Facilities Management Division, Bangalore
HINDUSTAN AERONAUTICS LIMITED Facilities Management Division, Bangalore
Electrical works for dedication 125KVA DG and 40KVA UPS for Data Center ARDC
6925
FM/NE-P/Advt./31/23-24 Dt:16.03.2024
Works
Electrical Planning and Contract Section-E and M Dept-FMD-Bangalore
₹0
₹37,340
27 Apr 2024
28 Mar 2024
28 Mar 2024
27 Apr 2024
Name of the Individual / Firm / Company: * Mandatory
Type of ownership
Details of Constitution or Legal Status such as certificate of incorporation, shops and establishments, etc.,
Address for correspondence:
Bank(s) details: [Copy of the cheque leaf to be uploaded]
Related Document to be Uploaded to eProcurement Portal (Note Cancelled cheque leaf to be uploaded)
PAN No.:
Average annual financial turn over during the last 3 years, ending 31st March of the previous financial year [ should not be less than 30% of Amount put to tender]
TURN OVER IN Rs:
Please Enter Turn over in Rupees for all the 3 years
Details of Registered Contractor
ESI No.:
GST Detail:
Please Enter GST Details
Related Document to be uploaded in ePortal
Contact details
Please Enter Contact person Name
Please Enter Mobile No
Valid Electrical contractor licence of appropriate voltage issued by any state Govt. under clause 45 of Indian Electricity Rules 1956 and as amended from time to time or to declare engage an electrical contractor who has the above mentioned licence and requisite experience.
Latest Bankers Solvency Certificate from Nationalized/ scheduled Bank issued within a period 12 months from the final date of submission of tender.
Please Enter Details to 'Name of the Bank' , 'Date of Issue','Value in C89``Rs. in Lakhs
Experience of having successfully completed similar works during last 7 years ending on the previous day of submission of tender should be either of the following: [Work completion certificates along with LOA/PO/WO should be uploaded] (i) THREE similar completed works each costing not less than the amount equal to 40% of the estimated amount put to tender. (ii) TWO similar completed works each costing not less than the amount equal to 50% of the estimated amount put to tender. (iii) ONE similar completed work costing not less than the amount equal to 80% of the estimated amount put to tender.
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No II
work done
Type of Work: [Incase of private works the same shall be supported with TDS certificate]
Please Enter Details for Work No III
Details of person holding the power of Attorney :
Related Document to be Uploaded to eProcurement Portal
Please Enter Details for Person holding Power of Attorney
DECLARATION I
Please Accept the Declaration I
DECLARATION II
Please Accept the Declaration II
The payment terms shall be governed as per the terms indicated in special conditions of contract.
Basic Rate to be quoted for each item. Subject work is called on works contract basis and prevailing GST of 18% has been added in the BOQ on overall total. Any revision on this GST rate is to HAL account.
Sucessful offer that is L-1 (Lowest offer) will be determined including GST.
The tenderers are requested to abide by the rules of prevailing GST act.
This BOQ specification has to be read in conjunction with technical specifications and tender drawings. Any ambiguty in these have to be brought to the knowledge of contract section before submission of tender to avoid future claims/dispute.
Specification of item
LT PANEL-1
Incomer
1No- 250A, 415V gr. 50KA 4P MCCB. Thermal Magnetic based
Lot - 300A TP + 150A N, 415V, short circuit rated 36KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1Nos- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
1 Set-250/5A current transformers of suitable class and VA burden for metering.
1No 32 A 415V gr TP 36KA MPCB of for tapping power for metering and control circuit
1Set - RYB indicating lamps of LED module with 6A, 230V,10KA, SP MCB.
1Set- 6A, 230V, 10KA SP MCB for the protection of measuring instruments.
Outgoings
1 No - 160A 415V gr. 36KA TP+NL MCCB Thermal Magnetic based with O/L, S/C Releases.
2 Nos - 125A 415V gr. 36KA TP+NL MCCB Thermal Magnetic based with O/L, S/C Releases.
1 No - 32A 415V gr. 25KA TP+NL MCCB Thermal Magnetic based with O/L, S/C Releases.
Supply, installation, testing & commissioning of Following Change over Switch-Disconnector LT Panel (PTA)
Incomer
1No- 4Pole, 250A,415V 3 position manually operated changeover Switch-Disconnector including all accessories and ON/OFF indications front operating handle, etc.complete in all respects.
Lot - 300A TP + 150A N, 415V, short circuit rated 36KA for 1sec, Aluminium bus bars with busbar insulators, heat shrinkable PVC sleeves etc.
1Nos- Multi function meter (MFM/MDM) suitable for 3ph, 4 wire, 240V(L-N), 5A, CL-1, RS 485 Port Digital MFM/MDM of EM6400NG of Schneider or any equivalent make meeting technical specification of above MFM complete in all respect.
1 Set-250/5A current transformers of suitable class and VA burden for metering.
1No 32 A 415V gr TP 36KA MPCB of for tapping power for metering and control circuit
1Set - RYB indicating lamps of LED module with 6A, 230V,10KA, SP MCB.
1Set- 6A, 230V, 10KA SP MCB for the protection of measuring instruments.
Outgoings
4 Nos - 63A 415V gr. 25KA TP+NL MCCB Thermal Magnetic based with O/L, S/C Releases.
3 Nos - 32A 415V gr. 25KA TP+NL MCCB Thermal Magnetic based with O/L, S/C Releases.
6Nos - 32A, 230V gr. 10KA breaking capacity, DP MCB
Supply, fixing on wall/grouting to floor up to a height of 1200mm above ground level as per site requirement including supply & fabrication of suitable MS angle iron frame work finished with two coats of enamel spray paint over a good primer, testing and commissioning of the 125A,4 pole 415V Switch disconnector fuse unit with equal rating DIN type HRC fuses, front operating handle, etc., enclosed in factory built powder coated sheet steel enclosure, including suitable cable end boxes(incoming/outgoing sides) wherever necessary complete in all respects and as directed by Engineer-in charge.
Supply, fixing, testing & commissioning of the following factory built powder coated Double door VTPN MCCB DB of any approved make fabricated out of M.S. sheet steel enclosure & necessary cut-outs for operating the MCCB/MCB knobs & comprising of suitable rating tinned copper busbars & earthing bus with tapped holes including internal wiring with stranded copper PVC wires or suitable size copper strips etc. & fixing the DB in flush with wall/ on wall as per site requirement with necessary M.S. angle supports, chipping the wall and replastering to smooth finish etc., wherever required as per site condition, complete in all respects, as directed by Engineer-in-charge and comprising the following as detailed below:
4 way (4+12) Double door VTPN MCCB DB
Supply and Fixing of 125 A MCCB, 4 pole 36kA ,415v TM based Incomer
Supply and Fixing of Outgoing 63A 3 pole MCB,415V 10kA breaking capacity
Supply & laying in the already excavated cable trench/cable tray/fixing on wall/duct wall with necessary M.S clamps / encasing in HDPE pipes etc., testing & commissioning after laying of following size XLPE insulated Aluminium (Al) /Copper (Cu) conductor 1100V gr., earthed Armoured (Arm) U.G cables as directed and as per technical specification and as detailed below. (Note:- Excavation, sand & Brick Protection, concrete cutting, reconcreting, casing pipes will be measured separately.)
3.5 CX70 Sqmm Aluminium armoured conductor
3.5 CX120 Sqmm Aluminium armoured conductor
3.5 C X 50 Sqmm Aluminium armoured conductor
4 CX16 Sqmm Aluminium armoured conductor
Supply and laying of 90mm dia, PN10 HDPE pipe of confirming to IS 4984:19955 in the excavated trench/duct/at road crossings or on wall with suitable clamp for encasing cables complete in all respect as directed by Engineer-in-charge.
Laying of one number of XLPE power cable of 1.1KV grade of 3.5CX120Sqmm size direct in ground/encasing in HDPE pipes etc. including excavation and refilling the trench excluding sand cushioning and protective covering as per CPWD specification required and complete in all respect as directed by Engineer-in-charge.
Laying and fixing of one number of XLPE power cable of 1.1KV grade of 3.5CX120Sqmm size on wall surface (clamped with 25/40x3mm MS Flat Clamp) as per CPWD specification required and complete in all respect as directed by Engineer-in-charge.
Laying and fixing of one number of XLPE power cable of 1.1KV grade of 3.5cX70 Sqmm size Cable and on existing cable tray (clamped with 25x3mm MS Flat Clamp) as per CPWD specification and as required and complete in all respect as directed by Engineer-in-charge.
Laying and fixing of one number of XLPE power cable of 1.1KV grade of 3.5cX50 Sqmm size Cable and on existing cable tray (clamped with 25x3mm MS Flat Clamp) as required and complete in all respect as per CPWD specification and as directed by Engineer-in-charge.
Laying and fixing of one number of XLPE power cable of 1.1KV grade of 4CX16 Sqmm size Cable and on existing cable tray (clamped with 1mm thick saddle) as required and complete in all respect as per CPWD specification directed by Engineer-in-charge.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as per CPWD specification and as required:
3.5C x 120 Sqmm. Al Armoured LT cable.
3.5C x 70 Sqmm. Al Armoured LT cable.
3.5C x 50 Sqmm. Al Armoured LT cable.
4C x 25 Sqmm. Al Armoured LT cable.
4C x 16 Sqmm. Al Armoured LT cable.
Supplying and installing of 150mm width x 50mm depth x 1.6mm thickness size perforated painted with powder coating MS Cable trays with perforation not more than 17.5% in convenient sections, joined with connectors, suspended from the ceiling with MS suspenders including suspenders, bolts & nuts,painting suspenders etc as required and complete in all respect as per CPWD specification and as directed by Engineer-in-charge.
Supply and grouting in soil cement concrete cable route markers of size 100mmx100mm at top, 250x250mm at bottom and 600mm in height constructed using 6mm size TMT rod and 1:2:4 cement concrete including facework. "LT CABLE" should be engraved on two opposite sides and painted with red enamel paint with yellow as background colour. The cable route marker shall be installed 200mm below ground level using 1:2:4 cement concrete all around the cable marker and as directed by by Engineer-in-charge.
EARTHING
Supply, providing and fixing Cast Iron Pipe earth station confirming to IS 3043 complete with 2750mm long, 100 mm Inner Dia(ID),13mm thickness CI Pipe, with 2 part clamp made out of GI flat 50x6 mm continuously welded around the pipe using cast iron welding electrodes as per drawing. The cost also incudes excavation for earth pit, providing & laying homogenous mixture of charcoal lumps, salt & sand all around the pipe as per specification, supplying and fixing of RCC Collar of size 450 mm dia, 450 mm height and 50 mm thick over Cement concrete base of minimum size 150mm width & 100mm thick all around below collar shall be provided using 1:2:6 CC after necessary excavation, refilling of soil, consolidating, ramming, leveling of soil etc., supplying & fixing the label board (MS Plate of size 300mmx200mmX2mm) welding to the electrode complete as per specification, standard drawing, instructions of EIC.
Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick confirming to IS 3043 complete including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as per CPWD specification and as directed by Engineer-in-charge.
Providing and fixing 25mmX5mm Copper Strip on surface or in recess for connections etc as per CPWD specification and as directed by Engineer-in-charge.
Supplying & laying 25 mm X 5 mm GI strip on surface or in recess for connections etc as required and as per CPWD specification and as directed by Engineer-in-charge.
20 mm cement plaster of mix (1:4 (1 cement: 4 fine sand) on fair faces of the above Brick masonry including curing as per CPWD specification and as directed by Engineer In Charge.
DISMANTLING OLD PANELS
Disconnecting & Dismantling of LT Panel at NAC Centre, First Floor (Qty:01 No.) - With 100A SFU Incomer (3.5C X 50Sqmm incoming cable) and 4 Nos of 63A Outgoing SFU and shifting the removed items to scrap yard with in 1 KM distance ,ARDC as-is-basis without any damage and handing over the same to the Engineer-in-charge at Plant Maintenance office main factory, ARDC Division including loading, transportation, unloading etc., complete in all respects. The scope also includes disconnecting the existing cables from panel, complete in all respects and as directed by the engineer-in-charge.
Disconnecting & Dismantling of Bus Bar Box in FM Hall (Qty:01 No of Size 38"X34") and Wall Mounted 200A TPN SFU Box including Switchgear of 200A (Qty:01 No) in Data Centre along Horizontal TPN DBs with 63A incomer (Approx. Qty:02 Nos,) and shifting the removed items to scrap yard with in 1 KM at ARDC Division including loading, transportation, unloading etc., complete in all respects. The scope also includes disconnecting the existing cables from panel, complete in all respects and as directed by the engineer-in-charge.
Demolishing cement concrete manually /by mechanical means including removing debris from the work site and taking out of the division and depositing in the place as per CPWD specification and as directed by the Engineer-in-charge.
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
raw.json
RAW_JSON
PQfreeviewEC2923.pdf
TENDER_DOCUMENT • 0.21 MB
TenderNoticeEC2923.pdf
TENDER_DOCUMENT • 0.45 MB
TechnicalBidEC2923.pdf
TENDER_DOCUMENT • 2.73 MB
SLD1.pdf
TENDER_DOCUMENT • 0.25 MB
Electricallayout1.pdf
TENDER_DOCUMENT • 0.18 MB
SLD2.pdf
TENDER_DOCUMENT • 0.45 MB
PBfreeviewEC2923.pdf
TENDER_DOCUMENT • 0.31 MB
Corrigendumno1.pdf
TENDER_DOCUMENT • 0.08 MB
Electricallayout2.pdf
TENDER_DOCUMENT • 0.26 MB
ECSFormatEC2923.pdf
TENDER_DOCUMENT • 0.17 MB
UndertakingletterEC2923.pdf
TENDER_DOCUMENT • 0.26 MB
ChecklistEC2923.pdf
TENDER_DOCUMENT • 0.15 MB
PQEC2923.xls
TENDER_DOCUMENT • 0.25 MB
PriceBidEC2923.xls
TENDER_DOCUMENT • 0.77 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .