
(e) MCCB 63 Amps, 16KA ,4 pole with adjustable thermal and adjustable magnetic settings – 02 Nos
(f) Double pole MCB 63 Amps – 02 Nos
(g) Indicating lamps Led type (RYB).
(h) Mutifunction digital meter with CTs & PTs of suitable size & Type idicating Volts, Amperes, PF, kW, kVA including energy meter - 01 No.
(j) Control wiring complete with suitable size of copper cable PVC insulated and connection between busbar and MCCB & Changeover is with suitable size of Aluminium strip only.
(k) Civil work including PCC for fixing of panel and other work as directed by Engr-in-Charge.
Note: Aluminium busbar in all panels should be colour coding RYB.
Material and labour for replacement of LT distribution panel, made out of 3.15 mm thick MS sheet, powder coated, dust & vermin proof, IP-66 Protection, Outdoor type factory made cubical totally enclosed type with front and rear door opening as per engineering practice provided with locking arrangement for opening of panel with provision of seperate chamber in upper part to enclose Aluminium busbar of cap 400 Amps on epoxy insulators in horizontal position and stepped manner with with min 20cm distance between busbars & panel body and 06 Nos separate chambers of adequate size embedded in 40mm thick PCC 1:2:4 type B-1 (using 20mm graded aggregate), on angle iron of size 40x40x6mm with footing 30 cm clear space between bottom of panel and flooring including all accessories prewired with insulated copper wires of suitable size. The panel shall compromise of the following fittings and fixture :- (Location at Technical power house supply feeding from New power house for distribution)
(a) MCCB 250 Amps, 35 KA 4 pole with adjustable thermal and adjustable magnetic settings - 01 No (incoming)
(b) MCCB 100 Amps, 16 KA , 4 pole – 02 Nos
(c) MCCB 63 Amps, 16KA , 4 pole – 03 Nos
(d) Double pole MCB 63 Amps – 02 Nos
(e) Indicating lamps Led type (RYB).
(f) Mutifunction digital meter with CTs & PTs of suitable size & Type idicating Volts, Amperes, PF, kW, kVA including energy meter - 01 No.
(g) Control wiring complete with suitable size of copper cable PVC insulated and connection between busbar and MCCB & Changeover is with suitable size of Aluminium strip only.
(h) Civil work including PCC for fixing of panel and other work as directed by Engr-in-Charge.
Note: Aluminium busbar in all panels should be colour coding RYB.
S&F weather proof outdoor bus bar chamber, made out of 3.15mm thick MS sheet with front & rear Opening, powder coated, dust & vermin proof, IP-66 Protection comprising 4 Nos aluminium strips each of 200 Amps, 80cm long having 10cm min distance from the body and between bus bars, fixed in steped way duly insulated mounted on epoxy insulators in horizontal position in stepped manner with 4 No’s mounting legs made out of 40mm x 40mm x 6mm angle iron grouted in PCC block (30cm depth below ground level and 60cm above ground level) in cement concrete 1:3:6, type C-2 (using 40mm grade crushed stone aggregate), and one MCCB of 125 Amps, 16 KA as incomer connected with bus bars by means of suitable size of aluminium thimbles, nuts, bolts & washers including cable glands at entry and outlet points including excavation and earth work, returning filling and removal of surplus soils complete all as specified and directed by Engr-in-charge.
Earthing with galvanized steel earth plate electrode 600 x 600 x 6mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with tope edge of the plate not less than 1.5mtr below normal ground level, connected to galvanized earth strip 32 x 6mm as earthing lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel besides earth work GI pipe light grade 40mm bore for protection of GI strip from earth electrod to earth dolly supplying and laying charcoal dust common salt PCC 1:2:4 type B-1 chamber and RCC copver 40mm thick (1:2:4) type B-1 using 20mm graded stone aggtregate reinforcedwith 8mm die TMT bars @ 100mm C/C both ways with MS handle 12mm dia PGI funnel and wire mesh 20mm dia GI pipe light grade for watering all as shown in electrical plate No 3 and connected to earthing test point including testing complete all as specified and directed.
Earthing with galvanized steel earth plate electrode 600 x 600 x 6mm thick, buried directly in ground (earth pit not less than 2.25 mtrs deep below ground level) with tope edge of the plate not less than 1.5mtr below normal ground level, connected and including GI wire 4mm dia (upto the body equipment) by means of bolts, nuts, check nuts and washers of galvanized iron or steel besides earth work GI pipe light grade 40mm bore for protection of GI strip from earth electrod to earth dolly supplying and laying charcoal dust common salt PCC 1:2:4 type B-1 chamber and RCC copver 40mm thick (1:2:4) type B-1 using 20mm graded stone aggtregate reinforcedwith 8mm die TMT bars @ 100mm C/C both ways with MS handle 12mm dia PGI funnel and wire mesh 20mm dia GI pipe light grade for watering all as shown in electrical plate No 3 and connected to earthing test point including testing complete all as specified and directed.
Material and labour for maintenance free chemical earthing system complete with one No UL 464 approvrd copper bonded earth rod 17mm dia, 3.0 Mtr long electrode burried in ground to bore of 150mm dia , Vertically to a depth not less than 0.5 Mtr below normal ground level including provision to connect the earth continuity conductor with copper bonded earth rod as per manufacturer design or all as directed including 60 Kg NABLLAB certified back fill chemical compound for filling bore holes with Min 6.0 Kg of Hygroscopic Gel. The ground enhancement chemical may be used in place of back fill compound as required and manufacturer recommendation to obtain 1.0 Ohms earth resistance value. A layer of 250-300 mm soil ( Vegitable / Cotton soil) is also required out side earth bore including necessary ingredients and water during process to obtain desired value . The earthing copper strip of 20x3.0 mm up to length 7.5 Mtr upto test point from copper rod is also included. The scope included iron frame of size 20x20 mm fixed with hinged with pit cover of 300 x300 mm made of cast iron as per company standarad shall be as recommanded by manufacturer complete all as specified : Make;- JMV / Pargati electrocom / Enove/Marconite Note:- (i) Payment shall be made only after satisfactory testing to the entire satisfaction of GE. The contractor has made alternate earthing in case test result not found satisfactorywithout extra cost to the Govt quoted rates shall be deemed to included. (ii) Contractor shall submit one year guarantee for earth resistance below 2.0 Ohms and raeth neutral voltage less than that 2.0 volts.
Note : Schedule of credit for to be deducted on acceptances of bid.
AJ. Owners
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .