Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L-1₹26.7 LAccepted-AOC SIMBAL CAMP WARD NO 5 NEAR GURUDWARA SAHIB R S PURA DISTT JAMMU J K 1812104 | R S PURA | JAMMU | J K | 1812104 | L-1 | Accepted-AOC Being lowest bidder | |
| 2 | L-2₹28.1 L+₹1.4 L (5.28%)Rejected-Finance | L-2 | Rejected-Finance Other than lowest bidder | |
| 3 | L-3₹28.2 L+₹1.5 L (5.66%)Rejected-Finance | L-3 | Rejected-Finance Other than lowest bidder | |
| 4 | L-4₹28.5 L+₹1.8 L (6.72%)Rejected-Finance | L-4 | Rejected-Finance Other than lowest bidder | |
| 5 | L-5₹34.5 L+₹7.8 L (29.4%)Rejected-Finance | L-5 | Rejected-Finance Other than lowest bidder |
Tender Value
Refer Docs
EMD Value
₹1 L
Closing Date
27 May 2023, 6:00 pmClosed
GE Jammu
GE Jammu c/o 56 APO Pin-900277
REPAIR AND REPLACEMENT OF LED LIGHTS, OH TANK LIGHTS AND LT DISTRIBUTION NETWORK AT MIRAN SAHIB UNDER GE JAMMU
2023_MES_592546_1
GEJC-03/2023-24
Open Tender
Electrical and Maintenance Works
Item Rate
180 days
AoR of GE Jammu
Please refer Tender Documents
8 documents required · 8 mandatory
₹500
GE Jammu
₹1 L
Yes
23 Jun 2023
1 May 2023
29 May 2023
1 May 2023
27 May 2023
15 May 2023
Amount
Taking out old / unserviceable underground LT cables and connections including pipes, bricks or precast concrete cable cover etc of any from trenches / walls / poles of any cross sectional area and removing from site complete all as specified and directed.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 120 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 150 Sq mm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 185 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 240 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 300 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 400 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 10 Sqmm, 2 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing in replacement of XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm, 2 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 35 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 50 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 70 Sqmm, 3.5 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 95 Sq mm, 3.5 core, complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing/connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 16 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Supply and fixing XLPE insulated, armoured heavy duty electric cable with aluminium conductor, 1100 volts grade, cross-sectional area 25 Sqmm, 4 core complete all as specified and directed by Engineer-in-Charge. Note: - Wherever cable fixing / connection, suitable thimble should be used as per site situation.
Excavation in trenches not exceeding 1.5 metre wide and not exceeding 1.5 metre deep any type of soil getting out and levelling of bottom surface to required level for poles / stay assembly / cable complete all as specified and as directed.
Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25m thick complete all as specified and directed.
Removing excavated material from site to a distance not exceeding 50 metre away and depositing where directed not exceeding 1.5 metre from the starting point complete all as specified and directed.
Material and labour in replacement of galvanised iron pipe light grade 80 mm bore for cable protection as a guard pipe complete all as specified and directed.
Material and labour in replacment of galvanised iron pipe light grade 50 mm bore for cable protection as a guard pipe complete all as specified and directed.
Supply and laying including replacement of well burnt old size sub class 'B' bricks laid flat with width equal to length of brick perpendicular to the direction of cable, adjacent / abutting each other in trenches over the cable for protection complete all as specified and as directed by Engineer-in-Charge.
Supplying and laying in trenches clear sand for cushioning underground cable 8 cm below and 15 cm above complete all as specified and as directed by Engineer-in-Charge.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 400 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 300 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 240 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 185 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 120 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 70 / 95 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 50 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 35 Sqmm complete all as specified and directed.
Supply and fixing in replacement unserviceable aluminium lugs / thimble of size 25 Sqmm complete all as specified and directed.
Labour for taking out all incoming/outgoing electric connection from LT pannel /starter /motor /voltage stabilizer carefully for repair to cable/rectification the fault and re-connecting in position after repair and preparation the cable and fixing complete with nut, bolts, washers for cable size 120 to 400 Sqmm including Preparation of 3.5 core cable, 4 wire each alongwith connceted items like thimble,insulation tape & will be considerable in this job complete all as specified and directed by Engineer-in-charge
Material and labour for replacment of old burnt out aluminium bus bar and connected link bar with proper colour coading with insulation tape of current rating 630/400 Amps incl replacement of old rusted nut&bolts, washers complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement unsv indicators LED set of three pieces as per existing size and sample complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement Ampere meter analog type 0-400 Amp CT with suitable set of size 96 sqmm square type flush panel mounted complete all as specified and directed by Engineer-in-charge
Supply and fixing in repair Volt meter analog type 0-500 Volt 96 sqmm square type flush panel mounted complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 3 Pole, current rating 100 Amp, thermal setting adjustable type 70%-100% rapturring capacity 16 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 3 Pole, current rating 125 Amp, thermal setting adjustable 70%-100% rapturring capacity 16 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 4 Pole, current rating 160 Amp, thermal setting adjustable 70%-100% rapturring capacity 36 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 4 Pole, current rating 200 Amp, thermal setting adjustable 70%-100% rapturring capacity 36 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 4 Pole, current rating 250 Amp, thermal setting adjustable 70%-100% rapturring capacity 36 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 4 Pole, current rating 400 Amp, thermal setting adjustable 70%-100% rapturring capacity 36 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Material and labour for replacement of MCCB 4 Pole, current rating 630 Amp, thermal setting adjustable 70%-100% rapturring capacity 50 kA at 415V,50Hz complete all as specified and directed by Engineer-in-charge
Supply and Fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 100 Amp, 415 volts 3 phase , four pole complete all as specified and directed by Engineer-in-charge
Supply and Fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 200 Amp, 415 volts 3 phase , four pole complete all as specified and directed by Engineer-in-charge
Taking down unserviceable Street/Security/flood light fitting of any type from the pole/bldg after disconnecting electric connection carefully complete all as specified and directed (Note: Repair/replacement of spares shall be measured seperately)
Supply and fixing in replacement distribution board with Supply and fix timer switches astro type (Having longitude and latitude of Indian cities in memory) 250 V single phase of 20 Amp rating with contactor fitted inside steel enclosure complete all as specified and directed by Engineer-in-charge
Supply and fixing LED street light fitting 45 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge
Supply and fixing LED street light fitting 60 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge
Supply and fixing LED street light fitting 90 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge
Supply and fixing LED street light fitting 120 Watt 230 V AC outdoor type with high pressure die cast aluminum hosing and heat resistant complete with driver, lamp bracket with impact and corrosion resistant including thermal management in multiple optics complete with IP 65/66 protection complete all as specified and directed by Engineer-in-charge
Supply and fixing LED flood light fitting of cap 200 watt incl inbuilt surge protection as per requirement LED flood light fittngs along with IP 65/66 protection complete all as specified and directed by Engineer-in-charge
Labour charges repair/maint to Old/Unserviceable LED security/Street/flood light/High Mast Light of any capacity incl taking down existing fitting from pole/Bldg for replacement of unsv driver,cable terminal block and connection wire and refixing the same in position after repair incl testing completeall as specified and directed by Engr-in-Charge.(Note: spares shall be measured and paid seperately under respective item) NOTES : (i) Sufficient Electrician and Helper shall be deputed daily to concern sub division during office hours to ascertain the repairs to be carried out for lights under his AOR. (ii) Electronic drivers, if required to be replaced shall be measured and paid separately as under relevant items of this BOQ as SUPPLY ONLY (iii) Necessary arrangements for carrying out repairs shall be under taken by the contractor.
Supply and fixing in replacement of electronic driver of cap 45 watt of existing make for LED street light fitting complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of electronic driver of cap 60 watt of existing make for LED street light fitting complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of electronic driver of cap 90 watt of existing make for LED street light fitting complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of electronic driver of cap 120 watt of existing make for LED street light fitting complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of electronic driver of cap 200 watt of existing make for LED Flood light fitting complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of 1100 Volt Arial bunched cable having three phase conductor of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 3x35 sqmm + 1 x 25 sqmm complete with dead end clamp,suspension clamp,Eye Hook ,welding and cable Jointing Kit as per site requirement with the existing LT disribution system complete all as specified and directed by Engineer-in-charge
Description all as per srl item No 61 above of size 3x 50 sqmm + 1 x 35 sqmm complete all as specified and directed by Engineer-in-charge
Description all as per srl item No 61 above of size 3x 70 sqmm + 1 x 50 sqmm complete all as specified and directed by Engineer-in-charge
Description all as per srl item No 61 above of size 3x 95 sqmm + 1 x 70 sqmm complete all as specified and directed by Engineer-in-charge
Supply and fixing in replacement of 1100 Volt Arial bunched conductor having phase conductor of multistranded compacted circular aluminium conductor screen of extruded semi conducting compound extruded XLPE insulated , insulation screen of extruded semi conducting compound over all metellic screen of copper tape extruded PVC type ST-2 sheathed twisted around bare aluminium alloy messenger generally as per IS 7098 Part-II of size 3x50 sqmm + 1x 50 sqmm ,1X 35 sqmm and 1X16 sqmm complete with dead end clamp,suspension clamp,Eye Hook ,welding and cable Jointing Kit as per site requirement with the existing LT disribution system complete all as specified and directed by Engineer-in-charge
Material and labour for road cutting, PCC hard standing as per site requirement including excavation for laying of GI pipe and making good the disturbed surfaces all as per existing surfacecomplete all as specified and directed by Engineer-in-charge .
Material and labour for PCC(1:4:8) type D-2 using 40mm graded stone aggregate as in foundation of electric poles,struts,PCC blocks etc including necessary form work complete all as specified and directed by Engineer-in-charge
Material and labour for PCC(1:3:6) type C-2 using 40mm graded stone aggregate as in foundation of assembly,bed concrete including necessary form work and fair finish to exposed surfaces without using extra cement complete all as specifieds,struts,PCC blocks etc including necessary form work complete all as specified and directed by Engineer-in-charge
Material and labour for PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of poles and similar work including necessary form work and fair finish to exposed surfaces without using extra cement complete all as specified and directed by Engineer-in-charge
Dismantling/taking up of LT unserviceable pre-stressed concrete/steel poles of any size and shape and including taking out dismantled portion of poles embeded in ground after necessary demolition of concrete foundation and making good disturbed ground surface properly and disposal thereof as directed by the Engineer-in-Charge. (Note:- Earth work for taking out of poles shall be measured and paid separately under relevant item of this Schedule).
Material and labour for Steel tubular swaged pole complete with cast iron base plate, finial taper plug, bolts, nuts and screw as specified type 410 SP-31 (9.0 meters long) incl two coats of silver paint over a one coat of redoxide paint complete with strip of black and white strops having 30 cm of width upto 1.5 mtr height from top of coping complete all as directed by Engr-in-Charge. (Excavation, foundation concrete, preservative treatment etc will be measured and paid separately)
Material and labour for Pre stressed concrete pole 9.0 meter long 102mmX172 mm at Top and 12 mm and 279 mm at bottom class 10 with strip of black and white strops having 30 cm of width upto 1.5 mtr height from top of coping complete all as specified and directed.
Dismantling of ACSR conductors or disturbed span including line spacer and keeping serviceable materials in safe custody for re-use and unserviceable materials removing from the Site(s), complete all as specified and directed.
Labour for rectification of fault related ACSR jumpers,insulators binding wire by removing old one and replacement with new wire binding or rejumber as required etc complete all as specified and directed by Engineer-in-charge NOTE: Material shall be measured and paid separately under supply only.
Supply and fixing of ACSR conductor of any size and type from over head HT/ LT poles including binding at site to insulator with suitable size of binding wire etc including taking down existing worn out old broken ACSR conductor of any size and type and length at any position from LT/HT poles complete all as specified and directed by Engineer-in-charge
Fixing only by re-straining, tightening of ACSR conductors of any size/type on HT/LT poles including necessary new aluminium binding wire for fixing with insulator/PVC sleeves for jumper etc as required complete all as specified and as directed.(Note : Serviceable ACSR conductors shall be obtained from item No. 11 here-in-before).
Material and labour in replacement of Galvanised steel wire 4.0 mm dia for continuous earth wire and Cradles hexagonal/rectangular shall be provided and securely fastened to each pole and connected with earth ordinarily and cradle guarding where reqd complete incl dismentaling existing GI wire complete all as specified and directed by Engineer-in-charge
Dismantling cross arms of MS channel or angle sections etc., and keeping serviceable materials in safe custody for re-use and/or unserviceable materials removing from the Site(s), complete all as specified and directed
Material and labour of Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections i.e M.S. channel or angle sections etc. including new nuts, bolts, washers as reqd dia/length in size, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive one primer coat of red oxide, one under coat and one finishing coat of silver paint (1st quality ) as reqd complete all as specified and directed by Engineer-in-charge
Fixing only serviceable cross arm, MS Channel, angle section obtained from item No 9 here-in-before as ordered and inclusive of one coat of aluminium paint including preparation of old steel surfaces complete all as specified and directed.
Supply and Fix in replacement of onload changeover switch AC-23 (side handle) in sheet metal enclosure of capacity 150 Amp, 415 volts 3 phase , four pole complete all as specified and directed by Engineer-in-charge
Dismantling LT Stay assembly, of any size and unserviceable materials removing from the Site(s), complete all as specified and as directed. a) Unserviceable Stay assembly shall be taken off/dismantled at Ground Level and making good disturbed ground surface. b) Earthwork for demolition of cement concrete shall be incl in quoted rate.
S & F Stay assembly with accessories and GI stay rod 16 mm dia 1900 mm long, stay wire 7/4 mm stranded galvanised including mild steel stay plate 300 mm x 300 mm x 6 mm and galvanised thimble, galvanised steel 14 mm dia 400 mm long stay bow and GI nuts, washers including loop type insulator vitreous porcelain white, brown or green big size withoverall dimensions 90 mm x 140 mm clearance of hole 25.5 mm complete all as specified and shown in electrical plate No 01 of SSR Part - I (Excavation, stay clamps and concrete work etc will be measured and paid separately).
Dismantling insulators, any type, any size and keeping serviceable materials in safe custody for re-use and/or unserviceable materials removing from the Site, complete all as specified and as directed.
Material and labour of Insulator Pin type, porcelain, vitreous, white,brown or green including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed by Engineer-in-charge
Material and labour of Insulator Pin type, polymer composit material including one galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nut, 150 mm height, 150 mm dia for 11000 volts grade complete all as specified and directed by Engineer-in-charge
Fixing only serviceable pin type porcelain, vitreous, (white/brown or green) insulator for 1100 volts grade of any type complete all as specified and directed by Engineer-in-charge
Material and labour of Insulator Shackle type, porcelain, vitreous, white,brown or green , shall be in one piece and shall have a groove on the side and a hole for a cotter pin and two galvanised bolts 12 mm dia and nuts with or without a pair of straps in size 31 x 3 mm as indicated size height 75 mm and dia 90 mm, for working pressure 1100 volts complete all as specified and directed by Engineer-in-charge
Fixing only serviceable shackle type porcelain, vitreous (white / brown or green) insulator of any size and shape for 1100 Volts grade obtained complete all as specified and directed by Engineer-in-charge
Material and labour in replacement of Earthing complete with galvanised mild steel earth plate electrode of size 600x600x6mm thick burried directly in ground earth (in vertical) earth pit not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr below ground level connected to galvanised iron or earth lead wire 4mm dia (8 SWG) by means of nut, bolt, check nuts and washer of galvanised ironl including PCC pit in PCC 1:2:4 type B-1 pre-cast RCC cover slab using reinfocement with suitable handle made of round bar, including necessary excavation and earth work in any type of soil, 20mm dia medium grade galvanised steel tube flor watering with one end fixed with cast iron funnel and wire mesh 15mm dia bore light grade galvanised steel tubing upto 5 m length for drawing earth lead wire protection, common salt, charcoal, etc complete all as shown in electrical plate No 3 of SSR Part-I and incl dismantaling and taking down old u/s complete all as specified and directed by Engineer-in-charge
Supply and fixing in repair of PVC flat fibre separator for LT line 1100 volt OH conductor 3/4/5 wire system for maintaining horizontal spacing of conductor complete with nut & bolt in a span complete all as specified and directed.
Supply and fixing in replacement of insulation Rubber matting sheet of size 1 meter x 2 meter x 10 mm conforming to ISI electric shock proof 1100 Volt grade complete all as specified and directed by Engineer-in-charge
Sarbat Construction Co
DARVESH ENGINEERING WORKS
M/S RAJ ENGINEERS
M/s. Aggarwal Engineers
M/s Shakti Electric Works
M/S ESS ESS ENTERPRISES
M/S JIWANRISAM SERVICES PRIVATE LIMITED
BMMJ TRADERS AND ENGINEERS
stage.html
html • 0.07 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .