| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹31.8 LAccepted-AOC | L1 | Accepted-AOC Being lowest | |
| 2 | L2₹33.7 L+₹1.9 L (6.07%)Rejected-Finance 6 RAILWAY STATION ROAD ONKAR INDUSTRIES GULAMALI PURA BAHRAICH UTTAR PRADESH 271801 | BAHRAICH | UTTAR PRADESH | 271801 | L2 | Rejected-Finance Not being lowest | |
| 3 | L3₹34.6 L+₹2.7 L (8.64%)Rejected-Finance | L3 | Rejected-Finance Not being lowest | |
| 4 | L4₹35.8 L+₹4.0 L (12.6%)Rejected-Finance | L4 | Rejected-Finance Not being lowest | |
| 5 | L5₹36.1 L+₹4.3 L (13.5%)Rejected-Finance | L5 | Rejected-Finance Not being lowest |
Tender Value
₹38.0 L
EMD Value
₹76,100
Closing Date
13 Dec 2023, 6:00 pmClosed
Col Sachin Sharma CWE
Military Engineer Services, Commander Works Engineer, Udhampur, PO - Garhi, Udhampur-182121
ADDN/ALTN TO 4 POLE STRUCTURE WITH RMUs AT PB SUBSTATION, PB 27/28, TRANSIT MESS AND HELIPAD COLONY UNDER GE (UTILITIES) UDHAMPUR
2023_MES_629483_1
CWE/U(U)-86/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
Udhampur
As per NIT
6 documents required · 6 mandatory
₹500
GE (UTILITIES) UDHAMPUR
₹76,100
29 Jan 2024
23 Nov 2023
20 Dec 2023
23 Nov 2023
13 Dec 2023
8 Dec 2023
24 Nov 2023 - 4 Dec 2023
Amount
Supply, install, testing and commissioning of Ring maint unit of following configuration :- Make - Schneider/ABB/Siemens Source - 11 KV Amp - 630 Amps (HT) Phase - 3 Phase Breaking Capacity - 21 KA for 3 Sec Configuration - SF6 insulated/one side extensible System - Outdoor type No of ways - 5 Ways Operation - 10000 manual operation for VCB and operating sequence 0-0.3 sec co-3min-co Busbar - Copper Technical Configuration - 304 (Non-ferrite magnetic grade with stainless steel enclosure) Thickness - 2.5 mm Accessories - Manometer configuration for vacum /SF6 measurment Arrangement of system - 01 No load break as incommer( +C) & 04 No load break (Vaccum Circuit breaker module) as outgoings(+VVVV) Overall Configuration - (+CVVVV) IEC configuration - IEC-62271-100, IEC-62271-200-2003 & IEC 60694-1996. Protection Level - IP 54 with voltage Presence indication complete all as specified and directed.
Supply, install, testing and commissioning of Ring maint unit of following configuration :- Make - Schneider/ABB/Siemens Source - 11 KV Amp - 630 Amps (HT) Phase - 3 Phase Breaking Capacity - 21 KA for 3 Sec Configuration - SF6 insulated/one side extensible System - Outdoor type No of ways - 4 Ways Operation - 10000 manual operation for VCB and operating sequence 0-0.3 sec co-3min-co Busbar - Copper Technical Configuration - 304 (Non-ferrite magnetic grade with stainless steel enclosure) Thickness - 2.5 mm Accessories - Manometer configuration for vacum /SF6 measurment Arrangement of system - 01 No load break as incommer( +C) & 03 No load break as outgoings(+CCC) Overall Configuration - (+CCCC) IEC configuration - IEC-62271-100, IEC-62271-200-2003 & IEC 60694-1996. Protection Level - IP 54 with voltage Presence indication complete all as specified and directed.
Supply, install, testing and commissioning of Ring maint unit of following configuration :- Make - Schneider/ABB/Siemens Source - 11 KV Amp - 630 Amps (HT) Phase - 3 Phase Breaking Capacity - 21 KA for 3 Sec Configuration - SF6 insulated/one side extensible System - Outdoor type No of ways - 3 Ways Operation - 10000 manual operation for VCB and operating sequence 0-0.3 sec co-3min-co Busbar - Copper Technical Configuration - 304(Non-ferrite magnetic grade with stainless steel enclosure) Thickness - 2.5 mm Accessories - Manometer configuration for vacum /SF6 measurment Arrangement of system - 01 No load break as incommer(+C) & 02 No load break as outgoings(+CC) Overall Configuration - (+CCC) IEC configuration - IEC-62271-100, IEC-62271-200-2003 & IEC 60694-1996. Protection Level - IP 54 with voltage Presence indication complete all as specified and directed.
Note for item 1 to 3 : Quoted rate shall deemed to be include following - (a) Construction of plinth for Circuit breaker 1 mtr height x 1 mtr width x 075 mtr length including necessary duct for cable and required size of chequred plates and morum filling, PCC at top 10cm thick (1:2:4) and PCC foundation with 1:4:8 (square foundation) 25cm height all as per drawing provided by the department including plastering to exposed walls and white wash. Providing MS Channel on top for rolling to Breaker including chain link fencing of wire mesh 150x 100 size made out of Gl Wire of height 1.0 mtr fixed with the help of MS flat 25x6 mm and including MS angle 75x45x6mm thick Nos post by means of drilling holes at the distance of 30cm and fixed with the help of suitable nut, bolt and washer. The length of the MS angle iron not less than 2.25mtr, top of the pad to the shape of 60 degree including 3 Nos for inserting barbed wire including 03 runs of barbed wire and including provision of gate of size 1.5mx 0.9mtr made out of MS angle iron 50x 50x6 mm and MS bar 12 mm dia for meshing the gate and locking arrangements including PCC foundation 1:2:4 type B-1 for posts, 2 coats painting to steel members, complete all as specified and directed. (b) Pre-commissioning test of Circuit breaker shall be carried out by rep of accepting officer. Transportation to / fro charges required for inspection officer shall be borne by the contractor.
Providing earthing with GI earth plate electrode 600 X 600 X 6.3mm buried directly in ground (earth pit not less than 2.25m deep below ground level ) with top edge of the earth plate not less than 1.5m below ground level connected to GI strip 32 x 6mm thick for earthing lead fixed by means of nuts, bolt, washers etc connected to earth test point complete all as specified in electrical plate NO 3, including necessary excavation and earthwork in any strata of soil, comman salt, charcoal dust, 40 mm dia light grade GI pipe for protection to earth lead, GI water pipe 20mm dia with funnel & wire mesh, PCC pit with CI cover and frame etc all as specified and directed by Engineer-in-charge. Note:- All the joints shall be made with welding to get proper conductivity.
Cable jointing kit for 11 KV (Earthed) grade cable for End joint heat shrinkable type joint complete with jointing material and accessories suitable for 3 core XLPE armoured aluminium conductor cable of size 50 to 95 sqmm complete all as specified and directed.
XLPE insulated, armoured, aluminium conductor cable, 11000 volts grade, heavy duty, cross sectional area 95 sqmm, 3 core, laid in trenches/ducts/through pipe complete all as specified and directed
Excavating in trenches, not exceeding 1.5 m wide and not exceeding 1.5 m in depth; for foundation, etc. or for shafts, wells, cesspits, manholes, pier holes, for laying cables/pipes, etc. not exceeding 10 sqm on plan and not exceeding 1.5 m in depth in any type of soil and getting out soil, complete all as specified and as directed.
Returning, filling in (soil) including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick in any type of soil, complete all as specified and as directed.
Removing excavated material n exc. 50m and depositing where directed at a level n exc. 1.5 m above the starting point, complete all as specified and as directed.
Supply and lay DWC (Double wall corrugated) pipe 145 x 127 mm conforming to IS: 14930/ IS 16205 for protection of HT Cable 95 sqmm including necessary snap-fit coupler required for fixing complete all as specified and directed.
MOHAN LAL AND SONS
PROACH ASSOCIATES BUILDERS & ENGINEERS
PREM NATH KHAJURIA AND SONS
Electromechanics Engineers & Contractors
slathia construction works
FANGALIA TRADERS
HUMERS INFRATECH
stage.html
html • 0.06 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .