Loading…
Loading…
Tender Value
Refer Docs
EMD Value
₹36,000
Closing Date
9 Jan 2026, 12:30 pmClosed
SE AK Singh
Superintending Engineer E/M Circle, P.W.D. Kanpur
The work of Electrification under the extension of Orai office building of Construction Division 3 PWD in districtJalaun
2026_CEEMP_1103493_1
1772C/06-EMC/2025, Dated-18-12-2025
Open Tender
Electrical Works
180 days
Jhansi
Please refer Tender documents.
4 documents required · 4 mandatory
₹677
Electrical/Mechanical Division PWD Jhansi
₹36,000
Jhansi
3 Jan 2026
3 Jan 2026
9 Jan 2026
3 Jan 2026
9 Jan 2026
3 Jan 2026
6 Jan 2026
Wiring for light point/ fan point/ exhaust fan point/FRESH air fan/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit with Modular type switch, modular plate,suitable GI Box and earthing the points with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C
Wiring for twin control light with 1.5 Sq. mm FRLS PVC insulated copper conductor single core cable in surface/recessed medium class PVC conduit, 2 way modular type switch,modular plate,suitable GI Box and earthing the points with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required.
S/F for Plug Point, Aquaguard,T.V. point of suitable size GI box with modular plate and cover in front in recess, including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A Modular switch , connections etc. as required
Supply and fixing suitable size GI box with modular plate and cover in front surface or in dresses including providing and fixing to 2nos.3 pin 5/6 Ampere modular socket outlet and 2nos. 5/6Ampere modular switch, connections etc. as required,( for computer point)
S/F for Power point ,of suitable size GI box with modular plate and cover in front in recess, including providing and fixing 6 pin 15/16 A modular socket outlet and 15/16 A Modular switch , connections etc. as required
Supplying and drawing 1*1.5 Sq. mm size of FRLS PVC insulated copper conductor , single core cable in recessed PVC conduit for inverter wiring point for light /fan/plug . 1 X 1.5 sq. mm
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 1.5 sq. mm + 1 x 1.5 sq. mm earth wire
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 4 sq. mm + 1 x 4 sq. mm earth wire
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 6 sq. mm + 1 x 6 sq. mm earth wire
Wiring for circuit/ submain wiring along with earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required 2 X 10 sq. mm + 1 x 6 sq. mm earth wire
Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.
Installation of exhaust fan/fresh air in the existing opening, including making good the damage, connection, Testing, commissioning etc. as required.up to 450 mm sweep
Extra for fixing the louvers/shulters complete with frame for a exhaust/fresh air fan of all sizes.
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 12way, Double door
Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 6 way(4 + 18), Double door
Supplying and fixing of following ways surface/recesses mounting,vertical type,415 V, TPN MCB Distribution board of sheet steel,dust protected,duly powder painted,inclusive of 200 A tinned copper busbar, common neutral link,earth bar,din bar for mounting MCBs(but without MCBs and incommer) as required. 4 Way (4+12),Double door
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Single Pole
Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Double Pole
Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 milliamperes in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A
Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections,etc as required . 125 A,36KA,FPMCCB
S/F suitable size GI box for AC point/geyser point with modular plate and cover in front ,in recess , including providing and fixing 25 A modular socket outlet and 25 A modular SP MCB 'C' curve , connections etc. as required
Supplying and fixing brass batten/ angle holder including connection etc as required
Supply and fixing call bell/ buzzer suitable for single phase, 230 V complete as required
Earthing with GI earth plate 600 mm*600mm* 6mm thick including accessories, and providing masonry enclosures with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required .
Providing and laying earth connection from earth electrode with 6 SWG dia G.I. wire in 15 mm dia G.I. pipe from earth electrode including connection with G.I. thimble excavation and re-filling as required.
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 2 X 10 sq. mm (19 mm)
Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3.5 X 25 sq. mm (28 mm)
Supply and fixing of following size of medium class PVC conduit along with accessories in surface races including cutting the wall and marking good the same in case of racist conduit edge required . 25mm
Supply and fixing of LED tube light with heavy duty metal box type tube light fitting 1x22 watt. Suitable for up to 1x22 watt LED polycarbonate tube light complete including tube suitable for both surface & suspended complete in all respect. CAT-AAA 2620 system lumens, >120Lm/W, PF>0.95, THD<10%, CRI>80, sheet thickness min 0.8 mm., tube with aluminium heat sink > 300 V over voltage protection, 2.5 KV internal surge protection with 5 year warrantee.
Supply and laying of aluminum conductor PVC insulated armoured served sheathed cables 1100V grade on wall surface as directed by engineer in charge complete in all respects including excavation and refilling. The armouring of the cables shall be properly connected with the earth conductor by clamps etc. 25 Sq. mm 3 -1/2 core
S/F of L.E.D. Bulb 14 W/15 W pure white minimum lumen 1400-1500 lm, 110 lm/watt, pf > 0.8 with minimum 01 yearr warranty.
Supplying and fixing 63amps,TPMBB(10KA) rating, 415 volts, "C" curve, miniature circuit breaker suitable for inductive load of triple poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.
Supply of 250 mm sweep fresh air fan of maximum 35 watt power consumption, 900 rpm, air delivery of 800 m3/h, rated voltage 220 V-240V, rated frequency of 50 Hz and maximum noise level 45-50 dB.
Please Enable Macros to View BoQ information
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 2.03 MB
Tendernotice_2.pdf
PDF • 8.21 MB
Tendernotice_3.pdf
PDF • 0.97 MB
Tendernotice_4.pdf
PDF • 2.77 MB
BOQ_2034992.xls
BOQ • 0.31 MB
Download all tender documents and submit your bid