BILL OF QUANTITY
BOQ OF ELECTRICAL WORKS FOR PROPOSED RESEARCH LAB AT HINDU COLLEGE, DELHI
S.NO. DSR 2018 DESCRIPTION QTY UNIT RATE DSR AMOUNT NS AMOUNT
SUB-HEAD "A" ISOLATOR PANEL"
Supplying, Installation, Testing and Commissioning of
cubical type menufactured through 1.6/2 mm thick CRCA
sheet dust and vermin proof duly finshed by 7 tank
process with approved paint with bus bars, neutral
links, earth strips, cable alleys etc as required and as
per detailed specs with following components.
A ISOLATOR PANEL ( Indoor Type)
1. 1 Set of 315 Amps. 415 Volts 4P M.C.C.B. of 25 K.A.
breaking capacity with overload, S/C protection with 3 2 Sets 28938.86 57877.71
Nos. indication lights L.E.D. type .
2. 1 Set of 160 Amps. 415 Volts 4P M.C.C.B. of 25 K.A.
breaking capacity with overload, S/C protection with 3 2 Sets 31455.28 62910.56
Nos. indication lights L.E.D. type .
SUB-HEAD "A" ISOLATOR PANEL"
SUB HEAD "B" ELECTRICAL PANELS
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
Supplying, Installation,Testing and Commissioning of
Panel made of 16 S.W.G.C.R.C.A. sheet, steel dust and
vermin proof compartmentalized construction with bus
bar chambers, cable alley, cable glands plate etc. as
required duly painted from inside as well as out side, as
1. UPS INCOMING PANEL( Located in Basement)
i) 2 Sets of 315 Amps. 415 Volts 4P. M.C.C.B. of 25 KA with
overload, S/C and earth fault protection with electrical
i) 2 Sets of 400-Amps 3 phase 4 wire 415 volts 50 HZ AL bus
bars with colour coded PVC heat shrinkable sleeves
(Neutral to be equal to phase size).
i) 1 No. 315 Amps 4P. MCCB of 25 KA with electrical
interlock between two incomers and a bus coupler.
i) 2 Sets of Digital multi function meter with 315/5A CTs,CT
shorting links R/Y/B LED indicating lamps and 2A control
ii) 2 Sets of LED indicators for Incoming Breaker 'ON', 'OFF',
'TRIP' LED lamps.
iii) 1 Set of LED indicators for Bus Coupler 'ON', 'OFF', 'TRIP'
i) 5 Nos. 160 Amps. 4P MCCB of 25 KA with builtin
UPS INCOMING PANEL( Located in Basement) AS
DESCRIBED ABOVE
Digitally signed by
SURENDRA SURENDRA KUMAR MEENA
KUMAR MEENA Date:
2. UPS OUTGOING PANEL ( Located in Basement)
3 Nos. 125 Amps 4P M.C.C.B. of 25 KA with built in
protection inclusive O/L & S/C.
1 Set of 250 -Amps 3 phase 4 wire 415 volts 50 HZ Al bus
bars with colour coded PVC heat shrinkable sleeves
(Neutral to be equal to phase size).
3 Sets of Digital multi function meter with 125/5A CTs,CT
shorting links R/Y/B LED indicating lamps and 2A control
i) 6 Nos. 100 Amps. 4P MCCB of 25 KA with builtin
UPS OUTGOING PANEL ( Located in Basement) AS
DESCRIBED ABOVE
3. UPS EQUIPMENT PANEL ( Located at GND FLR )
1 Nos. 100 Amps 4P M.C.C.B. of 25 KA with built in
protection inclusive O/L & S/C.
1 Set of 125-Amps 3 phase 4 wire 415 volts 50 HZ Cu bus
bars with colour coded PVC heat shrinkable sleeves
(Neutral to be equal to phase size).
3 Nos. of phase indication lights L.E.D. type with
i) 6 Nos. 63 Amps. TPN MCB of 10 kA
UPS EQUIPMENT PANEL ( Located at GND FLR ) AS
DESCRIBED ABOVE
4. MAIN UPS DB-G(GND FLR) VERTICAL TYPE DB( TYP. -F2)
1 Nos. 100 Amps 4P M.C.C.B. of 25 KA with built in
protection inclusive O/L & S/C.
1 Set of 125-Amps 3 phase 4 wire 415 volts 50 HZ Cu bus
bars with colour coded PVC heat shrinkable sleeves
(Neutral to be equal to phase size).
3 Nos. of phase indication lights L.E.D. type with
i) 10 Nos. 63 Amps. DP MCB of 10 kA
MAIN UPS DB-G(GND FLR) VERTICAL TYPE DB ( TYP. -F2)
AS DESCRIBED ABOVE
5. MAIN UPS DB-F1 (1st FLR) VERTICAL TYPE- 8 WAY TPN
1 Nos. 100 Amps 4P M.C.C.B. of 25 KA with built in
protection inclusive O/L & S/C.
1 Set of 125-Amps 3 phase 4 wire 415 volts 50 HZ Cu bus
bars with colour coded PVC heat shrinkable sleeves
(Neutral to be equal to phase size).
3 Nos. of phase indication lights L.E.D. type with
i) 12 Nos. 63 Amps. DP MCB of 10 kA
MAIN UPS DB-F1 (1st FLR) VERTICAL TYPE- AS DESCRIBED
6. Supplying, Installing, Testing and Commissioning of
following M.C.B., MCCB duly enclosed in M.S. enclosures
in following capacities with proper cable end boxes.
a) 63 Amps. TPN MCB. 1 Sets 3516.28 3516.28
SUB HEAD "C" CABLES AND EARTHING
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
The rates quoted under this sub head shall include the
a) Providing proper tools and plants for doing proper cabling
b) Cutting chases, providing clamps hangers etc. for fixing
the cable/cable tray earth strip / earth wire in position.
c) Excavation back filling and disposal of surplus earth as
d) The cables in proper way taking into consideration the
turning radius of cable.
1. Supply, Making, Testing & Commissioning of advance
maintenance free Chemical Gel Earthing of Single Pipe
Technology (Copper) of 3mtr long 50mm dia JK Chem
rode filled with highly conducting metallic compounds
with the permenant sealings at the both the ends with
compressed at the top along with 50 Kgs of JK RESLOW
chemicals for (mixture of Sulphate, Silica, Alumina, Iron
Oxide, Titanium Oxide, Calcium Oxide, Potassium Oxide,
Chloride, Nickel Oxide, Magnesium Oxide, Sodium Oxide,
Zinc Oxide, etc) Resistance Lowering Grounding Minerals. 2 Sets 6938.04 13876.07
The loss on ignition by mass of the chemical compound
RESLOW shall be less than 20%. The chemical compound
should be tested and certified by any International
accredited and BIS (Bureau of Indian Standards)
accredited laboratory. The chemical earth electrode
manufacturer shall be an ISO 9001:2008 & ISO
14001:2004 certified organization.
(ii) Supply, Making, Testing & Commissioning of advance
maintenance free Chemical Gel Earthing of Dual Pipe
Technology (AL) of 3mtr long 50mm dia of outer shell
(MS) with the 25mm dia of inner shell (MS) of 80-100
microns galvanized JK CHEMRODE filled with highly
conducting metallic compounds with the permenant
sealings at both the ends with the lead terminal of
32x10mm size at the top along with 50 Kgs of JK RESLOW
(mixture of Sulphate, Silica, Alumina, Iron Oxide, Titanium
Oxide, Calcium Oxide, Potassium Oxide, Chloride, Nickel 2 Sets 6459.69 12919.38
Oxide, Magnesium Oxide, Sodium Oxide, Zinc Oxide, etc)
Resistance Lowering Grounding Minerals. The loss on
ignition by mass of the chemical compound JK RESLOW
shall be less than 20%. The chemical compound should be
tested and certified by any International accredited and
BIS (Bureau of Indian Standards) accredited laboratory.
2. Supply, installation, effecting proper connection testing
and commissioning of the following size copper earth
strips / G.I. Wires as required.
a) 70 sq.mm. Flex. Cu. Cable in P.V.C. conduit including and
termination on both ends
b) 16 sq.mm. Flex. Cu. Cable in P.V.C. conduit including and
termination on both ends
j) 8 SWG Cu Wire R.O RM 107.19
k) Supplying & fixing of earth connector strip made out of 40
x 5mm Cu. Strip of 450mm long with suitable holes of 9
Nos. 15mm dia with brass nuts & bolts with washers
complete with mounting arrangment on insulator duly
enclosed in M.S. enclosures with proper cable end boxes.
l) Supplying & fixing of earth connector strip made out of 40
x 5mm Al. Strip of 450mm long with suitable holes of 9
Nos. 15mm dia with Al alloy nuts & bolts with washers
complete with mounting arrangment on insulator duly
enclosed in M.S. enclosures with proper cable end boxes.
m) Supplying & fixing of earth connector strip made out of 32
x 5mm Cu. Strip of 300mm long with suitable holes of 6
Nos. 15mm dia with brass nuts & bolts with washers
complete with mounting arrangment on insulator duly
enclosed in M.S. enclosures with proper cable end boxes.
n) Supplying & fixing of earth connector strip made out of 32
x 5mm Al. Strip of 300mm long with suitable holes of 6
Nos. 15mm dia with Al Alloy nuts & bolts with washers
complete with mounting arrangment on insulator duly
enclosed in M.S. enclosures with proper cable end boxes.
o) Supplying & fixing of earth connector strip made out of 25
x 5mm Cu. Strip of 300mm long with suitable holes of 9
Nos. 10mm dia with brass nuts & bolts with washers
complete with mounting arrangment on insulator duly
enclosed in M.S. enclosures with proper cable end boxes.
3 (i) Supply and laying of Power Cable with aluminium / copper
conductor 1.1 kV grade, Stranded conductor, XLPE
Insulated, PVC tape inner sheathed, galvanized steel strip
armour, PVC Type ST2 sheathed as per IS 7098 (Part 1)
1988. The cables shall be laid in existing tray / built up
trench / hume pipes etc., Rate shall exclude cost of tray /
trench which is covered in separate line items. Rate to
include provision of approved aluminium cable labels at
both ends and route markers at 15mtr intervals. Each run
of cable to be tested with 1KV meggar and results
submitted to client. (Note:- Ref. Cable Schedule Chart.)
a) 3 1/2 x 185 sq. mm XLPE Insulated Al Ar. cable 210 RM 736.95 154759.19
b) 3 1/2 x 50 sq. mm XLPE Insulated Al Ar. cable R.O RM 301.48
c) 3 1/2 x 35 sq. mm XLPE Insulated Al Ar. cable 100 RM 235.82 23582.35
d) 4 x 25 sq. mm XLPE Insulated Al Ar. cable R.O RM 174.19
e) 3 x 10 sq. mm XLPE Insulated Al Ar. cable 600 RM 121.93 73158.89
(ii) Supplying, laying, installing, testing and commissioning of
the following size 1.1kV, single core copper conductor,
flexible cables . The quoted price shall be inclusive of
clamping while laying on tray. All cables to be provided
with identification tags.
a) 70 Sq. mm. single core Flex Cu. Cable R.O R.M. 830.74
b) 35Sq. mm. single core Flex Cu. Cable 100 R.M. 400.63 40063.20
c) 16Sq. mm. single core Flex Cu. Cable R.O R.M. 158.11
4(i) Supplying, installing, effecting connection testing and
commissioning cable and joints with solderless crimping
lugs, double compression glands etc. as required with
earthing of cable glands.
a) 3 1/2 x 185 sq. mm XLPE Insulated Al Ar. cable 4 Sets 1176.44 4705.75
b) 3 1/2 x 50 sq. mm XLPE Insulated Al Ar. cable R.O Sets 509.16
c) 3 1/2 x 35 sq. mm XLPE Insulated Al Ar. cable 8 Sets 572.14 4577.12
d) 4 x 25 sq. mm XLPE Insulated Al Ar. cable R.O Sets 602.96
e) 3 x 10 sq. mm XLPE Insulated Al Ar. cable 52 Sets 261.28 13586.65
(ii) Cutting, peeling, terminating and connecting above
mentioned cables with PVC cable gland with Earth Tags
and crimped Cu. Lugs.
a) 70 Sq. mm. R.O. Sets 468.97
5. Supply and fixing MS powder coated factory fabricated
perforated type cable trays of the following sizes as per
specification including suspenders, rag bolts, hanging
clamps as required as per site requirements..
i) 450 mm x 50 x 50 x 2 mm thick. R.O RM 656.55
6. Supplying material and making man holes of 300 x 300 x
450 mm with C.I. Man hole cover.
Earth work in excavation in all type of soils, sand and
moorum, depth and disposal of surplus earth.
8. Sand Cushioning & Brick Protection
Providing 150mm x 300mm thick sand cushioning and
brick protection for under ground armoured cables. 20 RM 178.21 3564.15
9. HUME PIPES AND MANHOLES
a) Supplying and fixing 200mm dia DWC HDPE pipe
including excavation, sand cushioning, brick protection 20 RM 870.94 17418.78
and back filling of soil.
SUB HEAD "D" DISTRIBUTION BOARD AND INVERTER
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
A. DISTRIBUTION BOARDS
1. 2.23 Supplying and fixing Cable End Boxes (IP 43) suitable for
following single pole and neutral, sheet steel, MCB
distribution board, 240 volts, on surface/ recess, complete
with testing and commissioning etc. as required.
2.23.2 For 8 way, Double door SPN MCBDB 26 Each 731.00 19006.00
8 WAY SPN DB (FOR UPS)
NS (1713) 63 Amps. DP M.C.B.S. as incomers. 26 Nos. 327.41 8512.54
NS (1706) 16 Amp S.P.M.C.B. as outgoings and 156 Nos. 138.00 21527.59
SUB - HEAD "E" POINT WIRING
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
The rates for Point Wiring shall include the following :
a) Point Wiring shall include with circuit wiring (2 x 2.5 sq.
mm.) of light / fan / outlets of any length from the
distribution board via switch to the point otherwise as
specified in BOQ.
b) All the light fixtures, ceiling fans, exhaust fans, third pin
of outlets, switch and outlet boxes shall be earthed with
1.5 mm dia. Insulated copper wire otherwise as specified
c) Providing & Embedding conduits and allied fittings in walls
/ floors etc. cutting chases and making the surfaces good
or fixing in partition cutting chases paneling false ceiling
work with proper hangers / clamps. (Conduits & wiring
for power out-lets only shall be paid seperately on linear
measurements basis).
d) All accessories necessary to complete the wiring as
e) Most of conduiting shall be done on surface, boxes may
be heavy duty urea/Polycarbonate type in place of G.I.
1. Supplying, Laying and Fixing of 63 AMP TPN Industrial
Socket controlled by 63 Amp TPN MCB complete with
4x4sqmm+ 2x 4sqmm earthing FRLS Cu Sheated
unarmored cable and laying on existing exposed cable
tray/trunking/raceway etc including providing 63 Amp
Industrial socket outlet and 63 Amp TPN MCB complete
with M.S. enclosure etc. as required including associated
civil works (like chipping, plastering, drilling etc..) and 5 Nos. 10402.88 52014.39
required to complete the job. (FOR Lab equipment) Note:-
consider Average distance from DB to industrial socket
point is 12-15mtr
Note:- Cost of Supply and laying of
raceway/Trunking/Cable tray is covered in sepertae items.
3. Supplying, Laying and Fixing set of 15Amp UPS power
plug outlets controlled with modular type mini MCB
complete with 3 X 4 sq.mm. FRLS insulated copper
conductor wires laying on existing exposed raceway
including providing 3nos. of 15 Amp 6 pin socket outlet 105 Nos. 2925.81 307209.97
and 16 Amp modular type mini MCB with indicator, cover
plate to outlet boxes and earthing etc as required.
Note:- Refer drawing/Layout for detail decription.
4. Supplying, Installation of following FRLS P.V.C. conduits
with junction boxes complete.
i) 20 mm dia conduit 10 RM 45.11 451.15
ii) 25 mm dia conduit 20 RM 50.42 1008.44
iii) 32 mm dia conduit R.O. RM 66.34
5. Supplying and drawing effecting of the following wires in
the existing conduits.
i) 2 x 4 sq.mm. wire along with 1 No. 2.5 Sq.mm PVC
insulated copper wire.
ii) 4 x 4 sq.mm. wire along with 2 No. 2.5 Sq.mm PVC
insulated copper wire.
iii) 2 x 6 sq.mm. wire along with 1 No. 2.5 Sq.mm PVC
insulated copper wire.
6. Designing, fabricating, installing and commissioning floor
/ ceiling junction boxes fabricated out of 2mm thick
C.R.C.A. steel sheet in following sizes with cover plate of
3mm thickness painted from inside as well as outside with
proper knock outs for conduits :-
7. 4.1 Supplying and installing following size of perforated
(DSR painted with powder coating M.S. cable trays with
perforation not more than 17.5%, in convenient sections,
joined with connectors, suspended from the ceiling with
M.S. suspenders including bolts & nuts, painting
suspenders etc as required.
a) 4.160. 450 mm width X 50 mm depth X 2.0 mm thickness 10 RM 700.00 7000.00
b) 4.140. 300 mm width X 50 mm depth X 1.6 mm thickness 10 RM 621.00 6210.00
c) NS 100 mm width X 50 mm depth X 1.6 mm thickness
Lowest R.O RM 298.55
8. Supplying, fixing of heavy duty Trunking/Raceway made
out of FRLS PVC channel The quoted rates shall be
inclusive of making the surface good as required/ or fixing
on wall with box fastners.
SUB HEAD "F" UPS SYSTEM
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
1. Supplying, Installation, Testing and Commossioning of 60
KVA high Performance IGBT / PWM based True Online
Double Conversion Fully Microprocessor Con-trolled DSP
based UPS System including SMF VRLA batteries suitable
for 15-20 Min backup on each UPS (12V-42AH-60nos. per
UPS. Consisting of 100% Capacity Static IGBT / PWM
Inverter and rectifier with inbuilt active power factor
correction, input current harmonics<5%, 1:1 Galavanic 1 Nos. 863810.34 863810.34
isolation transformer, with static and manual
maintenence bypass with efficenecy not less than 94% on
online mode along with features like inbuilt LCD display,
Reverse phase sequence protection, EPO and Backfeed
protection etc as required.
2. Supplying, Installation, Testing and commossioning of
Suitable rating uninyvyn interlink cable for connecting
60nos. Battries of each UPS 60KVA UPS
3. Supplying and Installation of of MS powder coated
battery rack made up of min 40x6mm angle or as 1 Sets 11278.63 11278.63
approved electrical incharge
SUB HEAD "G" MISCELLANEOUS
S.NO. DESCRIPTION QTY UNIT RATE AMOUNT
1. Supply, fabrication, installation of steel fabricated cable
supports/ Light fixture supports including, welding, 250 KG 104.17 26043.62
grouting and painting as required.
2. Supply, installation of 1.1 KV grade rubber mats of 1
3. Supply and installation of the following portable fire
a) 2 Kg Automatic Clean Agent based sprinkler type
b) 5 Kg ABC type fire extinguishers. 1 Nos. 1425.97 1425.97
4. Supply, Installation, Testing and Commossioning of
Electronic type Rod repellent system Generates
Ultrasonic varying frequency from 22KHz To 48KHz (56KHz-
123KHz) with variation cycle of 7 to 10Seconds to cover
area of 500sqft without any mechanical trap or toxic
chemicals opertaing at single phase 50Hz power supply
and Should be CE/NABL/STQC Certified.
GRAND TOTAL 32216.00 3167059.89
GRAND TOTAL 32216.00 3167059.89
GRAND TOTAL 3199275.89.
GRAND TOTAL 3199275.89.
stage.html
html • 0.05 MB
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.06 MB
NIT.pdf
Tender Document
SCOPE_OF_WORK.pdf
Tender Document
MAKE_LIST.pdf
Tender Document
BOQ.pdf
Tender Document
GCC_2019_with_Amendments08.pdf
Tender Document
Drawings123.pdf
Tender Document
SCC.pdf
Tender Document
TECHNICAL_SPECIFICATION.pdf
Tender Document
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .