Loading…
Loading…
| # | Company | Status |
|---|---|---|
| 1 | Admitted-Finance 2ND FLOOR SHOP NO 303 MARUTI PLAZA RONCHI BANGAR TOWNSHIP MATHURA | MATHURA | UTTAR PRADESH | 281001 | Admitted-Finance |
| 2 | Admitted-Finance | Admitted-Finance |
| 3 | Admitted-Finance | Admitted-Finance |
Tender Value
₹2.0 L
EMD Value
₹2,000
Closing Date
28 Jul 2022, 1:00 pmClosed
EE, E400 KV S/S Division Agra South
Near Amar Ujala Press, kakraith Road Agra
For Annual Maintenance of SCADA System Installed at 400 KV GIS Sub Station Agra South Under E400 KV S/S Division Agra South
2022_UPTCL_714098_1
T-10/E_400KV_Agra_South/22-23
Open Tender
Electrical Works
Lump-sum
75 days
E400 KV S/S Division Agra South
Please refer Tender documents.
2 documents required · 2 mandatory
₹590
EE, E400 KV S/S Division Agra South
₹2,000
29 Jul 2022
11 Jul 2022
28 Jul 2022
11 Jul 2022
28 Jul 2022
11 Jul 2022
Monthly Maintenance of SCADA System : (a) Testing and rectification of CRP signals in between primary equipment like Disconnector/Earth switch, Circuit Breakers and CTs & PTs GIS Moudles from Switch Yard/ GIS Hall to SCADA HMI as per approved schematics. (b) SCADA operation checking & rectification of primary equipment like Disconnector/Earth switch, Circuit Breakers. BCU operation healthiness checking from IEDs to Primary equipment. (c) SCADA HMI soft interlocks and its logic from BCUs to each feeders in Local/Remote mode and its rectification. (d) Checking of buffered/Unbuffered Reports of SCADA to avoid interruption in SCADA system, SCADA database and its backup storage of Hot and standby SCADA HMI-1/2 will be recovered. (e) Communication System architecture and fiber optics path between IEDs/BCUs to SCADA HMI-1/2 healthiness checking include PAS/Gateway/Decoder/Ethernet switch etc., replacing the damaged/faulty fiber patch cables for smooth operation of the System. (f) Checking of events, alarm, SOE and reports of integrating system with time stamping. (g) GPS synchronization healthiness checking with BCUs/relays and rectification of fault. (h) Checking the healthiness of protocols like IEC61850, IEC60870-5-101/104, Modbus, Modbus tcp, DNP3 etc and rectification of fault. (i) General checking of printer and other peripheral devices associated with SCADA system as per the architecture/ SAS drawing and rectifying the same.
Note: All system old files and setting with SCADA editor and runtime files and software relevant to relays, license keys with its passwords will be provided by UPPTCL
TIRUPATI ELECTRICALS
SATKAR TRADERS
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .