Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹5.6 CrAdmitted-Finance | ₹5.6 Cr | L1 | Admitted-Finance |
| 2 | L2₹6.3 Cr+₹65.6 L (11.7%)Admitted-Finance | ₹6.3 Cr+₹65.6 L (11.7%) | L2 | Admitted-Finance |
| 3 | L3₹7.3 Cr+₹1.7 Cr (29.7%)Admitted-Finance | ₹7.3 Cr+₹1.7 Cr (29.7%) | L3 | Admitted-Finance |
| Sl No | Description | Qty | Unit | Ali Mohammad Baba and Sons L3 | M/S AL JAN CONSTRUCTIONS L1 | TZ Engineering Works L2 |
|---|---|---|---|---|---|---|
| 1.003 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 1250 Amps of 3 phase, 50 c/s and 31.5KA for 1 second) as specified in the technical specification (4 No.Isolator to be supplied by JKPTCL) | ||||||
| 1.10 | Supply of material, Total unit, Amount (including all taxes, duties and Sapres) | 1 | NO. | 8,01,000 ₹8,01,000 | 15,00,000 ₹15,00,000 | 8,00,000 ₹8,00,000 Lowest |
| 1.20 | Erection/Civil including p/l of foundations, Testing and commissioning works Total unit, Amount (including WCT,LC) | 5 | NO. | 30,000 ₹1,50,000 | 9,000 ₹45,000 Lowest | 70,000 ₹3,50,000 |
| 2.00145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades as specified in the technical specification. (Isolator to be supplied by JKPTCL) | ||||||
| 2.10 | Erection/Civil, Testing and commissioning works including transportation from Divisional stores to the erection site Total unit, Amount (including WCT,LC) | 16 | NO. | 23,000 ₹3,68,000 | 5,500 ₹88,000 Lowest | 20,000 ₹3,20,000 |
| 3.00145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Earthing Blades as specified in the technical specification. (Isolator to be supplied by JKPTCL) | ||||||
| 3.10 | Erection/Civil, Testing and commissioning works including transportation from Divisional stores to the erection site Total unit, Amount (including WCT,LC) | 2 | NO. | 25,000 ₹50,000 | 7,000 ₹14,000 Lowest | 20,000 ₹40,000 |
| 4.00Single phase, 50 c/s 145KV Current Transformers (900-600-300/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA as specified in the technical specification. | ||||||
| 4.10 | Supply of material, Total unit, Amount (including all taxes, duties and Sapres) | 18 | NO. | 1,80,000 ₹32,40,000 Lowest | 2,50,000 ₹45,00,000 | 2,10,000 ₹37,80,000 |
| 4.20 | Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC) | 18 | NO. | 10,000 ₹1,80,000 | 3,000 ₹54,000 Lowest | 8,000 ₹1,44,000 |
Tender Value
₹5.6 Cr
EMD Value
₹11.2 L
Closing Date
16 Sept 2020, 2:00 pmClosed
Superintending Engineer Circle-ist
Office of the Superintending Engineer Circle-ist Bemina Srinagar
Supply, Erection, Testing ,Commissioning of Balance works for 50MVA,132/33KV GRID STATION Khrew as per BOQ
2020_PDD_102996_1
TLMD-IV/e-NIT/13 OF 2020-21
Open Tender
Electrical and Maintenance Works
Item Rate
240 days
Khrew Pampore
Please refer Tender documents.
4 documents required · 4 mandatory
₹5,000
Executive Engineer TLMD-IV Pampore
₹11.2 L
17 Nov 2020
26 Aug 2020
17 Sept 2020
26 Aug 2020
16 Sept 2020
26 Aug 2020
Amount
3 pole, SF6 gas filled, out door Circuit Breaker , including all accessories, auxiliaries and marshalling boxes/Kiosks, (145KV, 1250 Amps of 3 phase, 50 c/s and 31.5KA for 1 second) as specified in the technical specification (4 No.Isolator to be supplied by JKPTCL)
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil including p/l of foundations, Testing and commissioning works Total unit, Amount (including WCT,LC)
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades as specified in the technical specification. (Isolator to be supplied by JKPTCL)
Erection/Civil, Testing and commissioning works including transportation from Divisional stores to the erection site Total unit, Amount (including WCT,LC)
145kV, 50c/s , 2000 Amp, 31.5kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with Earthing Blades as specified in the technical specification. (Isolator to be supplied by JKPTCL)
Erection/Civil, Testing and commissioning works including transportation from Divisional stores to the erection site Total unit, Amount (including WCT,LC)
Single phase, 50 c/s 145KV Current Transformers (900-600-300/1-1-1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single phase, 50 c/s 145KV Nuetral Current Transformers (600-300/1-1-1 A or as per site specifications), 31.5KA for one second, rated dynamic current 100KA(peak), Class A insulation, Burden 20 VA as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single Phase 50 c/s, outdoor metal oxide gapless type, 120KV (rms) Surge Arrestor including Surge counters/monitors, insulating base all associated accessories, auxiliaries as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
132KV Control and Relay Panel for Feeder (2 No.)/Transformer (2 NO.) and bus coupler (1 No.) completely wired including Substation automation supporting IEDs/numerical relays inlcuding Distance Recorder as specified in the technical specification. (C&R Panel to be supplied by JKPTCL)
Erection/Civil, Testing and commissioning works including its transportation from Divisional stores to errection site Total unit, Amount (including WCT,LC)
Single phase, 50 c/s 132KV Capacitor Voltage Transformers (132/√3) KV/ (110/√3)V, One min power freq withstand 275KVrms as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
132KV Post Insulators Solid Core Type, Power Frequency Withstand Voltage 275KVP Dry lightning impulse withstand voltage ± 650 (KVP) as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
36kV, 50c/s , 2500 Amp, 25kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators without Earthing Blades as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
36kV, 50c/s , 2500 Amp, 25kA for one second, Ac motor operated horizontal double break, outdoor type 3 pole Isolators with One Earthing Blades as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single phase, 50 c/s 36KV Current Transformers (1200-600-300 /1-1-1 A or as per site specifications) , 25KA for one second, rated dynamic current 25KA(peak), Class A insulation, Burden 20 VA as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single phase, 36Kv50 c/s outdoor metal oxide gapless type 120kV (RMS) surge arestor incl. surge counters / moneters, insulating base all associated ccessories, auxiliaries as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
33KV Control and Relay Panel for Line/Feeder/transformer, completely wired including Substation automation supporting IEDs/numerical relays as specified in the technical specification. (C&R Panels to be supplied by JKPTCL)
Erection/Civil, Testing and commissioning works including its transportation from divisional stores to erection site Total unit, Amount (including WCT,LC)
Single phase, 50 c/s outdoor 33KV PT (33/√3) KV/ (110/√3)V with Highest System Voltage36KV, One min power freq withstand 70KVrms
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Galvanised Structures including Nuts & Bolts
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
2 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
4 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Spares)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
8 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
10 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
12 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
16 Core, 2.5 sq mm, 1100 V, PVC insulated, PVC sheathed, FRLS, galvanised steel wire/ strip armoured stranded copper conductor control cable complete as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
300 mm2 PVC insulated Cable 1.1KV Grade, 3.5 Core, Aluminium armoured, FRLS as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Marshalling kiosk with Kiosk frames mild steel structural sections for pressed and shaped cold-rolled sheet steel, thickness not less than 2.0 mm. Frames shall be enclosed in cold-rolled sheet steel of thickness not less than 1.6 mm. Doors and covers shall also be cold rolled sheet steel of thickness not less than 1.6 mm. complete structures shall be rigid, selfsupporting, free from flows, twists and bends. Dust and vermin proof construction and shall be provided with a degree of protection of IP: 55, with Copper Bar earthing. Finishing paint on panels shall be of shade 692 (smoke grey) of IS: 5. The inside shall be properly stoved. The paint thickness shall be at least 50 microns.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
500mm2 ACSR Moose Conductor (a)Aluminium =54/3.53 mm (b) Steel= 7/3.53 mm overall diameter =31.77mm Approx. Wt. =1998 kg/km ultimate strength = 159.60 KN
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single Tension Fittings For Single 500mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single Suspension Fittings For Single 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single Tension Fittings For Twin 500 mm2 ACSR shall have minimum failing load of 100% ultimate strength of Bundle conductors with compressive type Tension clamps having slipping strength 95% of ultimate Strength of conductors. The ball and socket designation must be 20mm. Minimum Ultimate strength (Tensile strength) shall be 70 KN.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Single Suspension Fittings For Twin 500mm2 conductor shall have minimum failing load of 50% ultimate strength of bundle conductors with Forged Steel Hanger free center type without bolt only having slipping strength 15% of ultimate strength of conductor.The ball and socket designation must be 20mm.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Disc Insulators 120 KN,Ball & Socket type, 145mm height and 280mm dia. Creepage total 430 mm and 260 mm protected.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Disc Insulators 70 KN,Ball & Socket type, 145mm height and 255mm dia. Creepage total 430 mm and 260 mm protected.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
T Clamps 500mm2 /500mm2, made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
T Clamps Twin 500mm2 / Twin 500mm2 , made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
P I Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
P G Clamps made of Alluminium Alloy and shall comply in all respects with IS:5561-1970 (latest edition)
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Earth Wire 7/3.15mm
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Earthwire Tension Clamps comprise of compression type tension clamp with two ‘D’ shackles, jumper terminals, nuts & bolts and washers etc.slip strength shall not be less than 95% of the ultimate strength of the ground wire. Conductivity shall not be less than corresponding length of GSS ground wire
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Spacers for twin moose
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Lugs, Ferrules, Cable Glands
33/0.433 KV, 250 KVA, 3-Phase Distribution Transformers with Bimettalic Terminal Connectors Energy Level-2
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil INCLUDING P/L OF FOUNDATIONS, Testing and commissioning works Total unit, Amount (including WCT,LC)
Concreting of yard & Laying Of yard metal (150mm thick)
Battery Bank 110 V,300 AH , of 55 No. cells of 2 V each, sealed maintenance free VRLA type,High impact Polyprophelene copolymer container,flame retardant as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
110 V Battery charger (Three phase): Battery charger as well as Automatic Regulators shall be of static type compatible with VRLA Batteries. Should also have necessary temperature sensors. should have both Automatic and Manual control of output voltage and current. (i) Float charging and load current ratings: 30 Amp / 60Amp / 70Amp / 100Amp at 220 V to 252 V D.C. (ii) Boost charging current rating: 50 Amps / 55Amp / 60Amp / 70Amp / 80Amp / 100 Amp at 198 V to 296/302 V D.C. as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
DC Distribution Panel (110V, DC) with 1 No.10Amp. Air break ckt. Double pole for battery incoming supply with DP MCBs & indicating Lamps etc. as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
AC Distribution Panel (415 V, AC) complete with ckt. Breakers, indicating Lamps etc as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Power cables for AC/DC network in Control room.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
100 KVA servo stabliser 3-phase 4 wire copper wond indoor type, input voltage range 220-460V, output 400V ± 1%,in two parts of oil cooled and air cooled having, Digital control, Response time <10ms, Automatic Switch-Off against:· Under / Over-Voltage· Over-Load & Short – Circuit· Single Phasing, Class C Type Secondary surge Protection No 1 2.65 2.65 6 Power cables for AC/DC network in Control room for 132/33KV Grid Station Lot 1 5.00 5.00
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
Supply and installation of Air Conditioner ( Hot & Cold) CENTRAL HEATING
Portable fire extinguisher dry chemical powder type of 10 Kg capacity along with all accessories as specified in technical specification,Portable fire extinguisher dry chemical powder type of 25 Kg capacity along with all accessories as specified in technical specification Portable fire extinguisher CO2 type of 5 Kg Capacity with supporting /mounting arrangement as specified in technical specificationSiren along with all accessories as specified in technical specification,Microprocessor based Fire Detection & Alarm System as specified in technical specification Power & Control Cables for fire detection & alarm system
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil, Testing and commissioning works Total unit, Amount (including WCT,LC)
33KV VCB (36 KV, 1250 Amps of 3 phase, 50 c/s and 25KA for 3 sec) outdoor type with all accessories and auxiliaries as specified in the technical specification.
Supply of material, Total unit, Amount (including all taxes, duties and Sapres)
Erection/Civil including P/L of foundations, Testing and commissioning works Total unit, Amount (including WCT,LC)
Providing & Laying of MS cable racks/ cables trays& accessories
400mmx3000mm
300mmX2500mm
Providing & Laying of MS Chequered Plates (6MM)
Main1200x1200mm
Main (900x900mm)
Sub Main(600x600mm)
Sub Main(600x450mm)
Tee Off(300x450mm)
TZ Engineering Works
Ali Mohammad Baba and Sons
stage.html
html • 0.03 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Tendernotice_1.pdf
PDF • 0.16 MB
SBDkhrew.pdf
Tender Documents • 1.53 MB
TECHNICALspecification.pdf
Additional Documents • 3.92 MB
BOQ_196351.xls
BOQ • 0.34 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .