Loading…
Loading…
| # | Company | Amount | Rank | Status |
|---|---|---|---|---|
| 1 | L1₹10.9 CrAccepted-AOC | ₹10.9 Cr | L1 | Accepted-AOC Lowest |
| 2 | L2₹11.2 CrRejected-Finance | ₹11.2 Cr | L2 | Rejected-Finance Other than lowest |
| 3 | L3₹11.3 CrRejected-Finance | ₹11.3 Cr | L3 | Rejected-Finance Other than lowest |
| 4 | L4₹11.7 CrRejected-Finance CHINAR COMMERCIAL COMPLEX THE BUND RESIDENCY ROAD SRINAGAR 190 001 | SRINAGAR | SRINAGAR | JAMMU AND KASHMIR | 190001 | ₹11.7 Cr | L4 | Rejected-Finance Other than lowest |
Tender Value
₹10.2 Cr
EMD Value
₹8.4 L
Closing Date
28 Sept 2024, 6:00 pmClosed
Chief Engineer Udhampur Zone
HQ Chief Engineer Udhampur Zone Pin-900386 C/O 56 APO
PROVN OF AVIATION HANGAR AT UDHAMPUR
2024_MES_668696_1
87900-A/E8
Open Tender
Civil Works
690 days
Udhampur
As per NIT
8 documents required · 8 mandatory
₹3,000
GE (N) Udhampur
₹8.4 L
Yes
Udhampur
17 Dec 2024
31 Aug 2024
5 Oct 2024
31 Aug 2024
28 Sept 2024
16 Sept 2024
2 Sept 2024 - 9 Sept 2024
11 Sept 2024
Amount
Sch 'A' Part - I (Building Work):-This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
Construction of Elevated Sentry Post complete all as shown on drawings and as specified.
Construction of Fire Point complete all as shown on drawings and as specified.
Construction of Block of Guard Rest Room Cum Sentry Post with toilet complete all as shown on drawings and as specified.
Construction of Block of Pump House including open platform and ramp complete all as shown on drawings and as specified.
Construction of Semi Under Ground Reservoir of capacity 25000 gallon complete all as shown on drawings and as specified.
PRE ENGINEERED BUILDING WORK (HANGAR) AND RCC FRAMED STRUCTURE ANNEXE (D/S) Design, manufacture, supply and errect Pre-Engineered Building (PEB) steel structure for hangar alongwith building Annexe D/S with RCC framed structure, complete all as specified and as shown on drawings. Note :- (i) This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only. (ii) PQC flooring including WMM, DLC, GSB, sand cushioning with polyethylene film and epoxy polyurethane floor coating in Hangar building shall not form part of lumpsum and shall be measured and paid for separately under respective items of Sch `A’/BOQ. However, surface preparation for flooring and soil stabilization for a depth of 600mm shall deemed to be includes in the lumpsum quoted. The contractors shall consider this aspect while quoting their rates.
Total Amount of Sch 'A' Part - II (Site Clearance and Site development)
Total Amount of Sch 'A' Part - III (Internal Water Supply)
Total Amount of Sch 'A' Part - IV (Internal Electric Supply)
Total Amount of Sch 'A' Part - V (Plumbing work)
Total Amount of Sch 'A' Part - VI (Protective Work )
Total Amount of Sch 'A' -VII (Area Drainage Work)
Total Amount of Sch 'A' Part - VIII (Sewage Disposal work)
Total Amount of Sch 'A' -IX (Road, Path and Culvert Work)
Total Amount of Sch 'A' -X (Chain link Fencing and Gate work)
Total Amount of Sch 'A' Part -XI ( External Water Supply Works)
Total Amount of Sch 'A' Part -XII (External Electric Supply)
Total Amount of Sch 'A' Part -XIII (Fire Fighting System)
Total Amount of Sch 'A' Part -XIV (Demolition)
Sch 'A' Part - XV (Misc Items work) Note : This Schedule is not Pre-Priced by MES and the Pre-Priced rate indicated as "Rs. 0.00" under col.5 signifies this fact only.
M & L for antistatic flooring over PQC flooring all as per following description: (a) Surface preparation:- new concrete should normally have been placed for at least 28 days and have a moisture content of less than 5%. Floors should be sound and free from contamination such as oil and grease, mortar and paint splashes or curing compound residues. Excess laitance deposits are best removed by light mechanical scabbling, grinding or grit/captive blasting follwed by vaccum cleaning to remove dust debris. (b) Anchorages:- Anchorage grooves shall be cut to a min depth and width of 2x flooring thickness to be laid at edges, bay joints, upstands, drains roadways and regular points, except on a planned copper tape path to earthing point. (c) Priming:- Providing and applying 2 pack epoxy resin primer NITOPRIME 25 for improved adhesion and corrosion protection on the acceptable substrate @ 5 Sqm/litre. Primer to air cure for 24hours before starting floor coating treatment. it must be tack free.
(d) Underlay epoxy (2mm):- Providing and laying self smoothing 3 component epoxy enderlay NITOFLOR EU 5 in 2mm thickness exhibiting following:- Compressive strength (ASTM C579):>60 N/mm2 @ 7 days Tensile strength (BS 6319 part 7):>11 N/mm2 @ 7 days Tensile modulus:>880 N/mm2(BS 6319 part 7) Flexural strength (BS 6319 part 3): 22 N/mm2 @7 days Water absorption (BS 1881 part 122): Nil Curing characterstics @ 350C Initial hardness: 16 hours Full cure: 7 days Pull of adhesion strength Crushing resistance:>2.2 N/mm2 (BS 8204 part 1) Curing characteristics @ 350C Initial hardness: 16 hours full cure: 7 days Adhesion: Greater than the tensile strength of concrete The mixed nitofolor EU5 should be spread to uniform thickness on the prepared surface using either a squeegee or a notched trowel. the subsequent use of a spiked roller, eliminates air entrainment. Overcoating of the nitoflor EU5 with any other fosroc floor system should not start until the nitoflor EU5 is at least 18 hours old, but not later than 48 hours. This shall be followed by laying of copper tape in predefined grid size based upon the floor size and connected to the earth points as per manufacturers instructions.
(e) NITOFLOR CONDUCTIVE UNDERCOAT: Supplying and applying under coat on the primer at a material consumption rate of 4.0 Sqm/litre for nitofor EPU conductive undercoat. The undercoat provides a conductive system passage to earth and correct application and strict adherence to coverage rates are critical to the final electrical properties of the completed floor. For undercoat curing to be complete, adequite ventilation and air movement are necessary. Thorough covering of earthing connections is essential. (f) TOP COAT:- Providing and applying 2mm Nitoflor EPU conductive system as a measure to control static electricity. Moreover, they provide a dense, impervious, coloured and chemical resistant floor surface which is hygienic and easy to clean nitoflor EPU conductive system consists of blended epoxy resins, curing agents, graded inert aggregates. They are epoxy polyurethane applied floor topings for use at a thickness of 2mm. When laid nitoflor EPU conductive system provides a seamless, smooth, light reflective surface. Technical Properties-specific gravity (mixed) approx 1.7 volume solids 100% Surface resistance (ASTM F150)- nitoflor or EPU conductive (25 x 10)3 - (1 x 10)6 Ohms compressive strength 50N/ Sqm @ 27 degree centigrade 7 days (BS 6319) Tensile strength -7 days (BS 6319) 10N/mm2 @ 27 degree centigrade Flexural strength -7 days (BS 6319) 25N/ mm2 @ 27 degree centigrade Pot life at 30 degree centigrade approx . 30 min Curing time at 30 degree centigrade foot traffic after 24 hrs Full traffic after 7 days
(iv) Trade names of chemical manufactured by one of the manufacturers are specified above. However, equivalent chemicals of M/S Fosroc chemicals, M/S Cipy polyurethanes Pvt Ltd, M/S Sika India Pvt Ltd, Choksey Chemicals Pvt Ltd, M/S Thermax Ltd may be used with prior approval of Accepting Officer.
200mm thick (compacted thickness) Granular Sub Base Course (GSB) Grade V in a single layer (as per Table 400-1 and 400-2 of MORTH&H specifications for Road and Bridge works) over compacted subgrade with stone aggregates by using motor grader, spreading, leveling and rolling with static roller of capacity 80-100 KN (static roller for layers upto 100mm thick only)/ vibratory roller of capacity 80-100 static wt (for layers 100-200mm thick) and consolidating to required gradient and camber complete all as specified and directed. Finished surface tolerances as per table 900-1 of MoRTH specifications for Road and Bridge works ,complete all as specified and directed.
150 mm thick (compacted thickness) Wet Mix Macadam (WMM) in two layers (Each layer of 75mm) manufactured in WMM plant. Each layer compacted separately (as per Table 400-12 and 400-13 of MORT&H specifications for Road and Bridge works), with crushed stone aggregates of specified grading, spreading and consolidated to reqd gradient and camber complete all as specified and directed. If the water absorption value of coarse aggregates is greater than 2%, the soundness test shall be carried out on the material delivered at site. Finished surface tolerances as per Table 900-1 of MoRTH specifications for Road and Bridge works ,complete all as specified and directed.
Providing and Laying Dry lean Concrete (DLC) 125mm thick having compressive strength not less than 7MPa at 07 days (para 4.1 IRC:SP:49-2014) for each consecutive group of 05 cubes. Individual strength of each cube must not be less than 5.5 MPa at 07 days (para 4.1 IRC:SP:49-2014). Size of aggregates not exceeding 26.5mm (Grading and other physical parameters as per Table 600-1 of MORTH&H specification for Road and Bridge works/ Table 1 IRC:SP:49-2014). Min cement content must not be less than 140 kg/cum (para 4.2 IRC:SP:49-2014) mixed in Batching Plant, transported to site and laid including spreading and compacting using double drum smooth wheeled vibratory rollers with 80-100KN static weight including necessary formwork, finishing etc complete all as specified and directed. Transverse joints, where required will be paid for separately ,complete all as specified and directed.
Supplying and Laying (no additional payment for overlap) 400 micron thick HDPE sheet (Virgin Quality) having minimum weight 390 gm/sqm over tack coat/sand cushion as specified in the design with overlap between adjacent strips as minimum 100mm and transverse joints at ends as minimum 150mm etc ,complete all as specified and directed.
10 mm thick sand cushion with clean river sand duly clear of residual, organic and deleterious materials spread evenly to uniform thickness laid over DLC layer. The sand cushion must not contain stones/other hard or uneven matter, complete all as specified and directed.
150 mm thick Pavement Quality Concrete (PQC) of minimum field Flexural Strength of 45 kg/sq cm, Lower control limit (LCL) at 28 days in pavement slab using min 400 kg of cement per cum as per IRC 15-2017 (only 43 grade OPC must be used in PQC) mixed with non-circular synthetic fibre reinforcement by mech means at the rate by weight of cement as specified by manufacturer per cum of PQC. The max size of aggregate in PQC must be 31.5 mm and gradation as per Table 3 of IRC:15-2017, laid spread and compacted with fixed-form paver (width to be planned as per project requirements). Note: Non-circular synthetic fibre reinforcement shall be measured & paid for separately.”
Forming 25 mm width expansion joint in concrete slab for full depth of PQC using high RPM Diamond bit cutter. The joint be cleaned and filled with pre-molded compressible polyethylene closed cell type filler board as specified and applying closed cell, medium density, crossed linked polyethylene foam backup rod of 30 mm dia, over filler board and then priming top 15 mm with approved primer and filling with polyurethane based sealant complying with BS- 5212,8S-4254 and EN 141875-2003 with minimum MAF ± 30%, applying masked tape on the edges of joints to prevent accidental spillage of sealant and removing the masking tape after filling of sealant as per the method specified by the manufacturer complete as specified and directed. The joint sealing shall be carried out by original approved applicator with sealant having 10 year performance guarantee. Work shall be carried out under recommended temperature conditions specified by the sealant manufacturer. Top- level of joint sealant should be as per application temperature conditions and season to avoid sealant extrusion/ failure, complete all as specified and directed.
Cutting of construction joints 25 mm deep and 10 mm wide using high RPM diamond bit cutter, cleaning of surface and filling with closed cell, medium density cross linked polyethylene backup rod of 12 mm dia, application of bond breaker tape on top of back up rod for complete width of the joint, priming top 15 mm with approved primer, applying masking tape on edges of joints to prevent accidental spillage of sealant and filling with polyurethane based sealant complying with BS- 5212,BS-4254 and EN 141875-2003 and removing the masking tape after filling of sealant and as specified and as per the method specified by the manufacturer, complete all as specified and as directed. Before the adjoining bay is laid. The joint sealing shall be carried out by original approved applicator with sealant having 10 year performance guarantee. Work shall be carried out under recommended temperature conditions specified by the sealant manufacturer. Top level of joint sealant should be as per application temperature conditions and season to avoid sealant extrusion/ failur ,complete all as specified and directed.
Forming dummy/contraction joint using high RPM diamond cutter with an initial saw cut of 3 mm soon after the concrete has set, upto a depth of 1/3rd to 1/4th the thickness of the slab, widening the first saw cut/- to 6 mm width and 24 mm deep from the top. Joint to be filled with closed cell, medium density, cross linked polyethylene foam backup rod of 8 mm dia for complete length of the joint, priming the top 15 mm with approved primer, applying masking tape on edges of joints to prevent accidental spillage of sealant and filling with polyurethane based sealant complying with BS- 5212,BS-4254 and EN 141875-2003. The joint sealing shall be carried out by original approved applicator with sealant having 10 year performance guarantee. Work shall be carried out under recommended temperature conditions specified by the sealant manufacturer, Top level of joint sealant should he as per application temperature conditions and season to avoid sealant extrusion/ failure ,complete all as specified and directed.
Supply only non-circular virgin synthetic fibre of 12-18mm length, specific gravity 1.34 to 1.39, UV stable, alkali resistant with equivalent dia 15-40 micron, minimum melting temperature as 2400C and minimum tensile in all types of concrete and mortars (0.25% or at the rate as per manufacturer's instructions by weight of cement) ,complete all as specified and directed.
Marking strip, straight line, zebra crossing and stop line not less than 2.5 mm thick with hot applied thermoplastic road marking paint of approved brand (white or yellow) including admixture layer of beads confirming to BS-6088 and MOST specification by using automatic mechanical road paint marking including cleaning of all dirt, scales ,oil, grease and foreign material etc. (Make Asian Paints /Shalimar /Nerolac Paints or equivalents ) ,complete all as specified and directed.
LLDPE septic tank designed to carry sewage and sludge water, comprising earth work , excavation, returning filling, disposal of surplus spoils to a distance not exc 50 mtr from starting point in any type of soil, PCC 1:4:8 type D-2 (using 40 mm graded crushed stone aggregate) in foundation, 200mm thick, vent shaft, connections etc.for 10 users (2000 litres) including all fittings, fixtures, testing on completion complete all as specified.
Construction of brick masonry valve chamber of size 1200mm x 1200mm x 1000mm (Internal dimension) with PCC 1:3:6 foundation 150mm thick, brick work 23cm thick built in CM 1:6, PCC 1:3:6 coping 50 mm thick, plastering 15mm thick in CM 1:4 to all internal and exposed surfaces including excavation earth work in any type of soil, MS sheet cover 3mm thick fixed with angel iron frame 50x50x6mm with locking arrangement embedded in PCC and painting ot MS cover with two coats of synthetic enamel paint over one coat of red oxide primer etc complete all as specified and directed.
Soakage well 3m dia and 3m deep ,excavation in any type of soil , PCC 1:3:6 brick masonary honey combed with top ring of M-25(Design Mix) including intercepting chamber and screen chamber made of brick masonary in CM(1:4), RCC cover slab of RCC M-25(Design Mix), intercepting pipe of RCC/ DWC complete filled with bricks bats, complete all as shown on drawings and as specified.
Concealed sub main wiring with two runs of 4 Sqmm ( 2x4 sqmm ) 1100 volts grade single core FRLSH PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including non-metalic PVC rigid conduit 25 mm dia ISI marked with all conduit accessories mounting on suface of walls /roofs / ceiling including cutting chasing and with one run of 4 Sqmm (1x4sqmm ) single core FRLSH PVC insulated unsheathed copper conductor cable as earth wire, complete all as specified and directed.
Single pole and neutral enclosure with a two pin and earth plug and socket complete with one single pole MCB of 16 to 32 Amps 240 volt capacity , complete all as specified and directed.
Supply, fixing and comminssioning of water cooler, fully stainless steel, electric driven single phase having approx storage and nominal cooling capacity capacity 40/80Ltr and nominal colling capacity of 40 Ltrs per hour , complete all as specified and directed.
Voltage stablizer for automatic operation, single phase naturally air cooled, indoor type and designed for input variation between 170V to 250V with output voltage stablised at 230V with accuracy of (+/-1% ) and of capacity 2 KVA , complete all as specified and directed.
Voltage stablizer for automatic operation, single phase naturally air cooled, indoor type and designed for input variation between 170V to 250V with output voltage stablised at 230V with accuracy of (+/-1% ) and of capacity 4 KVA , complete all as specified and directed.
Voltage stablizer for automatic operation, single phase naturally air cooled, indoor type and designed for input variation between 170V to 250V with output voltage stablised at 230V with accuracy of (+/- 1% ) and of capacity 5 KVA , complete all as specified and directed.
Supply and install AC in wall split unit air conditioner reversible type indoor and outdoor unit, BEE 5 star inverter type split AC with cordless remote control unit PM 2.5 filter for better indoor air quality of capacity 1.5 ton with standard accessories including MS frame work for installation of outer with all side and making required hole in wall for passing cooling pipes/cable and repair work done damaged portion of wall in CM 1:4 , complete all as specified and directed. Make:- Voltas, LG, SAMSUNG.
Supply and install AC in wall split unit air conditioner reversible type indoor and outdoor unit, BEE 5 star inverter type split AC with cordless remote control unit PM 2.5 filter for better indoor air quality of capacity 2 ton with standard accessories including MS frame work for installation of outer with all side and making required hole in wall for passing cooling pipes/cable and repair work done damaged portion of wall in CM 1:4, complete all as specified and directed. Make:- Voltas, LG, SAMSUNG.
Earthing complete with galvanised steel earth plate electrode 600mmx600mmx6mm thick buried directed in ground (earth plate not less than 2.25m deep below normal ground level) with top edge of the plate not less than 1.5m below normal ground level) connected to and including galvanised strip 32x6mm by means of bolts, nuts, check nuts and washers of galvanised iron including PCC 1:2:4 in pit, angle iron 25x25x3mm frame work with precast RCC 1:2:4 cover reinforced with 8mm dia TMT bars @ 150mm C/C both ways and 12 mm dia MS fabricated handle, medium grade GI watering pipe 20mm bore with funnel, wire mesh and light grade GI protection pipe 40mm bore upto 5m length for drawing in earth lead wire, salt, charcoal, etc. Including excavation and earth work in any type of soil, removal of surplus soil to a distance not exc. 50m complete all as shown in electrical plate No 3 of MES schedule 2009 (Pt-I) and connected to main control board all as specified or indicated including testing on completion.
Supply , installation, testing and commmissioning of 5 ton capacity EOT Crane double grider with a span 40 mtrs approx, electrically operated through pendant push botton station floor operated type having hook height of 8 mtrs approx, trolley with frame crab buffer gears with gear boxes shafts rope drum rope sheaves wire rope wheels lifting hook plant from on one side of the crane brakes motors limit switches control panel pendant push button station micro speed arrangement wiring etc complete all as specified. (a) Capacity 5 Ton (5000 Kgs) (b) Overload capacity 25% (c) cass duty, II indoor type (d) Lift- 4-7 Mtrs approx (d) Hoisting speed 3 mtr per/min with VVVF Drive (e) CT Speed 15-20 mtr per/min with VVVF Drive (f) LT Speed 15-20 mtr per/min with VVVF Drive (g) Operation Pendant push button from floor (h) Hoisting motor 7.5 HP (Flame proof crane duty motor) (j) CT motor 2 HP (Flame proof crane duty motor) (k) LT motor twin drive 5 HP (2 Nos) (Flame proof crane duty motor) (l) Wire rope 12 mm x 4 Falls , usha martin (m) Main grider box type
Note:- The EOT crane shall also be provided with suitable capacities and no of squirel cage motors including starters for main hoist -01 nos, cross travel - 01 no, long travel-02 with suitable VVFD drive, suitable control panel box including MCB/contactor/overload realy, push buttons station etc. Crane shall also be provided with suitable hydraulic thruster type breaking system for main hoist cross travel and long travel. Drum couplings with suitable dia wire ropes of min tensile grade of suitable N/sqmm connected with ''C'' shank type hook with safety latch shall be provided. Wheel -04 Nos, 200 mm dia for long travel with safety latch shall be provided. Crane has to be provided with two coats of zinc chromite followed by two coats of golden yellow synthetic enamel paint. Note: Any other item like LT cable of suitable size from control panel to bus bar of crane in steel cable tray etc required for smooth & efficient operation of the crane will be part of the item and no extra amount will be paid on this account.
Supply & fix air compressor 500 ltr tank mounted on wtih 10 HP three cylinder , pressure switch, dry type suction air filter with silencer, auto starts and auto control , V-belt drive arrangement, air receiver tank,Auto cut Switch, safety valve, Delivery valve, pressure Gauge & t/p electric Motor etc all as specifed as below:- (a) Bore and stroke - 5'' & 2/3/4x3/1/2'' (b) Piston displacement - 37.8 CFM (c) Free air delivery - 30 (d) Maximum working pressure - 12.3 KG (e) Regulation - Auto start and Stop (f) Drive HP - 10 HP (g) No of cylinders - 2 (h) Air receiver (liters) - 500 Ltrs
Supply, erection and commissioning of 'heavy grade' MS ERW pipes with all fitting such as bends ,reducers, tees flanges, tapers etc. laid in trenchor on walls of size 80mm dia as per IS-1239, thick ness 6 mm ,complete all as specified and directed .The rates shall include the cost of consumables for cutting and welding, anticorrosive bitumastic paint and wrapping with polythene sheet based pipe coats of 4mm thick for under ground pipe/painting with coat of red oxide and two coats of sythetic enameled paint of post office red colour as required. complete all as specified and directed by Engr-in-Charge
Supply, erection and commissioning of 'heavy grade' MS ERW pipes with all fitting such as bends ,reducers, tees flanges, tapers etc. laid in trenchor on walls of size 40mm dia as per IS-1239, thick ness 6.0mm ,complete all as specified and directed .The rates shall include the cost of consumables for cutting and welding, anticorrosive bitumastic paint and wrapping with polythene sheet based pipe coats of 4mm thick for under ground pipe/painting with coat of red oxide and two coats of sythetic enameled paint of post office red colour as required. complete all as specified and directed by Engr-in-Charge
Supply, erection and commissioning of 'heavy grade' MS ERW pipes with all fitting such as bends ,reducers, tee flanges, tapers etc. laid in trench or on walls of size 25 mm dia as per IS-1239, thick ness 6.0mm ,complete all as specified and directed .The rates shall include the cost of consumables for cutting and welding, anticorrosive bitumastic paint and wrapping with polythene sheet based pipe coats of 4mm thick for under ground pipe/painting with coat of red oxide and two coats of synthetic enameled paint of post office red colour as required. complete all as specified and directed by Engr-in-Charge
Cutting of existing cast iron pipes upto 150mm bore in position for new connection by inserting of new tees all as specified and directed (Tee, lead joint, excavation and earth work shall be included in quotal rates).
Cast iron non return sluice valve of size flanged of class 1.0 PN, 80 mm dia complete all as specified and directed by Engr-in-Charge
Supply and fix cast iron flanged sluice vlave PN 1.6 ISI marked (ISI No. 14846) complete with opreting while of size 100 mm dia.
Supply and fix cast iron flanged sluice vlave PN 1.6 ISI marked (ISI No. 14846) complete with opreting while of size 150 mm dia.
Gun metal gate valve with iron wheel head screwed both ends for iron pipe 40 mm dia complete all as specified and directed by Enge-in-Charge
Gun metal gate valve with iron wheel head screwed both ends for iron pipe 25 mm dia complete all as specified and directed by Engr-in-Engr
Aviation obstruction light red colour 3 watt LED type filament less bulb complete including strandard fixing arrangement including necessary nut, bolts, washers, clamps etc complete all as specified and directed by Engr-in-Charge. Make:- SHYAAM CAT NO SSPL/1251 or equivalent make approved by Accepting Officer.
Flameproof / weatherproof wall mounted fan AC single phase 230 V, 50 Hz, 24” , motor rating 0.25 HP ,1440 RMP, aluminium Die cast LM-6 materil, suitable for Gas group IIA, IIB, and Class Zone 1 & 2 approved and certified by CIMFR Dhanbad,PESO (CCOE) Nagpur, 180 degree rotation and mounting assembly including fixing of wall mounted fan at a suitable height with grounting of nut and bolts complete all as specified and directed by Engr-in-Charge. Make :- SHYAAM CAT No SSP/MT/140 or equivalent make approved by Accepting Officer.
Flameproof / weatherproof Padestal Fan AC single phase 230 V, 50 Hz, 24” , motor rating 0.25 HP ,1440 RMP, aluminium Die cast LM-6 materil, suitable for Gas group IIA, IIB, and Class Zone 1 & 2 approved and certified by CIMFR Dhanbad,PESO (CCOE) Nagpur with adjustable height suitable for 180 degree roatation complete all as specified and directed by Engr-in-Charge. Make :- SHYAAM CAT No SSP/MT/140 or equivalent make approved by Accepting Officer.
Flameproof / weatherproof Exhaust Fan with Louvers AC single phase 230 V, 50 Hz, 24” , motor rating 0.5 HP ,1440 RMP, aluminium Die cast LM-6 materil, suitable for Gas group IIA, IIB, and Class Zone 1 & 2 approved and certified by CIMFR Dhanbad,PESO (CCOE) Nagpur complete with louver heaving aluminium/sheet metal flap with thickness not less than 1.00 mm and mounting assembly including fixing exhaust fan with grounting of nut and bolts complete all as specified and directed by Engr-in-Charge. Make :- SHYAAM CAT No SSP/MT/140 or equivalent make approved by Accepting Officer.
Earthing complete with GI earth plate electrode 600mmx600mmx6mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below Normal ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. GI plate connected with galvanised earth lead wire 4.0mm dia by means of GI nuts, bolts and washers of galvanised iron or steel all as shown in electrical plate no.5 connecting to earth test point all as specified or indicated including testing on complition with following:- (a) Test point GI wire 4mm dia . (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (d) Angle iron frame made of 40x40x4 mm angle iron for 30x30 mm PCC pit for holding the pit cover.
(e) Multi-functional digital meter EM 6400 class 0.2 for current, voltage, power factor, KVA, KVAR, Frequency KWHR and maximum demand recording and indicating. (f) LED indicating lamps, Breaker On Red, Breaker Off Green, Spring charged, trip circuit healthy, Auto trip indicator, RYB phase indications. (g) Switch for closing/tripping of VCB (h) Heater with switch, thermostat and illumination. (j) One analog type Ammeter 0-60 Amps range CT operated 96x96 mm square flush type (k) 01 No shunt trip coil and closing coil 110 V DC (l) Power pack unit 24 volts DC with dry rechargeable batteries complete (m) Mechanical and Electrical interlocking with existing system (n) Degree of protection-IP56 (o) Paint shade-RAL 7032 (p) Acessories- (i) Push button for trip circuit healty check (ii) Trip neutral close switch (iii) Local remote switch (iv) Panel illumination lamp with switch (v) 3 Pin plug with switch (vi) Push button for emergeny trip (vii) Push button for alarm accept (q) Auxillary power supply system of panel complete with maintainance free lead acid battery bank, mounted on 40x40x5 mm MS angle iron rack and provided with connector etc complete in all respect with installed capacity 24 volts jDC 2 Nos each of 12 volts 100 AH including battery charger all as per standard specification suitable for 2x24 volts battery with DC amp meter, voltmeter, switches On/Off, trickle/Boost and copper cable connection upto panels etc
Supply and fix vaccum circuit breakers of capacities 630 Amps suitable for incommer bus couple HT 11 KV 3 phase 50 Hz indoor type totally encloused metal clad switch gear complete with vaccume circuits breakers having rupturing capacity 300 MVA overload and earth fault protection connected annuciator panel 12 window type 18.25 Ka/3 sec draw out type conforming to IEC 62271/100/102/200IS conforming to endrance equal to 1000 operatins IS standards to match both manufacturised spring charges mechanism operated on 230 volts AC complete all as specified and directed by Engr-in-Charge
Supply and fix HT XLPE insulated armoured aluminium conductor cable 11000 volts grade heavy duty cross sectional area 120 sq mm 3 core laid in trenches/ducts through pipe and testing complete all as specified and directed by Engr-in-Charge
Cables joining kit for 11 KV grade cable for outdoor termination heat shrinkable type joint complete with joining material and accessories suitable for 3 core XLPE armoured conductor cable of size 120 sq mm complete all as specified and directed by Engr-in-Charge
(e) Multi-functional digital meter EM 6400 class 0.2 for current, voltage, power factor, KVA, KVAR, Frequency KWHR and maximum demand recording and indicating. (f) LED indicating lamps, Breaker On Red, Breaker Off Green, Spring charged, trip circuit healthy, Auto trip indicator, RYB phase indications. (g) Switch for closing/tripping of VCB (h) Heater with switch, thermostat and illumination. (j) One analog type Ammeter 0-60 Amps range CT operated 96x96 mm square flush type (k) 01 No shunt trip coil and closing coil 110 V DC (l) Power pack unit 24 volts DC with dry rechargeable batteries complete (m) Mechanical and Electrical interlocking with existing system (n) Degree of protection-IP56 (o) Paint shade-RAL 7032 (p) Acessories- (i) Push button for trip circuit healty check (ii) Trip neutral close switch (iii) Local remote switch (iv) Panel illumination lamp with switch (v) 3 Pin plug with switch (vi) Push button for emergeny trip (vii) Push button for alarm accept (q) Auxillary power supply system of panel complete with maintainance free lead acid battery bank, mounted on 40x40x5 mm MS angle iron rack and provided with connector etc complete in all respect with installed capacity 24 volts jDC 2 Nos each of 12 volts 100 AH including battery charger all as per standard specification suitable for 2x24 volts battery with DC amp meter, voltmeter, switches On/Off, trickle/Boost and copper cable connection upto panels etc
Supply, erecting and fixing steel tubular swaged poles type 410 SP-55, (11 meter long), complete with cast iron base plate, final taper plug, bolts, nuts and screws as specified including painting with two coats of aluminium paint over one coat of red oxide primer and 06 Nos bands/ straps with white and red post office box colour (30 cm wide each) synthetic enamel paint at a distance 30cm from plinth block and numbering of poles with black synthetic emamel paint in 2.5 cm height including black bitumineous paint two coats on steel surface embedded in concrete foundation complete all as specified and directed. (Excavation and earth work, PCC foundation concrete shall be measured and paid separately).
Note: 1. Minimum height of panel from floor level shall be 450 mm. Platform shall be made out of PCC 1:2:4 type B-1 using 20mm graded stone aggregate & external surface shall be finishedeven and smooth with 15mm thick cement plaster in CM (1:4) finished even & smooth using extra cement & finally applied with three coats of white wash as directed by Engineer in charge. 2. Drawing of Panel shall be got approved by GE/ Engineer in Charge before fabrication.
Supply ,Installation ,testing and commissioning of foam monitor system for hangar alongwith 50 Ltr (AFFF) Chemical can with 50mm dia suction pipe and valve complete all as specified and directed by Engineer- in- Charge.
Supply and fix lightining arrestor (HT 11KV) Expulsion type complete with all fitting, transmission class, discharge capacity 65 Kilo Amp.Complete all as specified and directed.
Pin Type Porcelain viterous, white, or green insulator including one galvanised mild steel spindle, two galvanised iron washer and one nut 150mm hight, 150 mm dia suitable for 11000 Volt Complete all as directed by engineer-in- charge.
Supply and fix HT 11 KV, out door type gang operated air break switch suitable for horizontal or vertical mounting fixed type complete with 12 insulatores of rating upto 200 Amps complete all as specified and directed Gange operated air break switches (swing out expulsion fuse isolator) rated upto 200 Amps as indicated. They shall be three pole type ,gange opreted. suitable for both horizontal and vertical mounting with the following components (a) channel bases for mounting base for post pad insulatore. (b) operation mechanism complete with 5/6 m long operating pipe phase coupling shaft, operating handle with padlock arrangement but without padlocks. complete all as specified and directed..
HT 11 KV outdoor type gang operated air break switch suitable for horizental/vertical mounting fixed type complete with 12 insulator of rating upto 400 Amps.Gange operated air break switches (swing out expulsion fuse isolator) shall be of 11KV, rated upto 400 Amps as indicated. They shall be three pole type ,gange opreted. suitable for both horizontal and vertical mounting with the following components-(a) channel bases for mounting base for post insulth pad insulatore. (b) operation mechanism complete with 5/6 m long operating pipe phase coupling shaft, operating handle with padlock arrangement but without padlocks. complete all as specified and directed.
Supply, installing, connecting, commissioning and testing of energy efficient transformer (level 3 of IS 1180) of capacity 250 KVA outdoor type powder coated step down 11/0.433 KV, core type oll emerssed copper wound, natural oil cooled with external cooling tubes, having three phase 50 hz, AC supply, DYN-11 design, offload tap changer on HD side to vary secondary voltage± 7.5 % in steps 2.5 % as per IS 1180 (PT-I to III) with all standard accessories including HT and LT bushing LT box on LT side, including inbuilt protection and first filling of transformer oil (of die electric strength not less than 50 KV) up to required level in conservator tank with cover boxes, the dial type thermometer, rollers, stop, taps, breather with silica gel, conservator tank, level indicator, etc. complete all as specifed and directed by Engr-in-Charge Note:- (i) The transformer oil shall be fresh and approved certificate from manufacture shall be obtained by the contractor and furnished to GE, the copper shall be 99.97 % purity and approved certificated from manufacture shall be obtained by the contractor and furnished to GE. (ii) Pre- commissioning, inspection of transformer shall be carried out by rep of Acceptng Officer and T&P for the inspection shall be arranged by contractor, cost of the T&P etc for testing shall be deemed to be included in the unit rate. (iii) Provision of 04 nos of rubber mats synthetic 2mtr x 1 mtr x 0.5 mtr at near the surface of plinth/plateform of transformer shall be deemed to be included in the unit rate. (iv) After completion of work all T&P used for opening, handling of transformer shall be handed over to site incharge all as directed by the Engr-in-Charge
Construction of plateform for transformer 2 mtr height x 2.5 mtr width x 2.5 mtr length including morum filling and PCC at top 10 cm thick (1:2:4) and PCC foundation with 1:4:8 (80 cm width x 2.7 mtr length in squre foundation 25 cm height all as per drawing provide by the department including plastering to exposed wall and white wash. Provinding MS Chanel on top of size 75 x 40 x 08 mm of 1.5 mtr in length for rolling to transformer including chain link fancing of wire mesh 150 x 100 size made out of GI wire of height 1.5 mtr fixed with the help of MS strip 25x6 mm including MS angle 75x45x6mm thick nos post by means of drilling holes at the distance of 30 mtr and fixed with the help of suitable nut, bolt and wahsers. The length of MS angle iron not less than 2.25 mtr, top of pad to the shape of 60 degree including 3 nos for inserting barbed wire 0.3 runs of barbed wire and including provision of gate of size 1.5 mm into 0.9 mtr made out of MS angle iron 50x50x6 mm and MS bar 12 mm dia for meshing the gate and locking arrangement including PCC foundation 1:2:4 type B-1 for posts complete all as specified and directed by the Engr-in-Charge shall deemed to be included in the unit rate
Supply,installing, commissioning & testing of Diesel Engine driven Generator set of 160 KVA with AMF panel complete with suitable acoustic Enclosures all as per confirming to the latest CPCB norms guide lines CPCB IV +, 50 cycle per second with 0.8 power factor, engine as per ISO8528-5 G2 and alternator as per IS/IEC60034-1 complete.The alternator of rating 160 KVA of Generator set shall be directly coupled with Diesel Engine mounted on common base plate with alternator and all as specified and comprising of the following :- Engine Diesel engine shall be water cooled, 6 cylinder in-line 1500 rpm with maximum out put of suitable BHP at 1500 rpm 160 KVA alternator with standard accessories such as start/stop switch, self starting system, oil termp gauge, rpm meter, hours meter, oil pressure gauge, ammeter, high coolant temp gauge mounted on common base frame with silencer accessories and MS fuel tank for 12 hours continuous running fuel capacity built-in-the accoustic enclosure with vinration pads, 2x12V DC battery with battery charge alternator complete Alternator. Alternator assembly, brushless, 415V, AC 50 Hz, 3 phase, 4 wire type, confirming to IS/IEC60034-1, rated for continuous output of 160 KVA, PF 0.8, 1500 RPM insulation class 'H' enclosure SPDP (IP 23), self existing and self regulated with AVR for +/- 1% voltage regulation coupled directly with prime mover with flexible coupling . (Note :- The alternator is capable of developing rated output & able to take 10% overload for one hour at every 12 hrs of operation)
Accoustic enclosure:- Accoustic enclosure should be made up of 1.2mm thick CRCA sheets and structural/sheet metal, base frame. The walls of the enclosure shall be insulated with fire retardant foam so as to comply with the norms of 75 DB at 1 mtr sound levels specified as per latest CPCB (testing as per ISO 8528). The enclosure should have following features. (i) Compact, modular construction and sleek design with low noise level 75 DB, at a distance of 1 Mtr from canopy in free field conditions. (ii) Soundproof, weather-proof and environmental friendly silent set. (iii) Steel outer construction with 1.2 mm CRCA sheet with heavy-duty fabricated base frame and inbuilt fuel tank. (iv) Illumination arrangement isndie the canopy. (v) Four point lifting for easy handling. (vi) CRCA should be powder coated with UV resistant power coating. (vii) Fuel filling point inside canopy.
Control Panel (AMF Panel) (i) Automatic main faliure contactor based of suitable cap, control panel fabricated out of sheet steel angle, iron structure, acid treated for anti-corrosion, floor mounting, cubicle pattern, powder coated dust and vermin proof, complete with iternal wiring and with the followings: (ii) 1 x Genset controller - Procom/Depse/PS0602 (iii) 3 x Current Transformers of suitable rating - Kappa/Std (iv) 2 x Indicating lamps ''SET ON''/''LOAD ON'' (v) Bus bar with suitable capacity with incoming/outgoing terminals (vi) Digital combined volt, Amp, KW and Frequency meter (vii) 2 x Earth studs (a) Material and labour for making PCC foundation of DG set size as per manufacture recommendation (viii) Electronic governing (ix) MCCB of suitable rating with short circuit protection as per manufactures (x) Electrical parameter: Phase voltage, line current, frequency, average voltage, average current, KW, KWH, KVA, KVAR, power factor, earth fault current (xi) Mechanical parameter: Lube oil pressure coolant, temp, Engine speed fuel status, engine run hours, battery voltage. xii) Protections : (a) Electrical protections : Under/over voltage, Under/over requency, Phase failure, Pahse sequencer reverse, over current, over KW. (b) Mechancial Protections : Under/over speed, low tube oil pressure, High engine coolant temp, Low fuel level alarm, Start/stop fail, Charging alternator fail.
Note:- (i) DG Set should be sound proof as per latest policy (ii) First filling of engine oil and fuel, coolant should be arranged by the contractor for testing of DG Set (iii) Engine, alternator test certificate and warranty certificate shall be provided by the contractor. (iv) Engine operator/maintenance & spare manual shall be given to department (v) OEM certificate shall be given by the contractor (vi) Tools of DG set shall be supplied the contractor FOUNDATION DG Set shall be installed on new foundations block as per manufacturers recommendations including excavation works PCC etc for foundations, provision of cable ducts, making good any demage to exisitng structure, fuel piping from fuel tank to generator set with medium grade GI tubing and cold water piping system ( Medium grade GI tubing from nearest water point to radiator of engine with brass tap and stop cocks and fittings complete connecting the existing earthing strips to control panel, DG set and generator.
Supply and installation, testing and commissioning of Cubical housing ' KIOSK ' type LT pannel board (Approved by CPRI ) , outdoor factory made, totally enclosed dust and vermin proof openable from both ,front and rear side and made out of 3.15 mm thick CRCA sheet with angle iron frame of angle size 50mmx50mmx6mm having treated with MSR solution for anti corrosive treatment and apply spray paint with two coat of sythetic enameled paint over coat rear hinged doors shutters with godrej patten lock with 2 No. keys ,earthing strips at rear side , bottom detachable glande plate complete witch suitable size zink plated and passivated nut ,bolt ,spring and washers . The cabinet and all members chamically treated as MSR solution for anti corrosive treatment and apply spray paint with two coat of sythetic enameled paint over acoat of red oxide primer . the pannel suitable for 415 volts, 50Hrz ,Three phase ,4 wire system and internal connection should be provided with aluminium bus bars of suitable size and mounted on PCC (1:2) type B-1 including necessary foudation works and and legs pannel shell be fixed 40 cm below & 40 cm above from PCC plateform complete as specified and as directed with and including the following:- Pannel comprising the following as given below:- a) Incoming :- MCCB 4 pole, 630 amps, 415 volt, 50 HZ , with adjestble thermal magnetic release,50KA, manual fixed type - 01 No.
Supply and installation, testing and commissioning of Cubical housing ' KIOSK ' type LT pannel board (Approved by CPRI ) , outdoor factory made, totally enclosed dust and vermin proof openable from both ,front and rear side and made out of 3.15 mm thick CRCA sheet with angle iron frame of angle size 50mmx50mmx6mm having treated with MSR solution for anti corrosive treatment and apply spray paint with two coat of sythetic enameled paint over coat rear hinged doors shutters with godrej patten lock with 2 No. keys ,earthing strips at rear side , bottom detachable glande plate complete witch suitable size zink plated and passivated nut ,bolt ,spring and washers . The cabinet and all members chamically treated as MSR solution for anti corrosive treatment and apply spray paint with two coat of sythetic enameled paint over acoat of red oxide primer . the pannel suitable for 415 volts, 50Hrz ,Three phase ,4 wire system and internal connection should be provided with aluminium bus bars of suitable size and mounted on PCC (1:2) type B-1 including necessary foudation works and and legs pannel shell be fixed 40 cm below & 40 cm above from PCC plateform complete as specified and as directed with and including the following:- Pannel comprising the following as given below:- a) - MCCB TPN 160 amps, 415 volt, 50 HZ , with adjestble thermal magnetic release,50KA, manual fixed type - 01 No. Incoming
Supplay laying & testing cable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 150 sqmm, 3 core laid in trench complete all as specified and directed.
Supplay laying & testing cable HT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 11000 volts grade of size 95 sqmm 3 core laid in trench complete all as specified and directed.
Supplay laying & testing cable LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 1100 volts grade of size 240 sqmm 3.5 core laid in trench complete all as specified and directed.
Supplay laying & testing cable LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 1100 volts grade of size 120 sqmm 3.5 core laid in trench complete all as specified and directed.
Supply laying & testing cable LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 1100 volts grade of size 95 sqmm 3.5 core laid in trench complete all as specified and directed.
Supply laying & testing cable LT XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured electric power (heavy duty) with stranded aluminium conductor, 1100 volts grade of size 16 sqmm 4 core laid in trench complete all as specified and directed.
100 mm bore GI pipe medium grade with all necessary fittings like bend tees, elbows, flanges, reducers, gasket, nuts and bolts etc welding as required of pipe complete with necessary standard clamps structural steel support including PCC work for pipe line support//alignment wherever necessary as required/directed at site complete all as specified and directed.
Chemical earthing complete with Copper earth plate electrode 90cmx60cmx5mm thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below Normal ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. Copper plate connected with copper earth strip 32x6 by means GI nuts, bolts and washers of galvanised iron or steel all as shown in electrical plate no.5 connecting to earth test point all as specified or indicated including testing on complition with following:- (a) Test point Copper Strip 32x6mm. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (d) Angle iron frame made of 40x40x4 mm angle iron for 30x30 mm PCC pit for holding the pit cover. (e) Excavation and earth work in any type of soil,charcoal dust and salt,light grade GI watering pipe 20mm bore with funnel and wire mash and medium grade GI protection pipe bore and copper strip up to main earthing test point. All are as specified and direcded.
Elevated type omni- directional taxiway light fixture (7/10 W, 2 cd) complete, bule/yellow colour connected secondary lead i/e supply of LED lamps, and other standard accessories etc complete all required. The fitting arangement sahll be confirm to relevent standards and specifications as per the requirements
Supply and fixing 4 sqmm 2 core PVC insulated PVC sheathed, AFL secondary lead made out of unarmoured copper conductor 600V/1100V grade cable for connection to airfield light fixture as specified in particular specification etc complete as required
Cable jointing kit for 5/6 KV (Earthed) grade cable for outdoor termination heat shrink type joint complete with junction box in cc foundation with jointing material and accessoreies suitable for mulitstranded XLPE armourd coper conductor cable of size 6 sqmm complete as specified
M&L fix insulation for controler box with rubber gaskit suitable for housing of transofrmer 330 mm dia with 06 holes for single IT inculding cable connection continuity test and tapping joint completor allas required and as directed at site
M&L 15W (Taxi an dispersal light), 5KV, 50Hz individual ;amp series type isolating transformer encapsulated in TPR/TPE with primary and secondary connection leads complete and confirming to tenders technical specification, terms & conditions etc complete as required (for taxi and dispersal light)
Threeshold cum LED red colour obstruction light 30 watt V Complete All as Specified and directed.
Supplying, installation, testing and commissioning of UPS 30 Min back up single phase AC 5KVA intelligent, True Online UPS system input 160 to 260V and output 230 +/- 1% of with EP 26-12 SMF battery - 15 Nos battery with M S rack alongwith inlerlinks complete all as specified and directed.
Galvanised steel wire 6 SWG with suitable size of HDPE/GI pipe buried in ground alongwith UG cable in direct ground/trench etc. complete all as specified and directed.
Earthing complete with Copper earth plate electrode 60x60cmx3.15 thick burried in ground vertically to a depth not less than 2.25meters below ground level with top edge of the earth plate at a depth not lesss than 1.5 meter below Normal ground level, earth plate surrounded 15cm thick layers of common salt and charcoal dust starting from ground below 15 cm of earth plate and up to 15 cm above the same. Copper plate connected with copper earth strip 20x3mm by means nuts, bolts and washers of galvanised iron or steel all as shown in electrical plate no.5 connecting to earth test point all as specified or indicated including testing on complition with following:- (a) Test point Copper Strip 20x3 mm size. . (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh embeded in floor of PCC earth pit. (GI Funnel should properly tightned on GI watering pipe and embeded in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (d) Angle iron frame made of 40x40x4 mm angle iron for 30x30 mm PCC pit for holding the pit cover. (e) Excavation and earth work in any type of soil,charcoal dust and salt,light grade GI watering pipe 20mm bore with funnel and wire mash and medium grade GI protection pipe bore and copper strip up to main earthing test point.
LED type aerodrome beacon (12W, 2500 CD) light.Complete All as Specified and directed.
MV Panel 415 V wire system with incomer bus bar outgoing switch for supply to the AGL equipment (I) 200A, 4P MCCB - 02 Nos incoming (II) 200 A, 4P MCCB-01NOs for bus coupler (III) Outgoing 30A3pole MCCB -10Nos outgoing (IV) 10A,2pole MCB 4 NosA
M&L for Flame proof switch socket and plug combined in LM-6 240 Volt 50Hz 16 Amps certified as flame proof by CMRS Dhanbad suitable for group IIA, and IIB as per IS-2148 of 1981, degree of protection IP-65 as per IS-2147 of 1962, cable entry 02 Nos top and or bottom 3/4" light gray in LM-6 construction complete all as specified and directed. Make : SHYAAM CAT No SSPL/2C/1010 OR equivalent /FLEXPRO/SUDHIR Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
M&L for Flame proof switch socket and plug combined in LM-6 (4P+E) 32 Amp 5 Pin certified as flame proof by CMRS Dhanbad suitable for group IIA, and IIB as per IS-2148 of 1981, degree of protection IP-65 as per IS-2147 of 1962, cable entry 02 Nos top and or bottom 3/4" light gray in LM-6 construction complete all as specified and directed. Make : SHYAAM CAT No SSPL/2C/1010 OR equivalent /FLEXPRO/SUDHIR Note. The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
M & L, for flame proof rotary switch, LM- 6 suitable for 16A DP for three light fittings, earthing external 2 nos, and internal – 1 no, 2 nos ¾” ET entry, hardware in Al. Die Cast with anti corrosive epoxy powder coated with protection IP-65, equipment standard as per IS – 2148/81 along with cable glands & dummy plug suitable for gas groups IIA IIB, approved by CCE and certified by CMRI complete all as specified and directed.
M & L, flame proof 4 way terminal strip 15A junction box in cast aluminium LM-6 material, size ¾” ET, 100mm dia, with 6 nos, 4 Sq mm terminals with flanged cover, earthings external 2 nos and internal 1 no, 2 nos ¾” ET entry, hardware in Al. Die Cast with anti corrosive epoxy powder coated with protection IP-65 equipment standard as per IS, alongwith cable glands & dummy plug suitable for gas group IIA IIB certified by CIMFR Dhanbad & PESO Nagpur complete all as specified and directed. Note. The rate quoted to be inclusive of cable gland , dummy plug and brackets made of MS steel of suitable size for the above fittings.
S & F, Flame proof - weather proof LED light fixture multi LED typy 220-240V AC 200 Watt, 100 lumens per watt surge protective 4KVA, LED driver Al.die Cast LM6 suitable for gas group IIA,IIC & IIC complete with as per all as specified and directed. Make:- Cat Part No. SHYAAM -SSPL/1251 or equivalent make approved by Accepting Officer.
S & F Flameproof/Watherproof distribution panel Ai die cast LM-6 Exd board for zone 1 & 2 group IIA IIB FL MCCB,4P 125A as incoming and MCB 32-63 Amp TPN/4P - 05 Nos and MCB, 1P, 6/16A -15 Nos MCB outgoing with required number of terminals of elemex clip on type and required nos of cable entries as bottom wall mounting frame alongwith cable glands with anti corrosive epoxy powder coated, hardware in stainless steel (SS-304) with protection IP-65 equipment standard as per IS, certified by CIMFR Dhanbad & PESO Nagpur complete all as specified and directed. Note: The rate quoted to be inclusive of brackets made of MS steel of suitable size for the above fittings.
Mechanical foam Extinguisher 9 Lts IS : 15683, complete all as specified and directed.
Dry Cheminac Power (ABC) Extinguisher 9 Kg IS : 15683, complete all as specified and directed.
Wheeled Dry Chemical powder Extinguisher 25 Kg Cap IS : 16018, complete all as specified and directed.
Wheeled Mechanical foam Extinguisher 45 Ltr IS : 16018, complete all as specified and directed.
Wheeled CO2 Extinguisher 22.5 Ltr Cap IS : 16018, complete all as specified and directed.
Fire Extinguisher CO2 type 3 Kg Cap light Wt Squeese Grip type, complete all as specified and directed.
Water CO2 Extinguisher Stored pressure type 9 Lts, complete all as specified and directed.
Supply and install Fire bucket of 24 guage, galvanised steel sheet, bucket shall be round bottom shape, fire bucket stand & suitable MS suppots & painted white inside and red outside and black on top dome with letter FIRE in clack and gold with wall mounted bracket and screws. (01 sets-2 Buckets & stand) as archt.
Fire Beater as per standard size, Complete all as specified and directed by Engr-in-Charge
Fire Hook as per standard size, complete all as specified and directed by Engr-in-Charge.
150mm dia flanged end basket with Foot valve conforming to IS 4038, Stainer fabricated from 16 gauge brass sheet with 3mm slots, made from MS body with bottom and top removable flanges with nuts, bolts etc complete including joints and jointing materials as per site requirement complete all as directed by Engr-in-Charge.
100mm dia flanged end basket with Foot valve conforming to IS 4038, Stainer fabricated from 16 gauge brass sheet with 3mm slots, made from MS body with bottom and top removable flanges with nuts, bolts etc complete including joints and jointing materials as per site requirement complete all as directed by Engr-in-Charge
Point wiring for One light/fan point controlled by one way switch 5 Amp with 1.5 Sqmm single core multi standed copper conductor FRLSH insulated and unsheathed heavy duty cable in colour code including unaction earth wire with cable of size 1.5 sqmm copper conductor flexible FRLSH insulated drawn into and including concealed in ERW steel conduit of not less than 20mm dia and1.5mm wall thickness ISI marked terminated into annealed steel terminal boxes including modular plate and cover for mounting modular switch/ socket switches, sockets, fan regulators etc complete all as specified and directed by the Engr-in-charge.
All as per Srl item No 16.15 above but for 3/5 Pin socket outlet 5 Amp on independent board.
All as per Srl item No 16.15 above but for 3/5 Pin socket outlet 5 Amp on same board.
All as per Srl item No 16.15 above but for control by two way switch.
S&F Metal clad Plug socket single pole enclosure with two pin earth plug and socket with 32 Amp, 240 volts MCB complete all as specified and directed by engineer incharge.
LED lights fitting 1x 40W, 220V,AC Trimline Neu high performance batten, thermally conductive material high translucent serrated milky white diffuser with complete fitting including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by engineer in charge.
LED light fitting 1x 10W, 220V,AC Trimline Neu high performance batten, thermally conductive material high translucent serrated milky white diffuser with complete fitting including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by engineer in charge.
LED light fitting mirror type 1x 5W, 220V,AC Trimline Neu high performance batten, thermally conductive material high translucent serrated milky white diffuser with complete fitting including connecting up with three core flexible copper conductor cable of suitable size from ceiling rose complete all as specified and as directed by engineer in charge.
LED spot light with complete fitting accessory 1x15 watt 220 V AC decorative type including connecting up with three core flexible copper conductor cable of suitable size complete all as specified and as directed by engineer in charge.
LED 1x120 watt light fitting nexust star neo made up pressure die cast aluminium housing with toughened glass and high power LEDs and secondary lenses with IP66 protection including brackets made out of GI pipe light grade pipe bent to shape incl 02 Nos MS flate clamps incl nut bolts connection complete all as spd and directed.
Ceiling fans, complete with three blade, down rod, without fan regulator and accessories 230V, 1200mm sweep, ISI marked , min air delivery 210 CFM with service value 6.00 BEE Five star rated with brushless direct current motor (BLDC) complete all as Specified and directed.
Supply and fix exhaust fan, steel body AC single Phase. 230V of size 300mm sweep with, blades, and frame and louvers complete all as specified and directed bt Engr-in-Charge.
Supply and fix Wall mounted Fan Heavy Duty motor with double ball bearing, size 450mm sweep,1440 RPM, 100 watt steel body AC single Phase, 230V with complete accessories all as specified and directed bt Engr-in-Charge.
Supply and fix LED light 12 watt 230V complete all as directed.
Supplying, installation, testing and commissioning of UPS 30 Min back up single phase AC 5KVA intelligent, True Online UPS system input 160 to 260V and output 230 +/- 1% of with EP 26-12 SMF battery – 15 Nos battery with M S rack alongwith inlerlinks complete all as specified and directed.
Supply installation ,Testing & commissioning of maintenance free compound based electrode earthing with following specifications (a) Type = Copper Bond Rod (b) Material = Low carbon steel core (SAE 1018) © Length = 3000mm (d) Dia of Rod = 17mm (e) Coating thickness = 250 microns (f) Terminal = U Bolt clamp or equivalent (g) Tolrence in length = ± 20mm (h) Tolrence in diameter = ± 1.0mm (i) Tolrence in thickness = ± 0.03mm (k) Current with stand = 10KA for 1.0 sec and 25KA peak (l) Frequency = 50Hz (m) Back fill compound = Baron electrodite IROHS certification) (n) PIT Cover = FRP OR EPCC (o) Granular material resistance = 0.001Ohs (p) Mixer ratio with cement = 3:1 (q) Copper strip = 7.5RM Note : Electrode top terminal shall be sealed permanently packed with conductive concrete and CU bonded strip taken out be terminated on earth test point and equipped terminal
PVC conduit,concealed type, 25mm dia having wall thickness not less than 2mm, ISI marked inclusive of all fitting such as tees, bends, elbows, reducers, bell mouth tube ends etc as reqd fixed in chases/under floors/slab with fixing accessories such as couplers, lock nuts, saddles, pipe hooks etc complete all as specified.
Metal box on surface /in recess with 3mm phenolic cover for mounting switch socket etc as reqd of size 75x75mm box 1/2 modules etc complete all as specified.
Telephone M.S Tag box with hinged cover having locking arranghement as per telephone dept approved and having 20 pair tag etc as reqd.
RJ 11 Telephone socket in sxisting sheet steel box including connection ect as reqd.
2 pair, 0.4mm PVC insulated , PVC sheathed annealed tinned copper conductor telephone wire drawing in existing conduit all as specified.
White cover plate with frame,1 module for fixing telephone socket etc complete all as specifiedpecified.
Tubes, ‘light grade’galvanised,40mm with all fitting and fixed complete to walls and ceilings or laid in floors for incoming unction cable as protection pipe incl earth work in any type soil complete all as directed.
S & F sheet metal VTPN DBs-DPx3 160 MCCB DBs 04 way (DPx3 160 +12) with metal door 415 volts grade IP 43 protection grade fixed flush to wall complete including connections should be provide with necessary reducer lugs all as specified and unction by Engr-in-Charge. Make Legrand Cat Part No 5077 50 or equivalent to shnieder.
S & F thermal megnatic MCCB 4 pole 125 Amps 415 Volts 46 Ka including making necessary arrangement all as specified and unction by Engr-in-Charge for MCCb DB make legrand cat part No 4200 05 or equivlant to shinder.
S & F single pole and neutral sheet steel powder coated Distribution board for MCBs fitted with 200A bus bar , Neutral link ,Earth Bar and Din rail suitable for use on 240 V, 50 Hz supply double door SP&N DB system 12 ways.
Supply and fix sheet metal enclosure distribution board TPN 415 volts 4 way with 200 amps rated bus bar Complete all as specified and directed by Engr-in-Charge.
Supply and fixing MCB TPN 63 Amps 415V 10KA ‘B’ curve miniature circuit breaker (MCB) of following poles and current carrying capacity in the DB complete with connection testing and commissioning. Complete all as specified and unction by Engr-in-Charge.
S&F ‘B’ series SPN MCB 40 to 63Amps 240V ,50Hz,10kA lighting and other domestic loads incl all unction , fitting etc.
S&F ‘B’ series SP MCB 06 to 32 Amps 240V ,50Hz,10kA suitable for lighting and other domestic loads incl all unction , fitting etc.
Earthing complete with unaction steel earth plate electrode 60cmx 60cm x 6.3mm thick buried directly in ground vertically to a depth not less than 2.25m below ground level with top edge of plate not less than 1.5m below normal ground level connected to unction iron earth strip 25 x 4mm by means of GI bolts, nuts, check nuts and washers of unction iron or steel including excavation, earth work, PCC chamber, RCC cover slab, salt & charcoal, watering pipe, wire mesh, lugs, earth lead GI protection pipe 40mm bore, light grade all as per plate No.3 of SSR Part-I , all as specified and including followinga) Excavation and earth work in any type of strata. (b) Watering pipe GI light grade 20mm dia from top of the earth electrode up to MS funnel with wire mesh unction in floor of PCC earth pit. (GI Funnel should properly unction on GI watering pipe and unction in PCC floor of earth pit with open top suitable for watering of earth pits) (c) PCC earth pit 30x30x30cm constructed in PCC 1:2:4 type B1 exposed surfaces smoothly finished with 15mm thick cement mortar 1:6 plaster including RCC pit cover 25mm thick with 2 Nos MS handles of 12mm dia suitable for carrying of pit cover. (d) Angle iron frame made of 40x40x4 mm angle iron for 30x30 mm PCC pit for holding the pit cover.
Supply and fix LED building security light 35 watt, 230V, AC, outdoor type with high pressure dia cast aluminum housing and heat resistance complete with driver, lamp bracket with impact and corrosion resistance including thermal management in multiple optical complete with IP 65/66 protection complete all as specified and as directed.
Point wiring for power point control by one switch with 2.5 Sqmm nominal area PVC insulated single core multi standard copper conductor FRLSH insulated and undheathed heavy duty cable in colour code including unaction earth wire with cable of size 2.5 sqmm copper conductor flexible FRLSH insulated drawn into and including concealed in ERW steel conduit of not less than 20mm dia and 1.5mm wall thickness (ISI marked) terminated into annealed steel terminal boxes including modular frame and cover plate for fixing of modular switches, sockets etc; complete all as specified and as directed by Engr-in-Charge.
DWC pipe (double wall corrugated) confirming to IS: 14930 (part-II) alongwith necessary snap fit coupler for interconnection suitable for HT/LT cable (120/103mm as diameter) all spedified and directed.
DWC pipe (double wall corrugated) confirming to IS: 14930 (part-II) alongwith necessary snap fit coupler for interconnection suitable for LT cable (90/76mm as diameter) all spedified and directed.
DWC pipe (double wall corrugated) confirming to IS: 14930 (part-II) alongwith necessary snap fit coupler for interconnection suitable for LT cable (77/63mm as diameter) all spedified and directed.
Deduction to be made from BOQ for Sch 'A' Part - XVI (Schedule of credit) Amount of Rs. 78,000.00 during AOC. Note: Tenderers shall not quote for this schedule.
NITYA NAND AND SONS CONTRACTORS PVT LTD (BID ID -3104668)
Chandra Construction (BID ID -3097677)
M M SHAWL Engineers and contractors pvt ltd (BID ID -3102183)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.05 MB
Download all tender documents and submit your bid