Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹6.9 LAccepted-AOC | L1 | Accepted-AOC lowest bidder | |
| 2 | L2₹7.1 L+₹15,640 (2.25%)Rejected-Finance | L2 | Rejected-Finance bidder is not L1 | |
| 3 | L3₹8.1 L+₹1.2 L (17.0%)Rejected-Finance | L3 | Rejected-Finance bidder is not L1 |
Tender Value
Refer Docs
EMD Value
₹15,119
Closing Date
27 Sept 2024, 3:00 pmClosed
Executive Engineer-I,PWDte.
P12 CIT Road 1st floor Kol 14
Supply Installation Testing and Commissioning of Air Conditioning system 24 Hours with allied EI Work at PG Lab and Bacteriology Lab Department Microbiology at Academic Building of the Calcutta National Medical College Kolkata
2024_WBPWD_755132_1
WBPWD/EE/CKHED/eNIT-33/24-25 2nd call
Open Tender
ELECTRICAL WORKS ORG
Item Rate
30 days
Calcutta National Medical Collage and Hospital Kol
as per nit
4 documents required · 4 mandatory
₹15,119
9 Apr 2025
20 Sept 2024
30 Sept 2024
20 Sept 2024
27 Sept 2024
20 Sept 2024
Amount
Supply & Delivery of 7.5 TR capacity concealed type Split Air Conditioner of rated cooling capacity of 90000 Btu/Hr. With 2 Nos. Rotary compressor, 3 Nos. Indoor Units of rated power supply 230V-1ph-50 Hz,1 no ODU of rated power supply- 415 V, ± 5%, 50 Hz. three phase AC supply.Air flow/per IDU-1000cfm(make Hitachi)(Wired Type Remote)
Supply & Delivery of 3.0 TR capacity concealed type Split Air Conditioner of rated cooling capacity of 36000 Btu/Hr. With 2 Nos. Rotary compressor, 2Nos. Indoor Unit of rated Power Supply 230V-1Ph-50Hz., 1No Outdoor unit of rated power supply 230V-1 Phase-50Hz. Refrigerant- R410A ( Make:- Hitachi/Daikin/Carrier) (Wireless Remote)
Erection and Commissioning Charges for the Above Mentioned 7.5 Ton Concealed Type Split Air Conditioner . Incl Charges For Hanging Arangments by 6 mm thick M.S U channel.
Erection and Commissioning Charges for the Above Mentioned 3.0 Ton Con Type Split Air Conditioner . Incl Charges For Hanging Agreements.
Installation and Commissioning of copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Liquid Line 3/8" OD with .7mm thick.
Installation and Commissioning of copper refrigerant piping, complete with fitting, elbows, bends, supporting arrangement on walls for Suction Line 5/8" OD with .7mm thick.
Supply & Fixing Pipe Insulation in Liquid line 3/8" with 9mm nitrile rubber tube Suction Line.Incl Charges for Rapping the whole Pipe.
Supply & Fixing Pipe Insulation in Liquid line 5/8" with 9mm nitrile rubber tube Suction Line.Incl Charges for Rapping the whole Pipe.
Control copper Cabling from Condensing to Unit and control panel a) 4 core 2.5 sq.mm communication cable
Lifting ,Shifting Charges for Concealed Split Air Conditioner including scaffolding charge for installation of OD unit as per direction of EIC.(Ground Fl to 4th Fl )
Charges for Drain Pipe work Incl Charges 32mm dia PVC/HDPE harded pipes with Insulation, fitting, accessories, bends, elbows, tees, flanges, tappings, wall sleeves, hangers, supports, anchors. and after the work cementing the same.
Supplying, fabrication & fixing 3Nos. M.S u-channel of 6 mm thick of size (75 mm x 40 mm x 40 mm) of 2 m. length for making platform for installation of outdoor unit of 7.5/3.0 Tr Concealed Type split AC incl. drilling 2 nos holes in each channel including cutting holes into the wall & grouting the same with cement concrete (1:1 ½ :3) etc. fabricated with horizontal angle of 25 mm x 25 mm x 6 mm including supporting angle 50 mm x50mm x 6 mm in each platform in outer edge, for transmitting the load centrally through 2Nos.(50 mm x 50 mm x 6 mm) Angle inserted into the exiting wall. The entire platform should be baricated& safe for ODU maintenance. Area of the platform is 3 Mtr. x 1.5 Mtr.
Suppy & fixing of M.S grill Guard suitable for above mention outdoor unit Size of 3 mtrX 1 mtr X 1 mtr with locking arrangement with supply of 8 lever 4 key lock Make: Godrej
Charges for drop ceiling to cover the indoor units made of gypsum
charges for trap door made of aluminium channel & ply wood for IDU maintenance.
Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Havelles/Finnolex) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required
i) 4 x 84/0.3 (6 sqmm) + 2 x 56/0.3 (4 sqmm) ECC VTPNDB to AC (E-14,1(b),v)
ii) 2 x 36/0.3 (2.5 sqmm) + 1 x 22/0.3 (1.5 sqmm) ECC for computer board & power board (E-14,1(a),ii)
iii) 2 x 84/0.3 (6 sqmm) + 1 x 56/0.3 (4 sqmm) ECC TPN to AC (E-14,1(a),iv)
iv) 2 x 22/0.3 (1.5 sqmm)+1 x 22/0.3 (1.5 sqmm) ECC (E-14,1(a),i)
Dismatling the exisiting tubelight in carefully and refixing the same single/twin florescent light fitting complete with all accessories Directly on wall/ceiling with Z Clamp and suitable size MS fastener, Ceiling plate, ceiling rose nipples etc. as required
Supply of 240V. Single LED tube light Fittings complete with all accessories (Make: Philips; Cat No. TMC 501 P 1xT-LED 22W P 3242) incl. supply of 1 no. 20W LED Tube light (Master Led 18W865 T8 2100lm)
Supply of 415V, 3Phase Timer DB(equivalent of 2+12 way SPN Double Door DB in size) with steel sheet enclosure double door, phosphitised powder coated, neutral bar, Din Rail with IP- 43 protection comprises with 1 No.63A FP MCB('C" Curve,10KA),MNX 40 Contactor,25 A Starter,1 No.24 hours programming Time Switch( L&T/ Aproved make) with 15 min minimum switching time of any time and any day and 1no 32A 3Pole contractor(Make- L&T/Approved) complete with internal wiring by suitable sizze of copper wire and Provision for earthing attachment including LED indication light for running condition with locking arrangement & including ON/OFF push button ( Make- L&T/Approved). (Non schedule)
Supply of 230 V Timer DB(equivalent of 2+10 way SPN Double Door DB in size) with steel sheet enclosure double door, phosphitised powder coated, neutral bar, Din Rail with IP- 43 protection comprises with 1 No.25 A DP MCB('C" Curve,10KA),1 No.24 hours programming Time Switch( L/T) with 15 min minimum switching time of any time and any day and 1no 32A 3Pole contractor(Make- L/T) complete with internal wiring by suitable sizze of copper wire and Provision for earthing attachment including LED indication light for running condition with locking arrangement & including ON/OFF push button ( Make-Hager). (Non schedule)
Supply & Fixing 240 V, 3 nos. 6A, & 1 no. 20A plug socket with separate 3 nos. 6 A & 1 no. 20A Piano key type switch, indicator & 20A switch type SP MCB (Anchor) on sheet metal switch board embedded in wall incl. S & F 240x 200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. (E-7,26)
Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. (E-6,22)
Supply & Fixing 240 V, 6A, plug socket with separate 6 A Piano key type switch (Anchor) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. (E-6,21)
Supply & fixing 4 pole MCB enclosure with 1no. 415V 63 Amp 4-pole MCB (Legrand/SIEMENS/ABB) to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C (D-9/11)(D-6/7))
Supply & fixing 4 pole Outdoor type enclosure (SINTEX-3020) with 1no. 415V 63 Amp 4-pole Isolator(Legrand/SIEMENS/ABB) to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C (Non schedule)
Supply & fixing 2 pole MCB enclosure with 1no. 230 V 25/32 Amp 2-pole MCB(Legrand/SIEMENS/ABB) to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C (D-9/11)(D-6/7)
Supply & fixing 2 pole Outdoor type enclosure ( Sintex-3020) with 1no. 230 V 25/32 Amp 2-pole Isolator(Legrand/SIEMENS/ABB) to be fixed concealed in wall & mending good the damages to original finish incl. painting, connection & provision for earthing attachment as per direction of E.I.C (Sintex Box, D-6/7)
Finishing of the PVC insulated wire ends by socketting with pin/ ring type copper sockets and insulated tapes etc., including supplying sockets, tapes.
i)6 sqmm
ii) 4 sqmm
iii) 2.5 sqmm
iv) 1.5 sqmm
Rate should be quoted including of all taxes, duty and cess
Defect Liability period : 1 year
FUTURE SOLAR SYSTEMS (BID ID -5646974)
RAJA & S S COMPANY (BID ID -5647561)
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .