Tender Value
₹3.3 Cr
EMD Value
₹4.1 L
Closing Date
12 Apr 2025, 6:00 pmClosed
CE Shillong Zone
HQ CE Shillong Zone, Spread Eagle Falls, MES, Shillong, Meghalaya 793011
PROVN OF EXPRESS SC LINE FROM NIGLOK POWER STATION TO RAYANG MILITARY STATION UNDER GE 872 EWS
2024_MES_686804_1
89807/Rayang
Open Tender
Electrical and Maintenance Works
Item Rate
2560 days
RAYANG
All as per NIT and tender document
2 documents required · 2 mandatory
₹2,000
GE 872 EWS
₹4.1 L
Yes
30 May 2025
3 Dec 2024
14 Apr 2025
3 Feb 2025
12 Apr 2025
31 Mar 2025
Amount
Mobilization/ Transportation erection of T & P and dismantling of all reburied equipment at proposed site including deployment of suitable personels for effective soil investigation as directed.
Carrying out soil investigation as per relevant IS, complete all as specified and directed including the following:- Boring 150mm dia hole at various locations as shown at Site by Engr in charge in any kind of soil but excluding rock, collection of undisturbed sample at every 1.00 depth, Collection of disturbed sample at suitable depth as required at site. Conducting standard penetration test as per relevant IS at an interval of 1.50m (i) Up to a depth of 10.00m or refusal
Carrying out the following laboratory tests on the soil samples as per IS codes on each Bore hole. a)(i) Sieve analysis and Hydrometer tests of identification and classification of soil bases on properties and grain size. (ii) Specific gravity of the soil. (iii) Studies of settlement characteristics of soil based on consolidation tests and liquid and plastic limit. (iv) Stratification of soil for entire depth of bore log including ground water table location and other properties. Evaluation of shear parameters of undisturbed soil samples by adopting direct shear test. (v) Nature moisture content (NMC), void ratio and porosity, Tri- axial and direct shear test and confined compression test of undisturbed samples and bulk,submerged and dry density of the soil. b)Compilation of SSI Report as per IS (viz. Filed and laboratory test results), Preparation of reports, Recommendation for different type of foundations, water table with clear unambiguous recommendations for types of foundation for all structures with bearing capacity/pile capacities. The recommendations to be duly vetted by any NITs/ IITs as per Notes.
Submission of all report booklets 06 (Six) copies with CD 01 (One) copy duly indicating the following:- (i) Evaluation of safe bearing capacity of the soil with respect to shear failure test and permissible settlement (Total and differential) alongwith recommendation about type of foundation and minimum depth of foundation to be adopted. (ii) Evaluation of liquefaction potential. (iii) Evaluation of K-value. (iv) Specific suggestion if any soil treatment if required below foundation/ ground floor/ roads and type of treatment to be carried out.
Item No.4 Contd/.. Notes:- 1. Following points to be included in SSI report (not comprehensive, appropriate data/information may be added as per requirement:- (a) Introduction (b) Objective of the geotechnical investigations (c) Details of the proposed structures (d) Site conditions (e) Field investigations (f) Laboratory test results (g) Soil profile (h) Allowable bearing capacity- based on ‘N’ values, ‘c-Ø value and permissible settlement with sample calculations. Complete calculations shall be submitted in soft copy in the same CD containing the SSI report. (j) Liquefaction analysis with calculations. (k) Foundation alternatives duly tabulated building wise. (l) Clear recommendations duly vetted by any IITs/NITs. A table showing building name, BH No, depth & coordinate of the BH corrected SPT ‘N’ values and the recommended SBC and clear recommendation for depth and type including any required soil improvement matching with the site plan should form part of the recommendations. (m) Annexure including bore logs, c-Ø and indicated for BHs, likelihood of water- logging at site must also be checked. 2. If the soil/water has high (more than permissible) contents of sulphate, chlorides or any other deleterious material, the same should be brought out and appropriate recommendation be offered. The required chemical analysis needs to be undertaken for the same. 3. All relevant IS code on the subject should be followed and mentioned at appropriate places.
Design & construction of single storey sub station building of total plinth area 140 Sqm with RCC framed structure, seismic Zone-V consideration, ATT, water proofing treatment with permanent specification including fittings & fixtures complete in all respect as directed complete all as specified and directed and as shown in drawing No. CESZ/LKB/2024/ST-66 Sheet No.1/1 dated 28 Oct 2024, Notes: (i) Contractor shall get the design done from any consultant. (ii) The design shall confirm to latest IS:1893, IS 4326, IS:13920, IS 800 SP 34 and other relevant codes. (iii) The structure falls in Zone V. (iv) Structural analysis & design shall be done on latest version of STAAD. (v) Structural design shall be got vetted from any IITs/NITs. (vi) Contractor shall discussed the concept design with SO-I (Desig)/Director (Design) of HQ CESZ before finalising the Structural design.
Sr. Item No. 5. Contd/... (vii) The foundation shall be design as per the SBC of the soil at the location of construction. (ix) The Contractor shall provide the STAAD file/ AUTOCAD drg in soft copy, design folder and drgs duly vetted by any IITs/NITs shall also be submitted alongwith above said soft copy. (x) The contractor shall execute the work as per the said Structural drg only after approval of same from Accepting Officer of the contract. (xi) Vetted copy of design from any IITs/NITs shall be submitted at the time of final submission. (xii) Internal water supply i.e CPVC pipe, ball valve, stop valve, angle valve, bib taps, PVC connection, Pillar taps & shower rose and Internal water supply i.e point wiring, LED light, switches & sockets, cover plate, ceiling rose, sheet metal enclosure, MCB, RCBO, SPD, fan & earthing shall be measured & paid under relevant items. Rest everithing shown on drawing shall be included in quoted rate. (xiii) Unit Rate quoted against this Item shall be deemed to include for all minor extra constructional details which have not been specifically shown on drawings or given in particular specification but are essential for the execution of works and services in the workmen like manner, sound construction and established engineering practice. In all the above and similar cases the details indicated elsewhere in the drawings that are similar or near similar to the missed out items of works shall be followed. In the absence of any other similar or near similar details, minimum essential requirement for completion of the work from the structural and utility point of view shall be deemed to be included in the quoted rate.
Surface dressing not exceeding 15 cm deep and getting out in soft/loose soil complete all as specified
Removing of excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point all complete all as specified ans as directed.
Surface excavation not exceeding 30 cm deep and averaging 15 cm deep and getting out in soft/loose type of soil complete all as specified and directed.
Excavation over area not exceeding 1.5 m deep and getting out in soft/loose soil complete all as specified and as directed.
Excavation in post holes (or similar holes) each not exceeding 0.50 cum, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm, watering and removing surplus soil to a distance not exceeding 50 m and making good surface complete all as specified and directed.
Excavating in Trenches not exceeding 1.5 m wide and not exceeding 1.5 m in depth, for foundation etc or for shafts, wells, cesspits, manholes etc not exceeding 10 sqm on plan and not exceeding 1.5 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Returning, filling in, including spreading, leveling, watering and well ramming in layers not exceeding 25 cm in soft/loose soil complete all as specified and as directed.
Excavating in Trenches not exceeding 1.5 m wide and exceeding 1.5 m but not exceeding 3 m in depth, for foundation etc or for shafts, wells, cesspits, manholes etc not exceeding 10 sqm on plan and exceeding 1.5 m but not exceeding 3 m in depth and getting out in soft/loose soil complete all as specified and as directed.
Material & Labour for Hardcore of gauge not exceeding 63 mm deposited spread and levelled in layers not exceeding 15 cm thick watered and rammed to a true surface complete all as specified and as directed.
Material & Labour for Moorum/Red Bajri filling in floors or pavings, laid in layers not exceeding 15 cm thick, spread, levelled and rammed including watering complete all as specified and as directed.
Material & Labour for polythene film, 150 micron thick laid on a 10mm thick fine sand layer complete all as specified and as directed.
Material & Labour for Cement concrete work in pavement/ hard-standing of flexural strength 40 kg/per square centimetre in field using 400 kg of cement per cubic metre, thickness of concrete 15 cm or less complete all as specified and as directed.
Rolling and consolidating formation surfaces in cutting with 8 to 12 tonne power roller complete all as specified and as directed.
Material & Labour for Forming Contraction (Dummy) joints 65mm deep x 10mm wide filled with sealing compound, Grade 'A' complete all as specified and as directed.
Material & Labour for Plain Cement Concrete 1:4:8 type D-2 using 40 mm graded stone aggregate as in foundation filling and mass concrete complete all as specified and directed.
Supply & fix High strength steel deformed TMT bars (Fe 500D) 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
Supply & fix High strength steel deformed TMT bars (Fe 500D) 5mm dia and over upto and including 10mm dia in stirrups, spacers and binders cut to length, bent to shape required including cranking, bending spirally and binding with and including mild steel (annealed) wire not less than 0.90 mm dia or securing with clips complete all as specified and directed.
Supply & fix Mild steel round bars (Fe 500D) 10mm dia and over, cut to length, bent to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with and including mild steel wire (annealed) not less than 0.9mm dia or securing with clips complete all as specified and directed.
Material & labour for Reinforced Cement Concrete M-25 (Design mix) using 20 mm graded stone aggregate as in Columns, pillars, piers, post and struts, etc. complete all as directed.
Supply & fix Mild Steel Hand rails, half round or other steel section or core for wooden hand-rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolt, angle posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets(for securing wire mesh etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe 290 (Gde E-165) complete all as specified and directed.
Supply and fixed of mild steel screw bolts 12 mm diameter of shank (machine made) with hexagonal or square heads at one end and screwed the other, or screwed both ends, each screwed end to be fitted with washers and one hexagonal or square nut, length of bolt exceeding 5 cm and not exceeding 10 cm complete all as specified and directed
Supply only Chain Link MS galvanized fencing of mesh 100 x 100 mm and of any type of shape (minimum dia 4mm ) conforming to IS 2721 including line wire, binding wires, straining bolts complete all as specified and as directed.
Fixing only chain link fencing including line wires, any mesh size and type of standards, rails, straining bolts, etc. including provision of binding wire.
Material & Labour for painting with two coats of synthetic enamel paint on steel and iron surfaces of any description not exceeding 10 cm in width or girth including preparation of surfaces and applying one coat of red oxide primer complete all as specified and as directed.
Material & Labour for galvanised, 2 strand, steel barbed wire 2.24mm dia barbed with 2mm dia barbs at 75mm spacings and straining and fixing to any type of standard rails straining bolts, including, securing or tying at crossings with and provision of galvanised mild steel wire, staples or steel pins, etc. as directed (each line wire to be measured)
Material & Labour for preparation of new plastered surfaces and applying two coats of cement base paint of approved shade on walls all as specified & directed.
Use and Waste of formwork to sides of concrete foundations, foundation beams, footing, bases of column, raft and raft beams, sides and soffits of foundation beams, etc. flat rough finished surfaces of concrete complete all as specified and as directed.
Material & Labour for Reinforced Cement Concrete M-25 (Design mix) using 20 mm graded stone aggregate as in foundations, including rafts, footings, foundation beams; plinth beams; bases for columns and mass concrete complete all as specified and as directed.
Use and waste of formwork to sides of columns, pillars, piers, post and struts, etc, square, rectangular or polygonal, rough finished surfaces of concrete complete all as directed.
Material & Labour for Plain Cement Concrete 1:2:4 type B1 using 20 mm graded stone aggregate in coping, kneelers, apex stones, bed plates, kerbs, water trough and the like including weathering slightly rounded or chamfered angles and throating and necessary formwork complete all as specified and directed.
Supply & Fix Rolled mild steel of grade Fe-290 (Gde E-165) in framed work as in doors or gates of angle or other section with gusset plates, rails, braces, wheels etc., complete, drilled for fixing of steel sheeting or other covering. Doors, etc. to be prepared for hanging or sliding with and including either hooks and hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging; also fastening and fixing complete all as specified and directed.
Material & Labour for Rendering 15 mm thick in Cement Mortar 1:6 on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed
Material & Labour for preparation of new or previously untreated surfaces of steel and iron work of any description over 10 cm width or girth not otherwise described and applying two coat of synthetic enamel paint over a coat of red oxide prime in any tint complete all as specified.
Construction of on site LLDPE septic tank designed to carry sewage and sullage water for 10 users, including excavation in any type of soil, plain cement concrete 1:4:8 as in lean concrete, Vent shaft, connections and complete all as specified and as directed.
Material & Labour for soakage well of size 1.8 m dia and 3 m effective depth including intercepting chamber and screen chamber made of brick masonary, including excavation in any type of soil earthwork, returning, filling in and removal of soil upto not exceeding 50m and as shown in TD drawing No. CESZ/2020/TD-45, sheet 1/2 & 2/2 complete all as specified and directed.
Material & Labour for shallow sewers of 150mm dia RCC NP-3 pipes laid on 150mm thick moorum/sand/crushed stone bed with excavation upto depth 1.65m in any type of soil, including manholes of standard size made of brick masonry with SFRC ventilating cover and frame. Including all items and activities to execute and make sewer line functional complete all as specified and directed.
Labour and necessary tools & plants for Shifting HT 11KV Incoming cum outgoing Solar VCB Panel complete in all respect from Rayang Military Station MRS VCB Room to proposed 33/11KV Sub Stn Bldg after disconnecting all electrical and mechanical connections by taking necessary power shut down including installation, connecting electrical connections and commissioning complete in all respect at new location.
Labour for disconnecting, taking out safely existing serviceable XLPE insulated, screened PVC, galvanised steel strip armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts grade, cross sectional area 150Sqmm, 3 core of any make from Solar HT 11KV incoming cum outgoing VCB, duct, trench, 2 Pole structure, under road/culvert by necessary excavation work for re-use all as specified or as directed by the Engineer-in-Charge. HT Cable be taken out with due care to avoid any damages being re-used, PCC covers, GI tubings of any type, size and make also be taken out and kept in safe cusotdy for re-use. Note : Necessary earth work shall be measured and paid under relevant item of the schedule.
Labour only for Laying /rerouting of XLPE insulated, screened PVC, galvanised steel strip armoured, electric power cables (heavy duty) with aluminium conductor, 11000 volts grade, cross sectional area 150 Sqmm, 3 core as retrieved from taking down item No 43, including making connections and testing complete all as specified and as directed. Note : Necessary earth work, sand cushioning, protection pipe, cable jointing kits shall be measured and paid under relevant item of BOQ.
Material and labour for cable jointing kit for 11 KV (Earthed) grade cable for indoor termination, heat shrink type joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Aluminium conductor cable of size 120 sqmm to 185 sqmm complete all as specified and directed.
Laying only un-reinforced precast concrete cable cover, class HV, type 1 , flat, size 300mm x 180mm x 40 mm complete all as specified and as directed.
Material and labour for Steel tubular swaged poles (for 4 Pole structure suitable for one incoming and three outgoings) complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-68 (13.00 metres long) including cast iron base plate,finial taper plug, cap, mild steel bolts, screws, etc. including applying two coats of black bituminous paint internally and externally upto planting depth and applying two coats of aluminium paint over a coat of aluminium primer (externally from top of PCC copping) including writting MES Pole No. with synthetic enamel paint (first grade quality) complete all as specified and directed. Note:- (a) Earthwork & PCC shall be measured and paid separately under appropriate items. (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.
Material and labour for Lightning arresters expulsion type complete with all fittings, transmission class/ station class, discharge capacity 65 kilo amp, 33 KV complete all as specified and as directed.
Supply and fix of aluminium conductor steel reinforced complete all as specified and directed.
Supply and fix HT 33 KV out door type gang operated air-break switch suitable for horizontal or vertical mounting fixed type complete with 9 insulators and with earth switch upto 400 Amps complete all as specified and directed.
Supply, laying & testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor, 33000 volts grade, of size 3 core 240 sq mm complete all as specified and directed.
Supply and fix cable jointing kit for 33 KV grade cable for outdoor termination heat shrink type joint complete with jointing material and accessories suitable for single core XLPE, armoured, Al conductor cable of size 240 sqmm complete all as specified and directed.
Supply & Fix of Disc type insulator, porcelain, vitreous 145mm high and 255mm dia ball and socket type, white, brown or green single assembly for tension with tension clamps for conductors, working pressure 11000 volts complete all as specified and directed.
Supply & Fix Control cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 4 core 2.5 sqmm complete all as specified and directed.
Supply & Fix Control cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 7 core 2.5 sqmm complete all as specified and directed.
Supply & Fix Control cable 1100 volts with PVC insulated and steel armoured with multi stranded copper conductor of the sizes 12 core 2.5 sqmm complete all as specified and directed.
Supply,installation,testing & commissioning of 33KV 630Amps 25kA-3sec Indoor type floor mounted compact SF6 Gas Insulated Switchgear with internal copper bus bars, consisting of with two Nos. motorized Load Break Switch as incomer and two nos motorised Vacuum Circuit Breaker as outgoings along with Bus connect Air Insulated PT Panel. All live parts, bus bars, LBS & VCBs connections, ON-OFF offload switch, Earth switch of of feeder should be enclosed in one tank sealed for life robotically welded non magnetic and non ferrite grade stainless steel tank Grade 304 of minimum 2 mm thick having IP67 degree of protection filled with SF6 gas as insulation with leakage rate less than 0.1% per year tested as per IEC 62271-200. SF6 Gas Tank and cable chamber should be tested for an internal arc fault of 25kA for 1 sec with AFLR classification. All four modules LBS and VCB should be enclosued in one SF6 tank to avoid multiple conections. The unit shall have front cable entry for ease of installation and shall have site replaceable bushings for ease of troubleshooting during breakdown at site (to avoid dismantling of SWG and rectification at OEM factory for minor gas leakage issues due to bushung breakage). The Gas Insulated switchgear should be complete with all accessories and should be suitable to connect cable upto 1RX3Cx400sqmm. VPIS, cable supports, all front cable terminations, mechanical indications for VCB, OFF load switch & Earth switch , Manometer as per with IEC standards 62271-1, 100, 200. Altitude of installation up to 200 mtr as per IEC 60120. The unit shall include the following with all necessary standard fitting required at site. Product from License partner / Authorized Integrators are not accepted.
Sr Item No. 57 Contd/... VACUM CIRCUIT BREAKER feeder 630A VCB module for making & breaking of fault current alongwith Earth Swicth of full making capacity-2 Nos. Motor operated 630 A Vacuum circuit breaker having spring stored mechanism. ON-OFF off load switch and earthing switch downstream vacuum circuit-breaker. Menometer per tank per feeder. “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 25KA/ 3 sec Making Capacity - 62.5KA VCB must confirm operating sequence 0.0-0.3sec-CO-3Min-CO and 10000 mechanical operation. Power frequency withstand voltage - 70KV & Impulse withstand voltage - 170KV Front cover mechanism - IP2X. Green(ON)/Red(OFF) push buttons to operate VCB. Indication Lamp for ON, OFF, TCS, TRIP, SPRING CHARGE etc. Auxiliary powered numerical protection relay having Over Current, earth fault, Over Voltage & Undervoltage with IEC61850 complaint rear RJ45 port with programable 10 DO & 16DI. Multifunction meter with MODBUS communication - 1No. (Each VCB) Cast Resin Ring core CT for metering on cables 100-50/1A, Class: 0.5 2.5 VA - 3 Nos Cast Resin Ring core CT for protection on cables 100-50/1A, 5P10 2.5 VA - 3 Nos Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Switchgear VCB, Vaccum Interrupter, Relay must be of same make.and SCADA compatible suitable to system
Sr. Item No. 57 Contd/... LOAD BREAK SWITCH feeder 630A Load Break Switch module for making of fault current alongwith Earth Swicth of full making capacity-2 Nos. (Mechnical inter lock between 2 load break switch - 2 lock and one key to avoid parallel operation of LBS) Motor operated 630 A Load Break Switch having snap action mechanism. Three position disconnector/earthing switch downstream vacuum circuit-breaker. Three position single spring mechanism for disconnector/earthing switch “Live Cable” LED Indicators thru Capacitor Voltage Dividers mounted on the bushings. Short time breaking current - 25kA/ 3 sec Making Capacity - 62.5KA Power frequency withstand voltage - 70KV Impulse withstand voltage - 170KV Front cover mechanism - IP2X Cable covers - 3X Mechanical ON/OFF/EARTH/Spring charge Indication Cable boxes should be Arc Proof interlocked with respective Earthing Switches. Fault passage Indicatory to be given along with LBS module One Bus Connected Airinsulated equipment / metering cubicle consisting of following 3 nos. Single Phase PTs - 33kV/V3/110/V3 ,Cl-0.5 & 3 P ,50VA Space Heater with thermostat Sutable Analog Voltmeter with VSS 24V DC and 230V AC supply shall be extended at Site by Client. Supply of Electricals Bushing of 36kV of offered Sf6 Insulated SWG with suitable O-Rings - 3Nos (1set) in spare (Mandatory) for replacement at site. Final commissioning should be done in supervision of SWG OEM only.
Supply, Fixing and termination of Indoor 36kV Screen Connectors suitable for 33kV XLPE cable upto 1RX3CX400Sqmm, as per recommonded make of 36kV Sf6 Insulated SWG supplier. Screen Connectors should be terminated in 36kV CSG by "certified jointer" only duly certififed by SWG Manufacturer or supplier of Screen Connector complete all as specified and directed.
Supply, installation and testing for maintenance free chemical earthing by using Low carbon, copper coated earth rod of 14.2 mm dia and 3.0 mtr long, with 250 micron thick copper coated earthing electrode, UL 467, tested as per IEC 62561-2, including filling 2 nos bags x 25 Kg (total 50 KG) ground earth conductivity enhancing mineral compound and including PVC earth pit cover of square size complete connected to earthing test point / equipment etc all as specified or indicated including testing on completion. NOTE: (i) The unit rate includes for protection pipe and copper strip/copper wire as per recommendation of OEM from top of earth electrode upto 7.50 Mtrs above ground level. (ii) The earth result should be less than or equal to 1 Ω (Ohm). (iii) The Quoted rate shall deemed to be inclusive of connecting earthings in a Grid pattern to achieve earth value less than 1 Ω (Ohm).
Supply and fix UPS for 30 min back up single phase AC input 160 to 260 V and out put 230 ± 1% of capacity 3KVA complete all as specified and direcetd by Engr-in-charge. Note:- Cost of suitable rating maintenance free tubular battery bank including connections etc deemed to be included in quoted rates.
Supply, installation,engineering commissioning and testing of Substation level SCADA supplied and installed separately, essentially for monitoring and controlling of all the 33KV Panels and 11KV panels (total 8 Nos.), two Nos. power transformers, etc on IEC61850/latest platform via respective IED relays and capturing energy parameters on ModBus/ IEC61850/ IEC104 platform via respective Meters/ controllers all including required operator workstation, software with suitable tags for lifetime license, power-backup system and allied accessories, comprising of the followings:-
Sr. Item No.61 Contd/.... (I) SCADA Panel in Substation: (i). Industrial grade, continuous duty, EMC compliant Remote Terminal Unit (RTU) / Data Concentrator Unit (DCU) / substation management unit (SMU) stand-alone function, having at least 800MHz processor, having operational temperature from 0-70degC (commercial grade) processor and 512MB RAM, alongwith inbuild modem to transmit data over 4G with fallback to 3G/2G. The unit shall have following type test certificates from any NABL approved lab (The certificates must bear the NABL logo on it). (1) Conducted and Radiated Emission test as per CISPR 22:2018, Immunity to Electrostatic discharge Test as per IEC 61000-4-2 ::2008, Immunity to Radiated Test as per IEC 61000-4-3-2010, Immunity to fast Transients (2) Test as per IEC 61000-4-42012, IEC 61000-4-5:2014 (Up to 2 KV), Immunity to RF field induced conducted disturbance Test as per IEC 61000-4-6:2013, Power frequency IEC 61000-4-8, Dry heat IEC 60068-2-30 (per cycle) (a) gateway for interfacing with relays over IEC61850, meters on ModBus and upper-level SCADA/DCS on IEC-104 protocol, DT and panel data in analog format through AI converters as per site reqmnt (b) web-browser based, platform independent HMI for viewing substation dynamic SLD and substation feeder data incl. ON/OFF/TEST/ SERVICE position, energy parameters like line-current, line/bus-voltage, kVA, kW, kWh, pF, Hz etc. relay-parameterization, event/alarm notification and fault record viewing, feeder ON/OFF control and as specified in P.S. (c) Life time licensed SCADA software suitable for display of data in r/o 11KV Panel, LT Panels, DTs, UPS, DG Sets etc through suitable UI on HMI/server including intergration and developement of data base as per site reqmnt with reporting software and as directed (d) Data Historian for automatically downloading all IED relay's disturbance recorder data (e) All data and SIM cost for the period of one year shall be taken into account. (e) Communication Protocols IEC 60870-5-104, DNP3, IEC 61850 and Modbus (f) Ports 3 x RJ45 Ethernet, 2 x RS 485, and 1 x RS 232 (g) Minimum 64 DI, 32 DO (may be extended as per site reqmnt) (h) Operating Voltage Range 24 V DC, +/- 15% (j) Security Protocols IPsec, SSL and SRTP (k) Cyber Security as per IEC62351 & IEC62443 (l) Protection Degree IP 54 (m) Operating Temperature range -10degC to 55degC, Humidity upto 95% (n) Support two redundant physical channel communication to one control centre.
Supply & fix Industrial grade managed type Ethernet networking switch for star-coupler connection to all IED’s over IEC 61850 platform and upper level scada on IEC 104, suitable with 24 V DC supply and have minimum 32x10/100/1000 Base-T RJ45 and 2xFO ports.
Supply and fixing of 16U Wall Mount Network Equipment Rack to house ethernet switches and controllers- Patch Panel Bracket for Shallow Server Equipment, Controllers, etc. completed in all respect including MCBs, fuse, earthing, inbuild exhaust fan, etc. (suitable for installation in dust-proof environment)
(v) Supply and laying LAN Cable (CAT5/CAT6) with sufficient number of RJ-45 terminals, suitably routed via substation trenches/ducts/walled-pipes including cable tray/conduit as per site conditions from 11 kV HT VCB Panel/UPS/other equipments upto Ethernet switch / RTU module and from existing 11KV Sub Station, old server room, new server room to SCADA console complete. (vi) PVC Shielded, three-core 4 sqmm wiring suitable for 230VAC supply routing from nearest 16Amp power-point upto UPS/Inverter and from inverter upto SCADA console and workstation, suitably laid via conduit pipes and jointed using recommended termination/socket arrangement in a neat fashion as per instruction of engineer-in-charge. (vii) PVC insulated and sheathed Copper control cable 1.0 Sqmm x 2 core for Modbus communication via daisy chain, with isolation MCBs and suitably routed via substation trenches/ducts/walled-pipes including cable tray/conduit as per site conditions from all Modbus equipments to SCADA console. (viii) Integration of all IEDs and MFMs with RTU module, tagging of data points on IEC104 protocol
Supply & Fix Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed.
Supply & Fix 32 x 6 mm copper strip including connection from earthing in continuation to end point, complete all as specified and as directed.
Supply & Fix 100 mm bore GI tubing light grade ISI marked for protection of cable including necessary joint complete all as specified and as directed.
Supplying and laying synthetic Rubber insulated mats 3 mm thick for voltage upto 33 kv for electrical purpose as per IS 15652-2006, (superseding IS 5424) suitable for electrical shock safety of sizes 2m x 1m complete all as specified and as directed.
Material & Labour for brickwork in CM (1:4) using old size sub class B bricks straight or curved on plan exceeding 6 Mtr mean radius, for construction of cable duct including duct cover complete all as specified and as directed.
Material & Labour for rendering 15mm thick in cement mortar 1:4 on fair face of brick work finished even & smooth without using extra cement complete all as specified and as directed.
Supply, installation, testing and commisioning of copper wound power transformer 33 KV step down, outdoor type of capacity 2000 KVA , 33KV/ 11 KV, 3 phase, 50 Cycle AC with ON load tap changing arrangement with remote control panel operation on 33 KV side to vary secondary voltage from plus (+ ) 5% to minus (-) 15% in steps of 1.25% (17 Steps), impedance 7.35% at normal/common tap No.7 including suitable marshalling box and HV terminals 3 Nos outdoor bare bushings with sockets and LV terminals connectors to connect the transformer with HT XLPE Power cable of size upto 300 Sqmm 3 core with copper conductor and LV additional neutral with one no solid porcelain type outdoor bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-2026 primary side delta and secondary side star. The salient features of the transformer shall be as below:- (i) The transformer shall be DYN 11 vector group oil immersed naturally cooled, doubled wound electrolytic copper winding core type, radiator cooled MS tank complete with first fill of transformer oil as per Is-335 with ONAN cooling system. (ii) The temperature of oil shall not rise 550C of winding. (iii) The transformer shall be painted with two coats of synthetic enamel paint. (iv) Rating and diagram plate shall be affixed on the transformer. (v) The transformer should have Earthing terminals - 02 Nos. (vi) The transformer shall be provided with Lifting lugs. (vi) Thermomoter pocket, (vii) Air release hole with plug. (viii) Oil filling hole with plug on & incl. conservator with drain valve and plug. (ix) Plain type oil indicator on one side of conservator with maximum oil level marking. (x) Dehydrating breather - 01 No. (xi) Oil conservator with drain valve and plug. (xii) Sampling valves, top and bottom., (xiii) Under base with flat treated bi-directional rollers. (xiv) Drain cum bottom filter valve with plug. (xv) Top filter valve with plug. (xvi) Explosion vent with diaphragm and equalizer (pressure release device). (xvii) Jacking lugs and hauling holes. (xviii) Inspection cover. (xix) Detachable radiators with shut off valves between radiators and tanks. (xx) Radiator with air release hole and plug. Oil drain hole with plug and lifting eye all as per manufacturer's standards.
Supply, installation, testing & commissioning of single phase 5 KVA capacity (230V AC /96V DC) DSC/micro controller based pure sinewave inverter using PWM technology with constant voltage & frequency output including 6 Nos of 12V, 200 Ah capacity maintenance free invatubuler battery 60 months warranty including connection etc complete all as specified and directed.
Supply, installation, testing and commissioning of indoor type vacuum circuit breaker panels consisting of 2 incomer, 1 Buscoupler including bus raiser, 3 nos Outgoings with posibility of future extension at one side,capacity 11 KV, 630 Amp, 3 Phase, 3 wire, 50 Hz, having a rupturing capacity of 500 MVA at 11 KV, 26.3 KA breaking capacity for 3 sec, totally enclosed with extended Aluminium bus bar of 630 Amps for each phase, metal clad, Indoor extensible type, flush front, Horizontal isolation, Horizontal drawout type with Electrical and Mechanical interlock and automatic safety shutter gear including padlocking arrangement, isolation plugs, assambly of 3 vaccum interrupters (Should be VCB manufacturer's own make), with each pole individually encapsulated by epoxy insulations to make it dust proof and self - aligning finger type isolating contacts, truck having integral racking with necessary interlocks (for insertion and removing of VCB), manual and automatic motor charged independent closing/ tripping spring, trip free operating mechanism with closing and tripping push buttons and mechanical breaker, interconnected with HT sleeve (PVC not accepted) bus bar, including all protection, indication, Operation, monitoring and control and accessories as per the specification. ( 02 Nos outgoing, 01 No spare)
XLPE insulated, screened, PVC bedded, galvanised steel strip or wire armoured, electric power cables (heavyduty) with aluminium conductor, 11000 volts Earthed, grade cross sectional area 95 sq. mm 3 core complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for outdoor termination , heat shrink type, joint complete with jointing material and accessories suitable for 3 core XLPE, armoured, Al conductor cable of size 95 sqmm complete all as specified and directed.
Supply and fix cable jointing kit for 11 KV grade cable for in door termination, heat shrink type, joint complete with jointing material and accessories suitable for3 core XLPE, armoured, Al conductor cable of size 16 sqmm to 50 sqmm complete all as specified and directed.
Supplying and laying reinforced precast concrete cable cover, class EHV, type 1 with peak, size 450mm x 230mm x 50 mm complete all as specified and as directed.
Supplying and laying un-reinforced precast concrete cable cover, class HV, type 1 , flat, size 300mm x 180mm x 40 mm complete all as specified and as directed.
Supplying and laying un-reinforced precast concrete cable cover, class LV, type 1 , flat, size 250mm x 150mm x 40 mm complete all as specified and as directed.
Material & Labour for sand cushioning in trenches for protection of under ground cable provided in layers of sand as 8 CM before laying (beneath cable) and 15 CM (over the cable) after laying cable, & punning down complete all as specified and directed.
Supply, laying, jointing GI pipe light grade 40 mm dia bore for protection of cable, passing through cable inside GI pipe/ fixed with wall/pole/surface or passing through road/culvert etc complete all as specified and directed.
Material & Labour for danger notice plate of size 25x20 cm made up of 1.6 mm thick Mild Steel sheet vitreous enamelled white, with letters, figures, and conventional skull and bones in signal red colour and fixed with MS clamp, bolts, nuts, of approved size for HT conforming to IS2551 complete all as specified and directed.
Material & Labour for Anti climbig devices, comrising 2.24 mm dia galvanised steel 2 strand barbed wire with 2.00 mm dia barbs wrapped spirally round poles, to a length of 0.5 to 1.0 metre clamped and properly secured complete with nuts, bolts, clamps etc complete all as specified and directed.
Material & Labour for Plain Cement Concrete (1:2:4) type B2 (Using 40 mm graded stone aggregate) as in foundation of pole/ High Mast Structure complete all as specified and directed. Note: RCC foundation shall be as per approved design of OEM.
Material & Labour for Plain Cement Concrete (1:3:6) type D2 using 20mm graded stone aggregate for sub-base foundation all as directed.
Material & Labour for Spreading stone aggregate 20mm graded to a depth of 15 cm over a layer of fine sand inside the 33 KV switchyard all as specified and directed. Note- laying of sand shall be measured and paid separately under relevant items.
Supply, laying & spreading sand inside the 33 KV switchyard to a depth of 15 cms all as specified and directed.
Supply & lay cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured electric power cable (heavy duty) 1100 volts grade with stranded alumium conductor of size 16 Sqmm 4 core complete all as specified and directed.
Supply and fixing Street light fittings high-quality group control enabled integrated LED Street Light with a minimum system lumen of 3000 lm and system wattage not exceeding 25W with a nominal system efficacy of 110 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminium, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 75K hours@L70. The product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The LED used in the luminaire shall be SMD type only. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2. The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & "FAT" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with sample approval. The LED Luminaire & it's driver both should be BIS registered. contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver and including 1.2m long 32mm dia GI pipe light grade bend to shape and fixed using two nos clamps fabricated using MS Flat iron 40x5mm including necessary nut bolts and washers and making electrical connection using 1.5sqmm, 3 core multi-stranded copper conductor PVC insulated and over all PVC sheathed cable form light fitting complete all as specified and directed.
Supply and fixing loop in loop out box of FRP made with IP 65 protection of thermoplastic circuit breaker boxes with metric knckouts for cable entry and exit, combi climate cable glands of IP 66/67 for cable entry and grommets IP 65 for conduit for cable exit with MCB 6 Amps, 10 kA, C curve overload and short circuit protection, terminals as PVC connector heavy duty 32 Amps, 4 way for cable necessary fixing arrangement and with cable glands, etc all as specifed and directed.
Material & Labour for Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts and screws as specified type 410 SP-22 (8.50 metres long) including cast iron base plate,finial taper plug, cap, mild steel bolts, screws, etc. including applying two coats of black bituminous paint internally and externally upto planting depth and applying two coats of aluminium paint over a coat of aluminium primer (externally from top of PCC copping) including writting MES Pole No. with synthetic enamel paint (first grade quality) complete all as specified and directed. Note:- (a) Earthwork and PCC shall be measured and paid separately under relevant items in BOQ. (b) Volume occupied by Steel Pole shall be deducted to derive the quantity of PCC.
Cutting 25 mm existing steel tubing for alterations or additions (Each cut measured), complete all as specified and directed.
Screwing existing steel tubing for alterations or additions (or lengthening screw on pipe to form connector) complete all as specified and directed.
Supply and lay pipe galvanized, “Medium class”, including fittings 25 mm dia. laid in trenches complete all as specified and directed.
Supply and lay pipe galvanized, “Medium class”, including fittings 20 mm dia. fixed to walls and ceilings or laid in floors etc complete all as specified and directed.
Supply and fix Gun-metal, globe or gate valves of size 25 mm, with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
Supply and fix Gun-metal, globe or gate valves of size 20mm , with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed.
Material and Labour for concealed point wiring with PVC insulated unsheathed multistranded FRLS copper conductor in PVC conduit with cable 1.5 Sqmm size 1100 volts grade conforming to IS:694 and terminate to flush box of required size suitable for mounting modular switches and sockets including single core multi stranded FRLS copper conductor 1.5 Sqmm PVC insulated cable as earth wire connected to earth and common earth dolly drawn in same concealed conduit for light point/exhaust fan/ ceiling fan point controlled by one, one way modular switch complete all as specified and directed by Engr-in-charge. Note: Modular boxes with cover plate shall be measured and paid separately under respective item of BOQ.
Material and Labour for concealed point wiring with PVC insulated unsheathed multistranded FRLS copper conductor in PVC conduit with cable 1.5 Sqmm size 1100 volts grade conforming to IS:694 and terminate to flush box of required size suitable for mounting modular switches and sockets including single core multi stranded FRLS copper conductor 1.5 Sqmm PVC insulated cable as earth wire connected to earth and common earth dolly drawn in same concealed conduit for one three pin 5 Amp socket outlet point controlled by one, one way modular switch on independent board complete all as specified and directed by Engr-in-charge. Note: Modular boxes with cover plate shall be measured and paid separately under respective item of BOQ.
Material and Labour for concealed point wiring with PVC insulated unsheathed multistranded FRLS copper conductor in PVC conduit with cable 1.5 Sqmm size 1100 volts grade conforming to IS:694 and terminate to flush box of required size suitable for mounting modular switches and sockets including single core multi stranded FRLS copper conductor 1.5 Sqmm PVC insulated cable as earth wire connected to earth and common earth dolly drawn in same concealed conduit for one three pin 5 Amp socket outlet point controlled by one, one way modular switch on same board complete all as specified and directed by Engr-in-charge. Note: Modular boxes with cover plate shall be measured and paid separately under respective item of BOQ.
Material and Labour for concealed point wiring with PVC insulated unsheathed multistranded FRLS copper conductor in PVC conduit with cable 2.5 Sqmm size 1100 volts grade conforming to IS:694 and terminate to flush box of required size suitable for mounting modular switches and sockets including single core multi stranded FRLS copper conductor 2.5 Sqmm PVC insulated cable as earth wire connected to earth and common earth dolly drawn in same concealed conduit for one 15 Amps socket outlet point controlled by one, one way modular 16 Amps switch complete all as specified and directed by Engr-in-charge. Note: Modular boxes with cover plate shall be measured and paid separately under respective item of BOQ.
S & F recessed type false ceiling mounted type LED light 540mm x 540mm (overall size 600 mm x 600 mm) luminaire with CRCA housing suitable with fully diffused PS diffuser for general lighting in office areas. The luminaire should have a color consistency SDCM < 5, CRI 80 and CCT of 4000K/ 6500K. The luminaire shall be compliant with IP20 and IK02 classification. Luminaire shall be designed to emit at least 3600 nominal lumens and an outstanding backlit solution efficacy of atleast 120 lumen/watt and maximum system wattage of 30W. The luminaire shall be designed so as to ensure L70B50 @ 30K Hrs.@ 45 Degree Ambient. The electronic driver used shall have a power factor >0.95 and THD <10% The fixture should comply with the parameters as per IS10322. Similar to SM367 LED30S-6500 G6 L54W54 PSU OD. The LED Luminaire & it's driver both should be BIS registered. The contractor shall submit the following reports before supply of material for approvals LM79 issued by NABL accrediated lab, LM80 issued by LED manufacturer, Type Test Certificate for luminaire as issued by NABL accrediate lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver.
Supply, Installation, testing & comissioning of intregral LED 2ft luminaire of CRCA housing and PC diffuser (Diffuser-Non yellowing type). The luminaire should have a LED with colour consistency SDCM< 5,CRI> 80 and colour temperature - 4000 to 6500K, Luminaire shall be designed to emit at least 2000 nominal lumens at a system efficacy of at-least 120 lumen/watt, power consumption should not be more than 16W (+5%). the life of fixture (including Driver): 50000 burning Hrs.@ L70B50 Lumen maintenance @ design ambient temp 50 deg C. The electronic driver used shall have a power factor >0.95 and THD < 10% suitable for an operating voltage range of 150-270V AC current Ripple<5% internal surge protection should be minimum 2.5KV, electrical insulation class should be Class I &driver should be of class B serviceablility. The luminaire driver shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have in house NABL accredited lab conduct LM79, type test as per IS10322 & "FAT" before dispatch as per IS 10322. The LED Luminaire & It's driver both should be BIS registered contractor shall submit the following reports before supply of material for approvals LM79 issued by NABL accrediated lab, LM80 issued by LED manufacturer type test certificate for luminaire as issued by NABL accrediate lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver.
S & F Building security light fittings high-quality group control enabled integrated LED Building security Light with a minimum system lumen of 3000 lm and system wattage not exceeding 25W with a nominal system efficacy of 110 lumen/watt. The LED used shall have CCT of 5700K, SDCM ≤ 5 and CRI≥70. The housing should be made of LM6/ADC12 Alloy, non-corrosive Single Piece pressure die-cast aluminum, to withstand extreme environments. The spigot shall be part of “Single Piece Pressure Die-cast housing” & shall not be bolted to the luminaire housing to ensure robust design. The name of the brand should be embossed/engraved & should not be mentioned using sticker/screen printing. It should have corrosion resistant powder coating to pass NSS of 500 Hrs. The luminaire LED shall have declared Lifetime of 75K hours@L70. The product should be designed for continuous operation (10-12 Hrs. per day). The Ingress protection should be minimum IP66 & impact resistance shall be IK10. Control gear compartments shall be Top maintainable without accessing/opening the optical compartment. The Luminaire should have a minimum 20 KV/10KA SPD duly bolted in the Luminaire. The SPD should be able to sustain a minimum 15 hits of 10KA rating i.e. Total of 45 hits across all the three modes as per IEEE 62.41.2. The luminaire should be of Class B Serviceability. The LED used in the luminaire shall be SMD type only. The Driver should be asphalt potted & should be a BIS approved driver. The driver shall have operating voltage of 120V to 270V, PF≥0.95 @ full load, THD≤10% @ full load. The driver should be capable of withstand voltage stress of 440V for 8 Hrs., should have an auto shutdown @ 325V(±15V) and have an auto recovery feature. The driver shall comply to IEC61547 & IEC 61000-3-2. The luminaire driver & it’s SPD shall be of the same make/manufacturer as that of LED luminaires. Luminaire manufacturer must have In-house NABL accredited lab to conduct LM79, Type test as per IS10322 & "FAT" before dispatch as per IS 10322. The contractor must submit the NABL accreditation certificate for Luminaire manufacturer along with sample approval. The LED Luminaire & it's driver both should be BIS registered. contractor shall submit the following reports before supply of material for approvals: LM79 issued by NABL accredited lab, LM80 issued by LED manufacturer, Type Test report for luminaire as issued by NABL accredited lab, RoHS compliance issued by LED luminaire manufacturer, BIS certificate for LED Luminaire & Driver and including 1.2m long 32mm dia GI pipe light grade bend to shape and fixed using two nos clamps fabricated using MS Flat iron 40x5mm including necessary nut bolts and washers and making electrical connection using 1.5sqmm, 3 core multi-stranded copper conductor PVC insulated and over all PVC sheathed cable form light fitting complete all as specified and directed
M & L Sub main wiring with two run single core 6 Sqmm FRLSH copper conductor cable PVC insulated, unsheathed, 1100 V including 25 mm dia concealed on wall/ceiling in ISI marked with all accessories such as Tees, elbows, junction boxes etc, as required fixed on wall alongwith one run of 6 Sqmm single core PVC FRLSH insulated unsheathed copper conductor cable as continuous earth wire and connecting to main switch board / distribution board and testing on completion complete all as directed. Note : Two runs of 6 sqmm and one run of 6 sqmm cable and one run of PVC conduit shall be measured as one RM.
S & F modular switch one way 6 Amps, 1 Module, ISI marked complete all as specified. .
S & F modular socket 6 Amps, 2/3 pin combined modular type 2 Module, ISI marked complete all as specified.
S & F modular socket 6/16 Amps, 2/3 pin combined modular type, 2 Module, ISI marked complete all as specified.
S & F modular switch one way 16 Amps, 1 Module, ISI marked complete all as specified.
S & F ceiling rose 3 terminal / PVC insulated body ISI Marked all as specified..
S & F Modular cover plate with frame & flush box of 8 modules, complete all as specified and as directed.
S & F Modular cover plate with frame & flush box of 6 modules, complete all as specified and as directed.
S & F Modular cover plate with frame & flush box of 4 modules, complete all as specified and as directed.
S & F Modular cover plate with frame& flush box of 3 modules, complete all as specified and as directed.
S & F Modular cover plate with frame & flush box of 2 modules, complete all as specified and as directed.
S & F Modular cover plate with frame & flush box of 1 module, complete all as specified and as directed.
S & F Modular blanking plate1 module, complete all as specified and as directed.
S & F epoxy powder coated sheet metal enclosure for DBs, double door, Single pole and neutral 240V, 12 ways with mounting fitted with bus bar, DIN channel, neutral link and incoming contact complete all as specified and directed.
S & F MCB SP, 6 to 32 Amps, 'C' series 10 KA, 240 Volts and to be housed in DBS including necessry connection complete all as specified and directed.
S & F MCB, 40 to 63 Amps, SPN, 10KA , 415 Volts, C curve complete and to be housed in DBS SPN/TPN including necessary connection complete all as specified and directed.
S & F MCB, 32 Amps,SPN, 10KA , 415 Volts, C curve complete and to be housed in DBS SPN/TPN including necessry connection complete all as specified and directed.
S & F RCBO double pole 30mA for earth leakage, overload and short circuit protection for 40 Amp and to be housed in DBS complete including necessry connection complete all as specified and directed. Note: In case of tripping of RCBOs contractor will responsible for rectifying the wiring defect or replace wiring without any extra cost
S & F Surge Protection Device (SPD) single phase and neutral, T2 -limb, Imax 20 KA per pole complete fixed in distribution board and making connections complete all as specified and directed
Supply and fixing BLDC ceiling fans 1200 mm sweep, 230 volts, remote control operated, having Min air delivery 210 CFM with service value 6.00 BEE complete with blades, down rods, clamps, rubber reel, remote controle unit and all connected accessories, 230 V, Five star rated with brushless direct current motor (BLDC) including making connection by using 3 core flexible copper cable complete all as specified and directed
Supply and fix exhaust fan, steel body AC single Phase, 230V of size 450mm sweep, heavy duty with blades, frame and louvers including suitable size holes and PCC work complete all as specified and directed
Supply and fix exhaust fan, steel body AC single Phase, 230V of size 300mm sweep, with blades, frame and louvers including suitable size holes and PCC work complete all as specified and directed
Material and labour for earthing complete with galvanised mild steel earth plate electrode 600x600x6.0mm thick , burried directly in ground to a depth not less than 2.25 metres deep below ground level with top edge of earth plate not less than 1.5 metre below normal ground level surrounded with adequate quantity of charcoal dust mixed with salt to a packed thickness of 15 cm all around the plate, using Gl wire 4 mm dia as earth strip electrode bolted or rivetted to earth plate at one end and connected to equipments at another end, GI earth strip encased in and including 15mm dia Gl 'light grade' pipe from upper end of earth plate upto equipments, 20 dia bore Gl pipe light grade ' as water pipe from earth chamber to upper edge of earth plate, Test point , Gl funnel with wire mesh fixed on water pipe and PCC 1 : 2 : 4 type B - 1 ( using 20mm graded stone aggregate ) as in pit chamber and RCC pit cover 50mm thick precast RCC 1 : 2 : 4 type B - 1, duly reinforced with MS round bars 6mm dia @ 100 c / c both ways with 10mm dia MS round bar as in lifting handles, excavation, earth work including laying the GI pipe concealed in floor / wall all as described in electric plate of SSR Part I and testing on completion complete all as specified and directed
Supplying and laying of 32 mm outer dia CPVC pipes SDR 11 & Plain CPVC SDR 11 fittings on walls/ceiling or laying in floors/trenches including special fittings like CPVC Brass fittings (Brass elbow, Brass Tee, Male threaded brass adaptor, Female threaded brass adaptor) complete all as specified and directed.
Supply & Fix CPVC ball valves of 32mm outer dia, complete all as specified and as directed.
Supply & Fix 32mm bore Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed complete all as specified and as directed.
Supply & Fix 20 mm bore Stop valves, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions complete all as specified and as directed.
Supply & Fix Stop valves/Angle valves fancy type, chromium plated, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions and of size 15 mm bore complete all as directed and specified
Supply & Fix Bib taps, fancy type, chromium plated cast copper alloy, with crutch or butterfly handle, screwed down, screwed for iron pipe or for brass ferrule and fixed for 15 mm bore pipe complete all as directed and specified
Supply & Fix PVC connections 15mm size with PTMT nuts of length 450mm suitable for hot and cold water complete all as specified and directed.
Pillar taps, fancy type, cast copper alloy, with capstan heads, chromium plated, screwed down high pressure, with or without lettered 'Hot' or 'Cold' with long screwed shanks and fly-nuts, screwed for iron pipe and fixed for 15 mm bore pipe complete all as specified and directed.
Supply & Fix Brass chromium plated shower rose 125mm size suitable for CPVC SDR-11 pipe of outer dia 20mm complete all as specified and directed.
Supply & Fix 20 mm bore Stop valves (concealed type) for hot/cold water, cast copper alloy, screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or for unions complete all as specified and as directed.
Operation and Comprehensive maintenance of spares and SCADA system hardware and software including accessories installed including upgradation, performance monitoring, system backup, patch management, updates, emergency response and troubleshooting and the UPS system provided shall be included in this item including replacement of battery in this period and as specified and directed. The period of first two year shall be covered under Defect Liability Period of contract and all activities including servicing/routine maint/inspection shall be part of it. Note: (i) No charges towards internet and sim card shall be paid extra by the department. The system shall be included with sim and internet activation and periodic recharges during operation & Maintenance period. (ii) Payment shall be restricted to 90% (excluding final bill) at the time of completion of Phase-I & phase-II. During defect liability period, 5% of quoted amount of BOQ Items (SCADA SYSTEM) shall be paid for each DLP (Defect liability period) year on monthly/quarterly/half yearly/yearly basis as per submission of RAR by Contractor. Contractor shall carryout preventive/periodical maintenance during defect liability period of E/M assets created under subject contract.
Operation and Comprehensive maintenance of spares and SCADA system hardware and software including accessories installed including upgradation, performance monitoring, system backup, patch management, updates, emergency response and troubleshooting and the UPS system provided shall be included in this item including replacement of battery for 3rd year maint period after completion of Defect Liability Period and as specified and directed
Operation and Comprehensive maintenance of spares and SCADA system hardware and software including accessories installed including upgradation, performance monitoring, system backup, patch management, updates, emergency response and troubleshooting and the UPS system provided shall be included in this item including replacement of battery for 4th year maint period after completion of Defect Liability Period and as specified and directed
Operation and Comprehensive maintenance of spares and SCADA system hardware and software including accessories installed including upgradation, performance monitoring, system backup, patch management, updates, emergency response and troubleshooting and the UPS system provided shall be included in this item including replacement of battery for 5th year maint period after completion of Defect Liability Period and as specified and directed
JAZZCON ENGINEERS PVT LTD (BID ID -3277161)
ms singh construction (BID ID -3275864)
stage.html
html • 0.05 MB
tech_bid_open.pdf
tech_eval.pdf
fin_bid_open.pdf
boq_comp_chart.xlsx
xlsx
fin_eval.pdf
aoc.pdf
Tap a document below to read it instantly. You can also download everything as a ZIP if you prefer.
details.html
html • 0.03 MB
Download all tender documents and submit your bid
Disclaimer: TenderKart has made every reasonable effort to ensure that the information on this page is accurate and authentic, however it cannot be held liable for any third-party claims or losses or any damages. TenderKart makes no warranty, expressed or implied, as to the results obtained from the use of this information. If you notice any error or omission, please let us know at .