Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹24.0 LAccepted-AOC 306 KHEWAT NO 7 VILL HARIPUR TEH DISTT GURDASPUR PUNJAB 143531 | GURDASPUR | GURDASPUR | PUNJAB | 143531 | ₹24.0 L Quoted ₹25.5 L | L1 | Accepted-AOC Lowest |
| 2 | L2₹26.1 L+₹58,600 (2.30%)Rejected-Finance 29 MODEL TOWN BEHIND GURUDWARA PATHANKOT | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹26.1 L+₹58,600 (2.30%) | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹27.9 L+₹2.4 L (9.47%)Rejected-Finance | ₹27.9 L+₹2.4 L (9.47%) | L3 | Rejected-Finance Other than lowest |
| 4 | L4₹30.1 L+₹4.6 L (18.0%)Rejected-Finance 99 MODEL TOWN PATHANKOT 145001 | PATHANKOT | PATHANKOT | PUNJAB | 145001 | ₹30.1 L+₹4.6 L (18.0%) | L4 | Rejected-Finance Other than lowest |
| 5 | L5₹30.4 L+₹5.0 L (19.5%)Rejected-Finance SCHEME NO 07 BLOCK NO 22 FLAT NO 03 NEW GURDASPUR DISTT GURDASPUR PB 143521 | GURDASPUR | PUNJAB | 143521 | ₹30.4 L+₹5.0 L (19.5%) | L5 | Rejected-Finance Other than lowest |
Tender Value
₹48 L
EMD Value
₹96,000
Closing Date
4 Jun 2025, 6:00 pmClosed
Garrison Engineer, Gurdaspur.
Garrison Engineer, Gurdaspur (Tibri)
Certain repair/ replacement of internal electrification including rewiring at outstation area and Central Amenities at Tibri Mil Stn under GE Gurdaspur.
2025_MES_705956_1
GE GSR-19/2025-2026
Open Tender
Electrical and Maintenance Works
Item Rate
210 days
Garison Engineer
As per Tender Documents
8 documents required · 8 mandatory
₹500
GE Gurdaspur
₹96,000
25 Jul 2025
30 Apr 2025
11 Jun 2025
30 Apr 2025
4 Jun 2025
22 May 2025
Amount
Taking down carefully unserviceable point wiring of any description/ type/ size of light/ fan / tube/ power / two way/ bell etc. on TW batten/ conduit/casing caping including removal of batten/ conduit/ casing caping/ gutties/ wooden boards/ switches/ sockets/ regulators/ holders/ ceiling roses/ call bells/ etc and making good the disturbed surfaces of wall/ ceiling so as to match with the existing finishes complete all as directed.
M&L for point wiring with PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) using approved colour coding, 1100 volts grade, ISI marked, including PVC conduit heavy grade, 20 mm or higher dia. with fittings concealed in wall/ on surface for ceiling with continuous earth wire of PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) 1100 volts grade, ISI marked and connecting to the common earth dolly including provn of 3mm thick plastic laminated sheet of appropriate size and sunken CI/pressed steel terminal boxes for mounting switches, sockets and regulators etc. including cutting chases and making good to the disturbed surfaces finished as per existing for One light point/fan point/ bell point controlled by one, one way switch complete all as specified and directed.
All as per Srl item No 2 here-in-before but in existing PVC conduit.
All as per Srl item No 2 here-in-before but for one 5 pin socket outlet 5 Amp on independent board.
All as per Srl item No 4 here-in-before but in existing PVC conduit.
All as per item Srl No 2 here-in-before but for one 5 pin socket outlet, 5 amps on the same board with other switch.
All as per Srl item No 2 here-in-before but for one light point controlled by two, 2 way switches.
All as per serial item No. 02 here-in-before but with PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 2.5 Sqmm (nominal area), using approved colour coding, 1100 Volt grade ISI marked including PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 2.5 Sqmm (nominal area) 1100 Volt grade ISI marked as earth continuity conductor and connecting to the common earth dolly for 3 pin 15/16 Amps socket outlet on independent board.
All as per item Srl No 8.00 here-in-before but in existing PVC conduit.
M&L for point wiring with PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) using approved colour coding, 1100 volts grade, ISI marked, including PVC conduit heavy grade, 20 mm or higher dia. with fittings concealed in wall/ on surface for ceiling with continuous earth wire of PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 1.5 Sqmm (nominal area) 1100 volts grade, ISI marked and connecting to the common earth dolly including sunken factory made 16 SWG thick pressed steel terminal box of suitable size covered with and including modular white cover plate with inner frame suitable for housing modular switches, sockets, regulators etc. including cutting chases and making good to the disturbed surfaces as per existing for One light point/fan point/ bell point controlled by one, one way switch complete all as specified and directed.
All as per Srl item No 10 here-in-before but in existing PVC conduit.
All as per Srl item No 10 here -in -before but for one 5 pin socket outlet 5 Amp on independent board
All as per Srl item No 12 here-in-before but in existing PVC conduit.
All as per item Srl No 10 here-in-before but for one 5 pin socket outlet, 5 amps on the same board with other switch.
All as per serial item No. 10 here-in-before but with PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 2.5 Sqmm (nominal area), using approved colour coding, 1100 Volt grade ISI marked including PVC insulated and PVC unsheathed single core multistranded FRLSH copper conductor cable of size 2.5 Sqmm (nominal area) 1100 Volt grade ISI marked as earth continuity conductor and connecting to the common earth dolly for 3 pin 15/16 Amps socket outlet on independent board.
All as per item Srl No 15 here-in-before but in existing PVC conduit.
M&L for sub main wiring with two runs of single core multi stranded PVC insulated, copper conductor, grade 1100 Volt , FRLSH cable of size 6 sqmm including 6 sqmm multistranded copper conductor FRLSH cable PVC insulated for earthing duly connected with earth dolly, with approved colour coding including PVC conduit heavy grade, of appropriate dia. concealed in wall with accessories including cutting chases and making good to the disturbed surfaces as per existing and taking down old unserviceable wiring complete all as specified and directed. (Note :- Three run of cable alongwith PVC conduit together shall be measured as single run).
S&F switch piano flush type single pole one way 6 amps complete all as specified and directed.
S&F socket outlet 3 pin 6 amp flush type complete all as specified and directed.
S&F switch piano flush type 16 Amp single pole one way complete all as specified and directed.
S&F socket outlet 3 pin 16 amp flush type complete all as specified and directed.
S&F bell push flush type single pole one way ,6 Amp complete all as specified and directed.
S&F electric bell Ding Dong type 230V, 50Hz complete all as specified and directed.
M&L switch piano flush type single pole, 2-way, 5/ 6 Amps, 240 V complete all as specified and directed.
S&F in replacement of fan regulator electronic type 5 step type and connecting all as specified and directed.
S&F modular switch 1 way, 1 module 6 amps single pole one way all as specified and directed.
S&F modular socket, 2 module 6A 2/3 pin all as specified and directed.
S&F modular switch 1 way, 16 amps, 1 module all as specified and directed.
S&F modular socket , 6A / 16A - 2/3 pin combined, 2 module all as specified and directed.
S&F modular fan regulator 2 module electronic type 5 step, 120W all as specified and directed.
S&F modular bell push flush type single pole one way, 6 amp all as specified and directed.
Taking out old unserviceable light fitting from site all as specified and directed by Engineer-in-Charge
S&F surface mounting universal box type housing made of powder coated CRCA sheet suitable for upto 1 x 18/20 W LED tube including taking down existing old unserviceable housing complete all as specified and as directed.
S&F LED tube 18/20W ultra bright LED polycarbonate tube with efficacy minimum 2000 lumens, CCT > 6500K, PF > 0.90 suitable for fitting into exsting/ new batten housing and connections to ceiling rose using PVC insulated and overall sheathed flexible copper conductor wire of size 0.75 sqmm 3 core and taking down existing old unserviceable tube complete all as specified and directed. (Note :- The contractor will submit the LM-80 and LM-79 report form manufacturer to Engineer-in-Charge for approval before incorporating the items in work).
S&F in replacement tube light fitting LED 20W inverter batten type fitting 4 feet long aluminium housing, charging time 10-12 hours with 4 hours backup IP20, rated volatge 230 V, 50Hz system of wattage 20W (+/- 10%), current less than 1.2 mA, power factor more than 0.95 and system lumen efficeincy of 100 lm/watt, CCT > 6500 K, CRI > 80, THD < 30%, driver efficeincy more than 85% complete with all accessories prewired and connections to ceiling rose using PVC insulated and overall sheathed flexible copper conductor wire of size 0.75 sqmm 3 core all as required at site including taking down existing old unserviceable fitting. (Note :- The contractor shall submit the LM-80 and LM-79 report form manufacturer to Engineer-in-Charge for approval before incorporating the items in work).
S&F lamp holder with LED retrofit lamp 9 watt suitable for Lamp holder base complete all as specified and directed.
S&F ceiling rose, 3 terminals/ phase/ PVC/ polycarbonate, isolated body complete all as specified and directed.
Taking out existing old unserviceable distribution box / sheet metal enclosure off size and making good disturbed surfaces as per existing complete all as specified and directed.
M&L for distribution board made out of CRCA sheet DB vertical type double door TPN 4 way including fixing in the wall, cutting chases, grounting and making good to match with the existing including making connections all as directed containing the folowings:- (a) MCCB 4 Pole 100 Amps 16 KA breaking capacity with thermal release- 01 No (In coming). (b) Bus bar factory made made out of aluminium duly insulated with wire adhesive tape RYB & black - 04 Nos. (c) MCB SPN 40 Amp - 4 Nos, MCB SP 10-32 Amp- 08 Nos (Out going). (d) Connection from MCCB to bus bar will be made with aluminium strip of suitable capacity as directed.
S&F in repair sheet metal enclosure for DB’s when MCB’s to be used, 240 volt 8 way SPN with bus bar and double door complete all as specified and directed.
S&F in repair MCB single pole 20 amps to 32 amps complete all as specified and directed.
S&F in repair MCB single pole and neutral 6 to 32 amps complete all as specified and directed.
M&L for earthing complete with galvanised steel earth plate electrode 60cm × 60cm × 6mm thick, buried directly in ground vertically to a depth not less than 2.25 metres deep below ground level with top edge of the earth plate at a depth not less than 1.5 metres below ground level earth plate surrounded from all sides by 15cm thick packed layer of charcoal dust and common saft filling in alternate layers and electrode connection by using earth lead GI wire 4mm dia (8 SWG) by means of bolts, nuts, check nuts and washers made of galvanised iron and thimbles and other end of the earth wire connected to main switch board protected by galvanised iron light grade pipe 15mm bore in wall/ floor/ and GI pipe 20mm bore light grade for watering with funnel and wire mesh PCC chamber in cement concrete 1:3:6 type C-2 and RCC pit cover including necessary excavation and earth work in any type of soil, returning filling with approved soil and disposed of surplus soil to a distance not exc 50 mtr away all as shown in electrical plate No 3 of SSR 2020 (Part-I).
S&F in repair GI pipe bracket made out of GI pipe light grade 32 mm bore and bent to shape 1.5m long, MS clamps made out of MS flat iron of size 40mm x 5mm and drilling of hole for and including nuts, bolts and washers, painting MS clamps with two coats of synthetic enemal paint over a coat of red oxide primer including taking down the existing GI pipe bracket complete all as specified and directed.
S&F LED security light fitting 45 Watt output, warm white CCT > 3000K with IP 66 protection suitable upto 50mm OD holder on existing wall/ bulilding/poles, LED light fitting shall be made up of pressure die cast aluminium LM 6 alloy with toughend glass, high power LEDs with efficiency minimum 4500 lumens and secondary lenses with brand name embossed on cover. High power ceramic base, CRI >70, surge protection of min 5 KV with driver including taking down existing old unserviceable fitting complete. (Note:- Luminaries and driver shall be of same make).
S&F in repair 10 sqmm one twin core cable flat or circular, 1100 volts grade heavy duty cable PVC insulated aluminium conductor stranded, served with inner sheathing of PVC tape and overall PVC sheathed in service connections complete all as specified and directed.
S&F in repair octane 24 watt 4000k LED Panel slim compact aluminium die cast edge lit panel recess mounted square fixture with opal diffuser and separate electronic drive, ceiling cut out 284mmx284mm all as specified and directed.
S&F in repair indoor type decorative recess mounted direct/ indrect 60cm x 60cm luminaries light fixures 36 watt LED netural white complete including making connection with twin core twisted flexible copper conductor cable with suitable size complete all as specified and directed.
A Schedule of Credit for old/unserviceable demolished/ dismantled items has been catered for in the tender. The Schedule of Credit is pre-priced by MES. The final amount of the tender shall be arrived at after deducting the total amount of Rs. 1,47,410/- Schedule of Credit from the total amount of BoQ as per General Summary sheet catered for after Schedule of Credit.
kailu construction co (BID ID -3307286)
P S BUILDERS (BID ID -3306743)
satpal and brothers (BID ID -3310225)
HARPAL ENGINEERS AND BUILDERS (BID ID -3313214)
stage.html
html • 0.05 MB
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.04 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .